1219 matches found
Rockwellautomation Rsview32 Unspecified Vulnerability
Rockwell Automation RSView32 7.60.00 aka CPR9 SR4 and earlier does not properly encrypt credentials, which allows local users to obtain sensitive information by reading a file and conducting a decryption attack. File data ot500222.nasl...
Windriver Vxworks Improper Restriction of Operations within the Bounds of a Memory Buffer
Wind River VxWorks 6.6 through 6.9 has a Buffer Overflow in the DHCP client component. There is an IPNET security vulnerability: Heap overflow in DHCP Offer/ACK parsing inside ipdhcpc. File data ot500061.nasl...
Abb Pm554-tp-eth Uncontrolled Resource Consumption
ABB, Phoenix Contact, Schneider Electric, Siemens, WAGO - Programmable Logic Controllers, multiple versions. Researchers have found some controllers are susceptible to a denial-of-service attack due to a flood of network packets. File data ot500200.nasl...
Schneider-electric Modicon Improper Check for Unusual or Exceptional Conditions
An Improper Check for Unusual or Exceptional Conditions vulnerability exists in Schneider Electric's Modicon M221 product all references, all versions prior to firmware V1.6.2.0. The vulnerability allows unauthorized users to remotely reboot Modicon M221 using crafted programing protocol frames...
Schneider-electric Modicon Improper Check for Unusual or Exceptional Conditions
A CWE-248 Uncaught Exception vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause a denial of Service when sending invalid debug parameters to the controller over Modbus. File data ot500243.nasl...
Siemens Simatic Unspecified Vulnerability
Open redirect vulnerability in the integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to redirect users to arbitrary web sites and conduct phishing attacks via unspecified vectors. File data ot500265.nasl...
Rockwellautomation Ethernet\/ip Improper Input Validation
Rockwell Automation EtherNet/IP Web Server Modules 1756-EWEB includes 1756-EWEBK Version 5.001 and earlier, and CompactLogix 1768-EWEB Version 2.005 and earlier. A remote attacker could send a crafted UDP packet to the SNMP service causing a denial-of-service condition to occur until the affected...
Schneider-electric Monitor Improper Restriction of Operations within the Bounds of a Memory Buffer
Buffer overflow in the UnitelWay Windows Device Driver, as used in Schneider Electric Unity Pro 6 and earlier, OPC Factory Server 3.34, Vijeo Citect 7.20 and earlier, Telemecanique Driver Pack 2.6 and earlier, Monitor Pro 7.6 and earlier, and PL7 Pro 4.5 and earlier, allows local users, and...
Schneider-electric Modicon Improper Check for Unusual or Exceptional Conditions
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in BMXNOR0200H Ethernet / Serial RTU module all firmware versions and Modicon M340 controller all firmware versions, which could cause denial of service when truncated SNMP packets on port 161/UDP are received by...
Enea Ose Unspecified Vulnerability
The Emerson Process Management ROC800 RTU with software 3.50 and earlier, DL8000 RTU with software 2.30 and earlier, and ROC800L RTU with software 1.20 and earlier have hardcoded credentials in a ROM, which makes it easier for remote attackers to obtain shell access to the underlying OS by...
Schneider-electric Modicon Improper Access Control
A CWE-284: Improper Access Control vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause a remote code execution by overwriting configuration settings of the controller over Modbus. File data ot500071.nasl...
Schneider-electric Modicom URL Redirection to Untrusted Site ('Open Redirect')
A URL Redirection to Untrusted Site vulnerability exists in the embedded web servers in all Modicon M340, Premium, Quantum PLCs and BMXNOR0200 where a user clicking on a specially crafted link can be redirected to a URL of the attacker's choosing. File data ot500231.nasl...
Schneider-electric Modicom Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting')
An Improper Neutralization of Input During Web Page Generation 'Cross-site Scripting' vulnerability exists in the embedded web servers in all Modicon M340, Premium, Quantum PLCs and BMXNOR0200 allowing an attacker to craft a URL containing JavaScript that will be executed within the user's browse...
Yokogawa B\/m Improper Access Control
License Manager Service of YOKOGAWA products CENTUM VP R5.01.00 - R6.06.00, CENTUM VP Entry Class R5.01.00 - R6.06.00, ProSafe-RS R3.01.00 - R4.04.00, PRM R4.01.00 - R4.02.00, B/M9000 VPR7.01.01 - R8.02.03 allows remote attackers to bypass access restriction to send malicious files to the PC wher...
Schneider-electric Modicon Exposure of Sensitive Information to an Unauthorized Actor
A CWE-200: Information Exposure vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause the disclosure of SNMP information when reading variables in the controller using Modbus. File data ot500316.nasl...
Rockwellautomation Controllogix Exposure of Sensitive Information to an Unauthorized Actor
The web interface in the Rockwell Automation ControlLogix 1756-ENBT/A EtherNet/IP Bridge Module allows remote attackers to obtain "internal web page information" and "internal information about the module" via unspecified vectors. NOTE: this may overlap CVE-2002-1603. File data ot500031.nasl...
Rockwellautomation Arena Access of Uninitialized Pointer
In Rockwell Automation Arena Simulation Software Cat. 9502-Ax, Versions 16.00.00 and earlier, a maliciously crafted Arena file opened by an unsuspecting user may result in the use of a pointer that has not been initialized. File data ot500054.nasl...
Rockwellautomation Rslinx Improper Input Validation
LogReceiver.exe in Rockwell Automation RSLinx Enterprise CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service service outage via a zero-byte UDP packet that is not properly handled by Logger.dll. File data ot500259.n...
Schneider-electric Modicon Improper Restriction of Operations within the Bounds of a Memory Buffer
Multiple buffer overflows in Schneider Electric Modicon Quantum PLC allow remote attackers to cause a denial of service via malformed requests to the 1 FTP server or 2 HTTP server. File data ot500027.nasl...
Schneider-electric Modicom Weak Password Recovery Mechanism for Forgotten Password
An Unverified Password Change vulnerability exists in the embedded web servers in all Modicon M340, Premium, Quantum PLCs and BMXNOR0200 which could allow an unauthenticated remote user to access the change password function of the web server File data ot500276.nasl...