Lucene search

K
cve[email protected]CVE-2017-14467
HistoryApr 05, 2018 - 9:29 p.m.

CVE-2017-14467

2018-04-0521:29:00
web.nvd.nist.gov
53
cve-2017-14467
access control
vulnerability
allen bradley
micrologix 1400
ladder logic
unauthenticated user
data disclosure
program modification

7.5 High

CVSS2

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

PARTIAL

Availability Impact

PARTIAL

AV:N/AC:L/Au:N/C:P/I:P/A:P

9.8 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

9.2 High

AI Score

Confidence

High

0.001 Low

EPSS

Percentile

43.5%

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE Description: Live rung edits are able to be made by an unauthenticated user allowing for addition, deletion, or modification of existing ladder logic. Additionally, faults and cpu state modification can be triggered if specific ladder logic is used.

Affected configurations

Vulners
NVD
Node
talosallen_bradleyRangeAllen Bradley Micrologix 1400 Series B FRN 21.2
OR
talosallen_bradleyRangeAllen Bradley Micrologix 1400 Series B FRN 21.0
OR
talosallen_bradleyRangeAllen Bradley Micrologix 1400 Series B FRN 15

CNA Affected

[
  {
    "product": "Allen Bradley",
    "vendor": "Talos",
    "versions": [
      {
        "status": "affected",
        "version": "Allen Bradley Micrologix 1400 Series B FRN 21.2, Allen Bradley Micrologix 1400 Series B FRN 21.0, Allen Bradley Micrologix 1400 Series B FRN 15"
      }
    ]
  }
]

7.5 High

CVSS2

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

PARTIAL

Availability Impact

PARTIAL

AV:N/AC:L/Au:N/C:P/I:P/A:P

9.8 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

9.2 High

AI Score

Confidence

High

0.001 Low

EPSS

Percentile

43.5%

Related for CVE-2017-14467