Lucene search
+L

34 matches found

Tenable Nessus
Tenable Nessus
added 2026/06/18 12:00 a.m.15 views

Siemens SIPROTEC 5 Small Space of Random Values (CVE-2024-54017)

Affected devices do not use sufficiently random values to create session identifiers. This could allow an unauthenticated remote attacker to brute force a session identifier and gain read access to limited information from the web server without authorization. This plugin only works with...

6.9CVSS6.6AI score0.00306EPSS
SaveExploits0References6
Tenable Nessus
Tenable Nessus
added 2025/11/18 12:00 a.m.8 views

Siemens SIPROTEC Inadequate Encryption Strength (CVE-2024-38867)

The affected devices are supporting weak ciphers on several ports 443/tcp for web, 4443/tcp for DIGSI 5 and configurable port for syslog over TLS. This could allow an unauthorized attacker in a man-in-the-middle position to decrypt any data passed over to and from those ports. This plugin only...

8.2CVSS7.1AI score0.00205EPSS
SaveExploits0References7
Tenable Nessus
Tenable Nessus
added 2025/11/18 12:00 a.m.7 views

Siemens SIPROTEC 5 Allocation of Resources Without Limits or Throttling (CVE-2025-40570)

Affected devices do not properly limit the bandwidth for incoming network packets over their local USB port. This could allow an attacker with physical access to send specially crafted packets with high bandwidth to the affected devices thus forcing them to exhaust their memory and stop respondin...

2.4CVSS5.8AI score0.00197EPSS
SaveExploits0References6
CNVD
CNVD
added 2025/08/22 12:00 a.m.9 views

Siemens SIPROTEC 5 Compact 7SX800 (CP050) Local USB Port Network Packet Bandwidth Limit Improperly Vulnerability

The SIPROTEC 5 Compact 7SX800 CP050 offers a range of integrated protection, control, measurement and automation functions for substations and other applications. The Siemens SIPROTEC 5 Compact 7SX800 CP050 suffers from an improper bandwidth limitation of network packets on the local USB port...

6.7AI score
SaveExploits0Affected Software1
CISA
CISA
added 2025/07/10 12:00 p.m.25 views

CISA Releases Thirteen Industrial Control Systems Advisories

CISA released thirteen Industrial Control Systems ICS advisories on July 10, 2025. These advisories provide timely information about current security issues, vulnerabilities, and exploits surrounding ICS. ICSA-25-191-01 Siemens SINEC NMS ICSA-25-191-02 Siemens Solid Edge ICSA-25-191-03 Siemens TI...

7.1AI score
SaveExploits0References13
Positive Technologies
Positive Technologies
added 2025/07/08 12:00 a.m.14 views

PT-2025-28400 · Siemens · Siprotec 5 7Sa82 +16

Name of the Vulnerable Software and Affected Versions: SIPROTEC 5 6MD84 CP300 All versions SIPROTEC 5 6MD85 CP300 All versions SIPROTEC 5 6MD86 CP300 All versions SIPROTEC 5 6MD89 CP300 All versions SIPROTEC 5 6MD89 CP300 V9.6 All versions SIPROTEC 5 6MU85 CP300 All versions SIPROTEC 5 7KE85 CP30...

6CVSS6AI score0.00277EPSS
SaveExploits0References3
ICS
ICS
added 2025/07/08 12:00 a.m.18 views

Siemens SIPROTEC 5

SUMMARY A sensitive data exposure vulnerability in SIPROTEC 5 can allow an attacker to retrieve sensitive session data from browser history, logs, or other storage mechanisms, potentially leading to unauthorized access. Siemens is preparing fix versions and recommends countermeasures for...

6CVSS7.1AI score0.00277EPSS
SaveExploits0References10
Tenable Nessus
Tenable Nessus
added 2025/02/20 12:00 a.m.7 views

Siemens SIPROTEC 5 Devices Use of Default Credentials (CVE-2024-54015)

Affected devices do not properly validate SNMP GET requests. This could allow an unauthenticated, remote attacker to retrieve sensitive information of the affected devices with SNMPv2 GET requests using default credentials. This plugin only works with Tenable.ot. Please visit...

8.7CVSS5.6AI score0.00584EPSS
SaveExploits0References3
Tenable Nessus
Tenable Nessus
added 2025/02/18 12:00 a.m.6 views

Siemens SIPROTEC 5 Cleartext Storage of Sensitive Information (CVE-2024-53651)

Affected devices do not encrypt certain data within the on-board flash storage on their PCB. This could allow an attacker with physical access to read the entire filesystem of the device. This plugin only works with Tenable.ot. Please visit https://www.tenable.com/products/tenable-ot for more...

5.1CVSS5.5AI score0.00163EPSS
SaveExploits0References3
Tenable Nessus
Tenable Nessus
added 2025/02/18 12:00 a.m.7 views

Siemens SIPROTEC 5 Active Debug Code (CVE-2024-53648)

Affected devices do not properly limit access to a development shell accessible over a physical interface. This could allow an unauthenticated attacker with physical access to the device to execute arbitrary commands on the device. This plugin only works with Tenable.ot. Please visit...

7CVSS5.4AI score0.00314EPSS
SaveExploits0References3
CNNVD
CNNVD
added 2025/02/11 12:00 a.m.16 views

Siemens SIPROTEC 5 安全漏洞

SIPROTEC 5 devices provide a range of integrated protection, control, measurement and automation functions for substations and other applications. A sensitive information plaintext storage vulnerability exists in Siemens SIPROTEC 5. The vulnerability arises because affected SIPROTEC 5 devices do...

5.1CVSS6.1AI score0.00163EPSS
SaveExploits0References1
CNVD
CNVD
added 2025/02/11 12:00 a.m.45 views

Siemens SIPROTEC 5 Sensitive Information Plaintext Storage Vulnerability

SIPROTEC 5 devices provide a range of integrated protection, control, measurement and automation functions for substations and other applications. A sensitive information plaintext storage vulnerability exists in Siemens SIPROTEC 5. The vulnerability arises because affected SIPROTEC 5 devices do...

5.1CVSS6.1AI score0.00163EPSS
SaveExploits0References1
CNNVD
CNNVD
added 2025/02/11 12:00 a.m.13 views

Siemens SIPROTEC 5 安全漏洞

Siemens SIPROTEC 5 is a multifunction relay from Siemens Germany. A security vulnerability exists in the Siemens SIPROTEC 5 that stems from the affected device not properly restricting access to the development shell through the physical interface. This could allow an unauthenticated attacker to...

7CVSS7AI score0.00314EPSS
SaveExploits0References2
ICS
ICS
added 2025/02/11 12:00 a.m.16 views

Siemens SIPROTEC 5 Devices

SUMMARY An information disclosure vulnerability in SIPROTEC 5 devices could allow an unauthenticated, remote attacker to retrieve sensitive information of the device. Siemens has released new versions for several affected products and recommends to update to the latest versions. Siemens is...

8.7CVSS7AI score0.00584EPSS
SaveExploits0References10
Tenable Nessus
Tenable Nessus
added 2025/01/20 12:00 a.m.9 views

Siemens SIPROTEC 5 Products Files or Directories Accessible to External Parties (CVE-2024-53649)

Affected devices do not properly limit the path accessible via their webserver. This could allow an authenticated remote attacker to read arbitrary files from the filesystem of affected devices. This plugin only works with Tenable.ot. Please visit https://www.tenable.com/products/tenable-ot for...

7.1CVSS5.5AI score0.00616EPSS
SaveExploits0References3
The Hacker News
The Hacker News
added 2024/10/09 3:33 p.m.40 views

Researchers Uncover Major Security Vulnerabilities in Industrial MMS Protocol Libraries

Details have emerged about multiple security vulnerabilities in two implementations of the Manufacturing Message Specification MMS protocol that, if successfully exploited, could have severe impacts in industrial environments. "The vulnerabilities could allow an attacker to crash an industrial...

10CVSS8.4AI score0.05057EPSS
SaveExploits2
Tenable Nessus
Tenable Nessus
added 2023/01/05 12:00 a.m.26 views

Siemens SIPROTEC 5 Devices Uncontrolled Resource Consumption (CVE-2022-45044)

Affected devices do not properly restrict secure client-initiated renegotiations within the SSL and TLS protocols. This could allow an attacker to create a denial of service condition on the ports 443/tcp and 4443/tcp for the duration of the attack. This plugin only works with Tenable.ot. Please...

7.5CVSS5.7AI score0.00699EPSS
SaveExploits0References3
Tenable Nessus
Tenable Nessus
added 2022/02/07 12:00 a.m.31 views

Siemens SIPROTEC 5 and DIGSI 5 Improper Input Validation (CVE-2019-10931)

A vulnerability has been identified in All other SIPROTEC 5 device types with CPU variants CP300 and CP100 and the respective Ethernet communication modules All versions , DIGSI 5 engineering software All versions V7.90, SIPROTEC 5 device types 6MD85, 6MD86, 6MD89, 7UM85, 7SA87, 7SD87, 7SL87,...

7.5CVSS7.1AI score0.01518EPSS
SaveExploits0References3
Tenable Nessus
Tenable Nessus
added 2022/02/07 12:00 a.m.23 views

Siemens SIPROTEC 5 Improper Input Validation (CVE-2021-37206)

A vulnerability has been identified in SIPROTEC 5 relays with CPU variants CP050 All versions V8.80, SIPROTEC 5 relays with CPU variants CP100 All versions V8.80, SIPROTEC 5 relays with CPU variants CP300 All versions V8.80. Received webpackets are not properly processed. An unauthenticated remot...

7.5CVSS7.2AI score0.01433EPSS
SaveExploits0References3
CNVD
CNVD
added 2021/09/15 12:00 a.m.38 views

Siemens SIPROTEC 5 Improper Input Validation Vulnerability

Siemens SIPROTEC 5 is a multifunction relay from Siemens, Germany. Siemens SIPROTEC 5 suffers from an Input Authentication Error vulnerability that arises from incoming webpackets that are not handled correctly. An unauthenticated, remote attacker with access to any Ethernet interface could explo...

7.5CVSS7.5AI score0.01433EPSS
SaveExploits0References1
Rows per page
Query Builder