HistoryJun 08, 2021 - 12:00 p.m.

Siemens SIMATIC HMI Products (Update A)

2021-06-0812:00:00
Industrial Control Systems Cyber Emergency Response Team
www.cisa.gov
21
siemens
simatic hmi
vulnerabilities
authentication
brute-force
update
remote access
cvss v3
exploitable remotely
excessive authentication attempts
authentication bypass
risk evaluation
technical details
affected products
vulnerability overview
cwe-307
cwe-305
mitigations
researcher
update information
critical infrastructure
worldwide
germany

CVSS2

5

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

NONE

Availability Impact

NONE

AV:N/AC:L/Au:N/C:P/I:N/A:N

CVSS3

9.8

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

AI Score

10

Confidence

High

EPSS

0.012

Percentile

85.2%

1. EXECUTIVE SUMMARY

  • CVSS v3 6.5 *ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • **Equipment:**SIMATIC HMI
  • **Vulnerabilities:**Improper Restriction of Excessive Authentication Attempts, Authentication Bypass by Primary Weakness

2. UPDATE INFORMATION

This updated advisory is a follow-up to the original advisory titled ICSA-20-252-06 Siemens SIMATIC HMI Products that was published September 8, 2020, to the ICS webpage on us-cert.cisa.gov.

3. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow a remote attacker to discover user passwords and obtain access to the Sm@rt Server via a brute-force attack.

4. TECHNICAL DETAILS

4.1 AFFECTED PRODUCTS

--------- Begin Update A Part 1 of 2 ---------

The following versions of Siemens SIMATIC HMI Products are affected:

  • SIMATIC HMI Basic Panels, 2nd Generation (incl. SIPLUS variants): All versions prior to v16 are affected by CVE-2020-15786
  • SIMATIC HMI Comfort Panels (incl. SIPLUS variants): All versions up to and including v16 are affected by CVE-2020-15786
  • SIMATIC HMI Mobile Panels: All versions up to and including v16 are affected by CVE-2020-15786
  • SIMATIC HMI United Comfort Panels: All versions up to and including v16

--------- End Update A Part 1 of 2 ---------

4.2 VULNERABILITY OVERVIEW

4.2.1 IMPROPER RESTRICTION OF EXCESSIVE AUTHENTICATION ATTEMPTS CWE-307

Affected devices insufficiently block excessive authentication attempts. This could allow a remote attacker to discover user passwords and obtain access to the Sm@rt Server via a brute-force attack.

CVE-2020-15786 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L).

4.2.2 AUTHENTICATION BYPASS BY PRIMARY WEAKNESS CWE-305

Affected devices insufficiently validate authentication attempts as the information given can be truncated to match only a set number of characters versus the whole provided string. This could allow a remote attacker to discover user passwords and obtain access to the Sm@rt Server via a brute-force attack.

CVE-2020-15787 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N).

4.3 BACKGROUND

  • **CRITICAL INFRASTRUCTURE SECTORS:**Energy
  • **COUNTRIES/AREAS DEPLOYED:**Worldwide
  • **COMPANY HEADQUARTERS LOCATION:**Germany

4.4 RESEARCHER

Joseph Gardiner from Bristol Cyber Security Group, University of Bristol, reported these vulnerabilities to Siemens.

5. MITIGATIONS

--------- Begin Update A Part 2 of 2 ---------

Siemens has released updates for the affected products and recommends users update to the latest versions.

Siemens has identified the following specific workarounds and mitigations users can apply to reduce the risk:

  • Apply defense-in-depth strategies.
  • For Unified Comfort Panels using SmartClient: The password truncation (CVE-2020-15787) cannot be resolved due to RFC 6143 and is limited to 8 characters. Complex passwords are recommended.

--------- End Update A Part 2 of 2 ---------

As a general security measure, Siemens strongly recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens operational guidelines for Industrial Security and following the recommendations in the product manuals.

For additional information, please refer to Siemens Security Advisory SSA-542525

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities.

References

CVSS2

5

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

NONE

Availability Impact

NONE

AV:N/AC:L/Au:N/C:P/I:N/A:N

CVSS3

9.8

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

AI Score

10

Confidence

High

EPSS

0.012

Percentile

85.2%