Lucene search
K

Circutor PowerStudio SCADA 4.0.5 Unquoted Service Path Elevation Of Privilege Vulnerability

🗓️ 06 Dec 2015 00:00:00Reported by LiquidWormType 
zdt
 zdt
🔗 0day.today👁 56 Views

Circutor PowerStudio SCADA 4.0.5 Unquoted Service Path Elevation Of Privilege Vulnerability impacting Window

Code
Circutor PowerStudio SCADA 4.0.5 Unquoted Service Path Elevation Of Privilege


Vendor: CIRCUTOR SA
Product web page: http:/www.circutor.com
Affected version: PowerStudio SCADA 4.0.5 and OPC Server 1.4.1

Summary: CIRCUTOR's Electrical Energy Efficiency software (e3) is currently
called PowerStudio and encompasses all of the tools needed to manage your power
control equipment: from electricity, gas and water meters to reactive energy
compensation systems and powerful power analyzers.

Desc: The application suffers from an unquoted search path issue impacting the
services 'CircutorPowerStudioScadaServer' and 'CircutorPowerStudioServer' for
Windows deployed as part of PowerStudio Series. This could potentially allow
an authorized but non-privileged local user to execute arbitrary code with
elevated privileges on the system. A successful attempt would require the local
user to be able to insert their code in the system root path undetected by the
OS or other security applications where it could potentially be executed during
application startup or reboot. If successful, the local user’s code would execute
with the elevated privileges of the application.

Tested on: Microsoft Windows 7 Professional SP1 (EN)
Microsoft Windows 7 Ultimate SP1 (EN)

--


C:Userseoleon>sc qc CircutorPowerStudioScadaServer
[SC] QueryServiceConfig SUCCESS

SERVICE_NAME: CircutorPowerStudioScadaServer
TYPE : 110 WIN32_OWN_PROCESS (interactive)
START_TYPE : 2 AUTO_START
ERROR_CONTROL : 1 NORMAL
BINARY_PATH_NAME : C:Program Files (x86)CircutorPowerStudio ScadabinPwrStudio.exe
LOAD_ORDER_GROUP :
TAG : 0
DISPLAY_NAME : CircutorPowerStudioScadaServer
DEPENDENCIES :
SERVICE_START_NAME : LocalSystem


======


C:Userseoleon>sc qc CircutorPowerStudioServer
[SC] QueryServiceConfig SUCCESS

SERVICE_NAME: CircutorPowerStudioServer
TYPE : 110 WIN32_OWN_PROCESS (interactive)
START_TYPE : 2 AUTO_START
ERROR_CONTROL : 1 NORMAL
BINARY_PATH_NAME : C:Program Files (x86)CircutorPowerStudiobinPwrStudio.exe
LOAD_ORDER_GROUP :
TAG : 0
DISPLAY_NAME : CircutorPowerStudioServer
DEPENDENCIES :
SERVICE_START_NAME : LocalSystem

C:Userseoleon>

#  0day.today [2018-04-02]  #

Data

Build on a solid foundation with Vulners data

We provide the essential building blocks for cybersecurity solutions with comprehensive, structured, and constantly updated vulnerability and exploits data

Api

Power your application with Vulners API

The Vulners REST API offers reliable, high-performance access to vulnerability intelligence, with 99.9% SLA uptime and CDN-backed data delivery for seamless global access

App

Assess and manage vulnerabilities with Vulners tools

Built on top of Vulners' database and SDK, end-user solutions give security professionals and developers lightweight and powerful tools for vulnerability remediation