As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 9.8 *ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: RUGGEDCOM CROSSBOW
  • Vulnerabilities: Missing Authorization, Improper Neutralization of Special Elements used in an SQL Command, Missing Authentication for Critical Function, External Control of File Name or Path, Improper Limitation of a Pathname to a Restricted Directory, Exposure of Sensitive Information to an Unauthorized Actor

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to execute arbitrary database queries or upload of arbitrary files to the application’s file system.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following products of Siemens, are affected:

  • RUGGEDCOM CROSSBOW: Versions prior to V5.5

3.2 Vulnerability Overview

3.2.1MISSING AUTHORIZATION CWE-862

The affected systems allow the upload of arbitrary files of any unauthenticated user. An attacker could leverage this vulnerability and achieve arbitrary code execution with system privileges.

CVE-2024-27939 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.2IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND (‘SQL INJECTION’) CWE-89

The affected systems allow any authenticated user to send arbitrary SQL commands to the SQL server. An attacker could use this vulnerability to compromise the whole database.

CVE-2024-27940 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.3IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND (‘SQL INJECTION’) CWE-89

The affected client systems do not properly sanitize input data before sending it to the SQL server. An attacker could use this vulnerability to compromise the whole database.

CVE-2024-27941 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.4MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306

The affected systems allow any unauthenticated client to disconnect any active user from the server. An attacker could use this vulnerability to prevent any user to perform actions in the system, causing a denial of service situation.

CVE-2024-27942 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.5EXTERNAL CONTROL OF FILE NAME OR PATH CWE-73

The affected systems allow a privileged user to upload generic files to the root installation directory of the system. By replacing specific files, an attacker could tamper specific files or even achieve remote code execution.

CVE-2024-27943 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H).

3.2.6EXTERNAL CONTROL OF FILE NAME OR PATH CWE-73

The affected systems allow a privileged user to upload firmware files to the root installation directory of the system. By replacing specific files, an attacker could tamper specific files or even achieve remote code execution.

CVE-2024-27944 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H).

3.2.7EXTERNAL CONTROL OF FILE NAME OR PATH CWE-73

The bulk import feature of the affected systems allow a privileged user to upload files to the root installation directory of the system. By replacing specific files, an attacker could tamper specific files or even achieve remote code execution.

CVE-2024-27945 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H).

3.2.8IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY (‘PATH TRAVERSAL’) CWE-22

Downloading files overwrites files with the same name in the installation directory of the affected systems. The filename for the target file can be specified, thus arbitrary files can be overwritten by an attacker with the required privileges.

CVE-2024-27946 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H).

3.2.9EXPOSURE OF SENSITIVE INFORMATION TO AN UNAUTHORIZED ACTOR CWE-200

The affected systems could allow log messages to be forwarded to a specific client under certain circumstances. An attacker could leverage this vulnerability to forward log messages to a specific compromised client.

CVE-2024-27947 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing, Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-916916 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • May 16, 2024: Initial Publication

References