1219 matches found
Emerson Dl Improper Neutralization of Special Elements used in a Command ('Command Injection')
Emerson Process Management ROC800 RTU with software 3.50 and earlier, DL8000 RTU with software 2.30 and earlier, and ROC800L RTU with software 1.20 and earlier allows remote attackers to execute arbitrary commands via a TCP replay attack. File data ot500187.nasl...
Schneider-electric Modicon Improper Handling of Exceptional Conditions
A CWE-248: Uncaught Exception vulnerability exists in Modicon M580, Modicon M340, Modicon BMxCRA and 140CRA modules all firmware versions, which could cause a Denial of Service attack on the PLC when upgrading the firmware with no firmware image inside the package using FTP protocol. File data...
Siemens Eta4 Unspecified Vulnerability
An issue was discovered in Siemens ETA4 firmware all versions prior to Revision 08 of the SM-2558 extension module for: SICAM AK, SICAM TM 1703, SICAM BC 1703, and SICAM AK 3. Specially crafted packets sent to Port 2404/TCP could cause the affected device to go into defect mode. A cold start migh...
Siemens Apogee Improper Authentication
A vulnerability has been identified in Siemens APOGEE PXC and TALON TC BACnet Automation Controllers in all versions V3.5. An attacker with network access to the integrated web server 80/tcp and 443/tcp could bypass the authentication and download sensitive information from the device. File data...
Schneider-electric Modicom Improper Check for Unusual or Exceptional Conditions
An Improper Check for Unusual or Exceptional Conditions vulnerability exists in the embedded web servers in all Modicon M340, Premium, Quantum PLCs and BMXNOR0200 where an unauthenticated user can send a specially crafted XML data via a POST request to cause the web server to become unavailable...
Siemens Simatic Unspecified Vulnerability
Siemens SIMATIC S7-1200 CPU PLC devices with firmware before 4.0 allow remote attackers to cause a denial of service defect-mode transition via crafted PROFINET packets, a different vulnerability than CVE-2014-2253. File data ot500177.nasl...
Omron Cx-programmer Exposure of Sensitive Information to an Unauthorized Actor
Omron CX-One CX-Programmer before 9.6, CJ2M PLC devices before 2.1, and CJ2H PLC devices before 1.5 rely on cleartext password transmission, which allows remote attackers to obtain sensitive information by sniffing the network during a PLC unlock request. File data ot500217.nasl...
Rockwellautomation Micrologix Improper Input Validation
An exploitable denial of service vulnerability exists in the Ethernet functionality of the Allen Bradley Micrologix 1400 Series B FRN 21.2 and below. A specially crafted packet can cause a device power cycle resulting in a fault state and deletion of ladder logic. An attacker can send one...
Rockwellautomation Micrologix Improper Restriction of Operations within the Bounds of a Memory Buffer
Allen-Bradley MicroLogix 1100 devices before B FRN 15.000 and 1400 devices before B FRN 15.003 allow remote attackers to cause a denial of service memory corruption and device crash via a crafted HTTP request. File data ot500089.nasl...
Siemens Simatic Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting')
Cross-site scripting XSS vulnerability in the integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to inject arbitrary web script or HTML via unspecified vectors. File data ot500137.nasl...
Schneider-electric Modicom Weak Password Recovery Mechanism for Forgotten Password
An Unverified Password Change vulnerability exists in the embedded web servers in all Modicon M340, Premium, Quantum PLCs and BMXNOR0200 which could allow an unauthenticated remote user to access the change password function of the web server File data ot500276.nasl...
Schneider-electric Modicon Improper Handling of Exceptional Conditions
A CWE-248: Uncaught Exception vulnerability exists in Modicon M580, Modicon M340, Modicon BMxCRA and 140CRA modules all firmware versions, which could cause a Denial of Service attack on the PLC when upgrading the firmware with a missing web server image inside the package using FTP protocol. Fil...
Enea Ose Improper Control of Generation of Code ('Code Injection')
The TFTP server on the Emerson Process Management ROC800 RTU with software 3.50 and earlier, DL8000 RTU with software 2.30 and earlier, and ROC800L RTU with software 1.20 and earlier allows remote attackers to upload files and consequently execute arbitrary code via unspecified vectors. File data...
Schneider-electric Modicon Unspecified Vulnerability
In Modicon Quantum all firmware versions, CWE-264: Permissions, Privileges, and Access Control vulnerabilities could cause a denial of service or unauthorized modifications of the PLC configuration when using Ethernet/IP protocol. File data ot500069.nasl...
Rockwellautomation Rslogix Unspecified Vulnerability
Rockwell Automation RSLogix 5000 7 through 20.01, and 21.0, does not properly implement password protection for .ACD files aka project files, which allows local users to obtain sensitive information or modify data via unspecified vectors. File data ot500148.nasl...
Schneider-electric Modicom Improper Neutralization of CRLF Sequences in HTTP Headers ('HTTP Response Splitting')
Improper Neutralization of CRLF Sequences in HTTP Headers 'HTTP Response Splitting' vulnerability exists in the embedded web servers in all Modicon M340, Premium, Quantum PLCs and BMXNOR0200 where a denial of service can occur for 1 minute by sending a specially crafted HTTP request. File data...
Siemens Simatic Unspecified Vulnerability
Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service defect-mode transition via crafted HTTPS packets. File data ot500037.nasl...
Schneider-electric Modicon Unspecified Vulnerability
A CWE-248: Uncaught Exception vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause denial of service when reading memory blocks with an invalid data size or with an invalid data offset in the controller over Modbus. File da...
Schneider-electric Modicon Improper Input Validation
A CWE-248: Uncaught Exception vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause denial of service when an invalid private command parameter is sent to the controller over Modbus. File data ot500324.nasl...
Schneider-electric Modicon Improper Check for Unusual or Exceptional Conditions
An Improper Check for Unusual or Exceptional Conditions CWE-754 vulnerability exists in Modicon Quantum 140 NOE771x1 version 6.9 and earlier, which could cause denial of service when the module receives an IP fragmented packet with a length greater than 65535 bytes. The module then requires a pow...