Lucene search

K
cvelistIcscertCVELIST:CVE-2013-2806
HistoryMar 26, 2019 - 4:47 p.m.

CVE-2013-2806

2019-03-2616:47:24
CWE-190
icscert
www.cve.org

7.8 High

AI Score

Confidence

High

0.001 Low

EPSS

Percentile

44.6%

Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the โ€œEnd of Current Recordโ€ field. By sending a datagram to the service over Port 4444/UDP with the โ€œRecord Data Sizeโ€ field modified to a specifically oversized value, the service will calculate an undersized value for the โ€œTotal Record Size.โ€ Then the service will calculate an incorrect value for the โ€œEnd of Current Recordโ€ field causing access violations that lead to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation security advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599

CNA Affected

[
  {
    "product": "RSLinx Enterprise Software",
    "vendor": "Rockwell Automation",
    "versions": [
      {
        "status": "affected",
        "version": "CPR9"
      },
      {
        "status": "affected",
        "version": "CPR9-SR1"
      },
      {
        "status": "affected",
        "version": "CPR9-SR2"
      },
      {
        "status": "affected",
        "version": "CPR9-SR3"
      },
      {
        "status": "affected",
        "version": "CPR9-SR4"
      },
      {
        "status": "affected",
        "version": "CPR9-SR5"
      },
      {
        "status": "affected",
        "version": "CPR9-SR5.1"
      },
      {
        "status": "affected",
        "version": "CPR9-SR6"
      }
    ]
  }
]

7.8 High

AI Score

Confidence

High

0.001 Low

EPSS

Percentile

44.6%

Related for CVELIST:CVE-2013-2806