Design/Logic Flaw
The database server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote authenticated users to gain privileges via a request to TCP port 1433...
Cross site request forgery (csrf)
The WebNavigator server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote attackers to obtain sensitive information via an HTTP request...
Hardcoded credentials
The Project administration application in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, has a hardcoded encryption key, which allows remote attackers to obtain sensitive information by extracting this key from another product installation and then employing this key during...
CVE-2014-4685
Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows local users to gain privileges by leveraging weak system-object access control...
CVE-2014-4685
CVE-2014-4685 affects Siemens SIMATIC WinCC prior to 7.3 (used in PCS7). Root cause: weak system-object access control enabling local privilege escalation for local users. Siemens released fixes in WinCC 7.3 (and PCS7 8.1); upgrading is advised. Other sources note mitigation steps and a broader s...
CVE-2014-4684
The database server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote authenticated users to gain privileges via a request to TCP port 1433...
CVE-2014-4683
The WebNavigator server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote authenticated users to gain privileges via a 1 HTTP or 2 HTTPS request...
CVE-2014-4686
Siemens SIMATIC WinCC (before 7.3) contains a hard-coded encryption key in the Project administration component, enabling remote attackers to extract the key from another installation and use it to sniff traffic on TCP port 1030. This can lead to credential exposure and elevated privileges. Publi...
CVE-2014-4686
The Project administration application in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, has a hardcoded encryption key, which allows remote attackers to obtain sensitive information by extracting this key from another product installation and then employing this key during...
Siemens SIMATIC WinCC Flexible (Runtime) Multiple Vulnerabilities
No description provided by source. Luigi Auriemma Application: Siemens SIMATIC WinCC flexible Runtime http://www.automation.siemens.com/mcms/human-machine-interface/en/visualization-software/wincc-flexible/wincc-flexible-runtime/Pages/Default.aspx Versions: 2008 SP2 + security patch 1 Platforms:...
Siemens SIMATIC WinCC Vulnerabilities (Update A)
OVERVIEW This updated advisory is a follow-up to the original advisory titled ICSA-14-205-02 Siemens SIMATIC WinCC Vulnerabilities that was published July 24, 2014, on the NCCIC/ICS-CERT web site. Researchers Sergey Gordeychik, Alexander Tlyapov, Dmitry Nagibin, and Gleb Gritsai of Positive...
PT-2014-16: Privilege Gaining in Siemens SIMATIC WinCC
The specialists of the Positive Research center have detected a Privilege Gaining vulnerability in SIMATIC WinCC. A hard coded encryption key could allow privilege escalation in the WinCC Project administration application if its network communication on port 1030/tcp of a legitimate user can be...
CVE-2014-1699
Siemens SIMATIC WinCC OA before 3.12 P002 January allows remote attackers to cause a denial of service monitoring-service outage via malformed HTTP requests to port 4999...
Design/Logic Flaw
Siemens SIMATIC WinCC OA before 3.12 P002 January uses a weak hash algorithm for passwords, which makes it easier for remote attackers to obtain access via a brute-force attack...
CVE-2014-1699
CVE-2014-1699 affects Siemens SIMATIC WinCC OA before version 3.12 P002 January. The vulnerability resides in the integrated Web server on port 4999/TCP and stems from improper input validation, allowing remote attackers to trigger a denial of service (monitoring-service outage) by sending malfor...
CVE-2014-1696
Siemens SIMATIC WinCC OA before 3.12 P002 January uses a weak hash algorithm for passwords, which makes it easier for remote attackers to obtain access via a brute-force attack...
CVE-2014-1698
Directory traversal vulnerability in Siemens SIMATIC WinCC OA before 3.12 P002 January allows remote attackers to read arbitrary files via crafted packets to TCP port 4999...
CVE-2014-1699
Siemens SIMATIC WinCC OA before 3.12 P002 January allows remote attackers to cause a denial of service monitoring-service outage via malformed HTTP requests to port 4999...
CVE-2014-1697
The integrated web server in Siemens SIMATIC WinCC OA before 3.12 P002 January allows remote attackers to execute arbitrary code via crafted packets to TCP port 4999...