Lucene search

K
icsIndustrial Control Systems Cyber Emergency Response TeamICSA-24-151-01
HistoryMay 30, 2024 - 12:00 p.m.

LenelS2 NetBox

2024-05-3012:00:00
Industrial Control Systems Cyber Emergency Response Team
www.cisa.gov
5
lenels2
netbox
hard-coded password
remote code execution
authentication bypass
elevated permissions
vulnerability
cve-2024-2420
cve-2024-2421
cve-2024-2422
cvss v4 9.3
cvss v4 9.1
cvss v4 8.8
cvss v3.1 9.8
cvss v3.1 9.1
cvss v3.1 8.8
commercial
critical infrastructure sectors

9.3 High

CVSS4

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/SC:N/VI:H/SI:N/VA:H/SA:N

9.3 High

AI Score

Confidence

Low

0.0004 Low

EPSS

Percentile

9.0%

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3 *ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: LenelS2
  • Equipment: NetBox
  • Vulnerabilities: Use of Hard-coded Password, OS Command Injection, Argument Injection

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to bypass authentication and execute malicious commands with elevated permissions

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following products of LenelS2, a Carrier Brand, are affected:

  • NetBox: All versions prior to 5.6.2

3.2 Vulnerability Overview

3.2.1USE OF HARD-CODED PASSWORD CWE-259

LenelS2 NetBox access control and event monitoring system was discovered to contain hard-coded credentials in versions prior to and including 5.6.1, which allows an attacker to bypass authentication requirements.

CVE-2024-2420 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-2420. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND (‘OS COMMAND INJECTION’) CWE-78

LenelS2 NetBox access control and event monitoring system was discovered to contain an unauthenticated remote code execution in versions prior to and including 5.6.1, which allows an attacker to execute malicious commands with elevated permissions.

CVE-2024-2421 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-2421. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:L/SI:H/SA:L).

3.2.3IMPROPER NEUTRALIZATION OF ARGUMENT DELIMITERS IN A COMMAND (‘ARGUMENT INJECTION’) CWE-88

LenelS2 NetBox access control and event monitoring system was discovered to contain an authenticated remote code execution in versions prior to and including 5.6.1, which allows an attacker to execute malicious commands.

CVE-2024-2422 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-2422. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Noam Moshe of Claroty Team82 reported these vulnerabilities to CISA.

4. MITIGATIONS

These vulnerabilities have been mitigated in NetBox release 5.6.2. It is strongly recommended that users upgrade to NetBox release 5.6.2 by contacting their authorized installer.
Users should follow recommended deployment guidelines found in the NetBox hardening guide found in the NetBox built-in help menu.

For more information, see Carrier’s security bulletin for LenelS2.

CISA recommends users take defensive measures to minimize the risk of exploitation of this these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • May 30, 2024: Initial Publication

References

9.3 High

CVSS4

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/SC:N/VI:H/SI:N/VA:H/SA:N

9.3 High

AI Score

Confidence

Low

0.0004 Low

EPSS

Percentile

9.0%

Related for ICSA-24-151-01