CVE-2021-37206
A vulnerability has been identified in SIPROTEC 5 relays with CPU variants CP050 All versions V8.80, SIPROTEC 5 relays with CPU variants CP100 All versions V8.80, SIPROTEC 5 relays with CPU variants CP300 All versions V8.80. Received webpackets are not properly processed. An unauthenticated remot...
CVE-2021-33720
A vulnerability has been identified in SIPROTEC 5 relays with CPU variants CP050 All versions V8.80, SIPROTEC 5 relays with CPU variants CP100 All versions V8.80, SIPROTEC 5 relays with CPU variants CP300 All versions V8.80. Specially crafted packets sent to port 4443/tcp could cause a...
CVE-2021-33720
Siemens SIPROTEC 5 relays with CPU variants CP050, CP100, or CP300 (all versions before 8.80) are affected by CVE-2021-33720 a classic buffer overflow (Buffer copy without checking size) caused by specially crafted packets sent to port 4443/TCP. This can cause a Denial-of-Service condition; ICS a...
CVE-2021-33719
A vulnerability has been identified in SIPROTEC 5 relays with CPU variants CP050 All versions V8.80, SIPROTEC 5 relays with CPU variants CP100 All versions V8.80, SIPROTEC 5 relays with CPU variants CP300 All versions V8.80. Specially crafted packets sent to port 4443/tcp could cause a...
CVE-2021-33719
The CVE-2021-33719 issue affects SIPROTEC 5 relays with CPU variants CP050, CP100, and CP300, where specially crafted packets to TCP port 4443 may cause a Denial-of-Service or remote code execution. Affected versions are all before V8.80. Siemens has released updates to v8.80 or later for CP050/C...
Siemens SIPROTEC 5 relays (Update A)
1. EXECUTIVE SUMMARY CVSS v3 9.8 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: SIPROTEC 5 relays Vulnerabilities: Classic Buffer Overflow 2. UPDATE INFORMATION This updated advisory is a follow-up to the original advisory titled ICSA-21-257-10 Siemens SIPROTEC 5...
Siemens SIPROTEC 5 代码注入漏洞
Siemens SIPROTEC 5 is a multifunction relay from Siemens, Germany. A buffer overflow vulnerability exists in the Siemens SIPROTEC 5 relays, which can be exploited by an attacker to send a constructed packet to port 4443/TCP, resulting in a denial of service condition...
Siemens SIPROTEC 5 (Update A)
1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: SIPROTEC 5 Vulnerability: Improper Input Validation 2. UPDATE INFORMATION This updated advisory is a follow-up to the original advisory titled ICSA-21-257-16 Siemens SIPROTEC 5 that...
Siemens SIPROTEC 5输入验证错误漏洞
Siemens SIPROTEC 5 is a multifunction relay from Siemens, Germany. Siemens SIPROTEC 5 suffers from an Input Authentication Error vulnerability that arises from incoming webpackets that are not handled correctly. An unauthenticated, remote attacker with access to any Ethernet interface could explo...
Siemens SIPROTEC 5 代码注入漏洞
Siemens SIPROTEC 5 is a multifunction relay from Siemens, Germany. A buffer overflow vulnerability exists in Siemens SIPROTEC 5 relays. An attacker can exploit the vulnerability by sending a constructed packet to port 4443/TCP, resulting in a denial of service condition or remote code execution...
The vulnerabilities of SIPROTEC relay protection devices stem from insufficient validation of input data, allowing attackers to trigger malfunctions in the service.
The vulnerability of SIPROTEC relay protection devices is related to insufficient verification of input data. Exploiting this vulnerability can allow attackers to trigger a service failure using specially created packets sent to port 50000/UDP...
Siemens Siprotec Improper Input Validation
A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules All versions. Specially crafted packets sent to port 50000/UDP of the EN100 Ethernet communication modules could cause a Denial-of-Service of the affected device. A...
CVE-2019-19279
A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules All versions. Specially crafted packets sent to port 50000/UDP of the EN100 Ethernet communication modules could cause a Denial-of-Service of the affected device. A...
Code injection
A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules All versions. Specially crafted packets sent to port 50000/UDP of the EN100 Ethernet communication modules could cause a Denial-of-Service of the affected device. A...
CVE-2019-19279
CVE-2019-19279 affects Siemens SIPROTEC 4 and SIPROTEC Compact relays with EN100 Ethernet modules (all versions). The issue is caused by sending specially crafted packets to UDP port 50000, which can trigger a network-denial-of-service on the affected device. Recovery requires a manual reboot. At...
CVE-2019-19279
A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules All versions. Specially crafted packets sent to port 50000/UDP of the EN100 Ethernet communication modules could cause a Denial-of-Service of the affected device. A...
SIEMENS SIPROTEC 4 and SIPROTEC Compact Relay Families Denial of Service Vulnerability
SIEMENS SIPROTEC 4 and SIPROTEC Compact Relay Families are offering integrated protection, control, measurement and automation functions for substations and other applications. A denial of service vulnerability exists in SIEMENS SIPROTEC 4 and SIPROTEC Compact Relay Families. An attacker can...
Siemens SIPROTEC 4 and SIPROTEC Compact
1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable remotely Vendor: Siemens Equipment: SIPROTEC 4 and SIPROTEC Compact Vulnerability: Improper Input Validation 2. RISK EVALUATION This vulnerability could allow an attacker to conduct a denial-of-service attack over the network. 3. TECHNICAL...
Siemens EN100 Ethernet Module (Update A)
1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable remotely/low skill level to exploit Vendor: Siemens Equipment: EN100 Ethernet Module Vulnerabilities: Improper Restriction of Operations within the Bounds of a Memory Buffer, Cross-site Scripting, Relative Path Traversal 2. UPDATE...
The vulnerability of the DIGSI 5 software and SIPROTEC 5 devices, which stems from insufficient validation of input data, allows attackers to trigger service interruptions.
The vulnerability of the DIGSI 5 software and the SIPROTEC 5 devices is related to insufficient verification of input data. Exploiting this vulnerability can allow a malicious actor to cause service failures by sending specially crafted packets to port 443/TCP...