Rockwellautomation Micrologix Unspecified Vulnerability

2019-11-0800:00:00
This script is Copyright (C) 2019-2021 and is owned by Tenable, Inc. or an Affiliate thereof.
www.tenable.com
10

0.001 Low

EPSS

Percentile

43.5%

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE Description: Live rung edits are able to be made by an unauthenticated user allowing for addition, deletion, or modification of existing ladder logic. Additionally, faults and cpu state modification can be triggered if specific ladder logic is used.

File data ot_500208.nasl
VendorProductVersionCPE
rockwellautomationmicrologix_1400_b_firmware*cpe:2.3:o:rockwellautomation:micrologix_1400_b_firmware:*:*:*:*:*:*:*:*