901 matches found
CVE-2019-14930
CVE-2019-14930 affects Mitsubishi Electric Europe B.V. ME-RTU (through 2.02) and INEA ME-RTU (through 3.0). The issue arises from undocumented hard-coded credentials for root, ineaadmin, mitsadmin, and maint, enabling unauthenticated access to the RTU. Additionally, ineaadmin and mitsadmin can es...
CVE-2019-14926
An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. Hard-coded SSH keys allow an attacker to gain unauthorised access or disclose encrypted data on the RTU due to the keys not being regenerated on initial installation or with...
CVE-2019-14926
CVE-2019-14926 concerns hard-coded SSH keys in Mitsubishi Electric ME-RTU (firmware up to 2.02) and INEA ME-RTU (up to 3.0). The root cause is static private-key values stored in /etc/ssh/ssh_host_rsa_key, /etc/ssh/ssh_host_ecdsa_key, and /etc/ssh/ssh_host_dsa_key that are publicly available from...
CVE-2019-14928
The CVE-2019-14928 issue affects Mitsubishi Electric Europe B.V. ME-RTU devices up to firmware 2.02 and INEA ME-RTU devices up to 3.0, with stored cross-site scripting (XSS) vulnerabilities in the web interface. The vulnerability arises from insufficient input validation, e.g., the SerialInitialM...
CVE-2019-14928
An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. A number of stored cross-site script XSS vulnerabilities allow an attacker to inject malicious code directly into the application. An example input variable vulnerable to...
CVE-2019-14927
Mitsubishi Electric smartRTU (firmware prior to Version 3.3 ) and INEA ME-RTU (firmware prior to Version 3.0 ) are vulnerable to an unauthenticated remote configuration download vulnerability (CVE-2019-14927 ). An attacker can exploit this improper access control by accessing a specific URL to do...
CVE-2019-14927
An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. An unauthenticated remote configuration download vulnerability allows an attacker to download the smartRTU's configuration file which contains data such as usernames,...
CVE-2019-14931
Mitsubishi Electric Europe B.V. smartRTU (prior to version 3.3) and INEA ME-RTU (prior to version 3.0) are vulnerable to an unauthenticated remote OS command injection (CWE-78). The root cause is the improper neutralization of special characters, specifically the shell command separator (;), when...
CVE-2019-14931
An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. An unauthenticated remote OS Command Injection vulnerability allows an attacker to execute arbitrary commands on the RTU due to the passing of unsafe user supplied data to t...
PT-2019-13870 · Mitsubishi · Me-Rtu
Name of the Vulnerable Software and Affected Versions: Mitsubishi Electric Europe B.V. ME-RTU devices versions 2.02 and earlier INEA ME-RTU devices versions 3.0 and earlier Description: An issue allows an attacker to inject malicious code directly into the application through stored cross-site...
CVE-2019-14926: Use of Hard-coded Credentials
An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. Hard-coded SSH keys allow an attacker to gain unauthorised access or disclose encrypted data on the RTU due to the keys not being regenerated on initial installation or with...
PT-2019-13868 · Inea · Me-Rtu
Name of the Vulnerable Software and Affected Versions: Mitsubishi Electric Europe B.V. ME-RTU devices versions 2.02 and earlier INEA ME-RTU devices versions 3.0 and earlier Description: An issue allows an attacker to gain unauthorized access or disclose encrypted data on the RTU due to hard-coded...
PT-2019-13867 · Mitsubishi · Me-Rtu
Name of the Vulnerable Software and Affected Versions: Mitsubishi Electric Europe B.V. ME-RTU devices versions 2.02 and earlier INEA ME-RTU devices versions 3.0 and earlier Description: An issue allows an attacker to read sensitive configuration settings due to insecure permission assignment. The...
CVE-2019-14930: Use of Hard-coded Credentials
An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. Undocumented hard-coded user passwords for root, ineaadmin, mitsadmin, and maint could allow an attacker to gain unauthorised access to the RTU. Also, the accounts ineaadmin...
CVE-2019-14928: Improper Neutralization of Input During Web Page Generation
An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. A number of stored cross-site script XSS vulnerabilities allow an attacker to inject malicious code directly into the application. An example input variable vulnerable to...
CVE-2019-14927: Missing Authentication for Critical Function
An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. An unauthenticated remote configuration download vulnerability allows an attacker to download the smartRTU's configuration file which contains data such as usernames,...
CVE-2019-14929: Insufficiently Protected Credentials
An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. Stored cleartext passwords could allow an unauthenticated attacker to obtain configured username and password combinations on the RTU due to the weak credentials management ...
CVE-2019-14925: Incorrect Default Permissions
An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. A world-readable /usr/smartrtu/init/settings.xml configuration file on the file system allows an attacker to read sensitive configuration settings such as usernames,...
CVE-2019-14931: Improper Neutralization of Special Elements used in an OS Command
An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. An unauthenticated remote OS Command Injection vulnerability allows an attacker to execute arbitrary commands on the RTU due to the passing of unsafe user supplied data to t...
Schneider Electric BMXNOR0200H Ethernet/Serial RTU Module Access Control Error Vulnerability
The Schneider Electric BMXNOR0200H Ethernet/Serial RTU module is an Ethernet Serial RTU Remote Terminal Unit module from Schneider Electric, France. An access control error vulnerability exists in the Schneider Electric BMXNOR0200H Ethernet/Serial RTU module. The vulnerability arises from the...