Lucene search
+L
EcoaRiskterminator

13 matches found

CVE
CVE
•added 2021/09/30 10:40 a.m.•112 views

CVE-2021-41291

CVE-2021-41291 affects ECOA Building Automation System BAS controllers. A directory-traversal vulnerability allows unauthenticated remote disclosure of device file contents by abusing the GET parameter (cpath in File Manager or fmangersub). Documented impact is disclosure of sensitive information...

7.5CVSS7.5AI score0.82689EPSS
SaveWeb
CVE
CVE
•added 2021/09/30 10:40 a.m.•106 views

CVE-2021-41290

The CVE-2021-41290 entry relates to ECOA BAS controller products (e.g., ECOA ECS Router Controller - ECS (FLASH); ECOA RiskBuster Terminator - E6L45; RB 3.0.0; TRANE 1.0; plus related ECOA software) and describes an arbitrary file write/path traversal vulnerability. Attackers can use POST paramet...

10CVSS10AI score0.02322EPSS
SaveWeb
CVE
CVE
•added 2021/09/30 10:40 a.m.•106 views

CVE-2021-41293

The ECOA Building Automation System (BAS) controller is affected by a path traversal/arbitrary file disclosure vulnerability. Affected component/file: viewlog.jsp; attack vector is via the POST parameter fname, allowing an unauthenticated attacker to disclose arbitrary files and sensitive system ...

7.5CVSS7.5AI score0.19867EPSS
SaveIn wildWeb
CVE
CVE
•added 2021/09/30 10:41 a.m.•99 views

CVE-2021-41299

CVE-2021-41299 affects ECOA BAS controller family (ECS Router Controller – ECS (FLASH), RiskBuster Terminator E6L45, RB 3.0.0, TRANE 1.0, Graphic Control Software, SmartHome II E9246, RiskTerminator). Root cause: hard-coded credentials embedded in the Linux distribution image, enabling remote att...

10CVSS9.6AI score0.02055EPSS
Save
CVE
CVE
•added 2021/09/30 10:40 a.m.•98 views

CVE-2021-41294

CVE-2021-41294 describes a directory traversal vulnerability in ECOA BAS controller (GET parameter handling) that enables unauthenticated remote deletion of arbitrary files and DoS. Concrete details across connected sources include affected ECOA products (ECS Router Controller ECS (FLASH), RiskBu...

9.1CVSS9.3AI score0.01185EPSS
SaveWeb
CVE
CVE
•added 2021/09/30 10:41 a.m.•98 views

CVE-2021-41301

The CVE-2021-41301 issue affects ECOA BAS controller family (ECS Router Controller - ECS (FLASH); RiskBuster Terminator E6L45; RiskBuster System RB 3.0.0 / TRANE 1.0; and related ECOA software). Root cause: information disclosure via direct object reference to syspara.dat or images.dat when acces...

10CVSS9.7AI score0.01989EPSS
Save
CVE
CVE
•added 2021/09/30 10:41 a.m.•93 views

CVE-2021-41300

CVE-2021-41300 concerns an information disclosure vulnerability in ECOA BAS controller. Multiple sources describe that the affected ECOA devices expose user credentials on a special web page, allowing unauthenticated remote access with full functionality. The Zero Science Lab report expands this ...

9.8CVSS9.6AI score0.0098EPSS
Save
CVE
CVE
•added 2021/09/30 10:41 a.m.•83 views

CVE-2021-41297

CVE-2021-41297 affects ECOA BAS controller family (building automation controllers) and is due to a weak access-control mechanism that can allow an authenticated user to obtain administrative credentials in clear text, enabling remote privilege escalation. The vulnerability is documented across m...

8.8CVSS8.8AI score0.00742EPSS
Save
CVE
CVE
•added 2021/09/30 10:40 a.m.•82 views

CVE-2021-41292

CVE-2021-41292 affects ECOA Building Automation System components (e.g., ECOA ECS Router Controller ECS (FLASH), RiskBuster Terminator E6L45, RB 3.0.0, TRANE 1.0, and related ECOA software). Root cause is an authentication bypass via cookie poisoning, enabling an unauthenticated attacker to bypas...

9.8CVSS9.2AI score0.01172EPSS
SaveWeb
CVE
CVE
•added 2021/09/30 10:41 a.m.•80 views

CVE-2021-41302

CVE-2021-41302 affects ECOA BAS controller family (ECS Router Controller - ECS (FLASH); RiskBuster Terminator - E6L45; RiskBuster System RB 3.0.0; TRANE 1.0; Graphic Control Software; SmartHome II - E9246; RiskTerminator). The issue is that backup exports and other sensitive data are stored in cl...

7.3CVSS7.3AI score0.00429EPSS
Save
CVE
CVE
•added 2021/09/30 10:40 a.m.•78 views

CVE-2021-41296

CVE-2021-41296 affects ECOA BAS controller family (ECS Router Controller ECS (FLASH), RiskBuster Terminator E6L45, RiskBuster System RB 3.0.0/TRANE 1.0, Ecoa Graphic Control Software, Ecoa SmartHome II, etc.). Root cause: weak/default administrative credentials that can be guessed, allowing remot...

9.8CVSS9.8AI score0.0095EPSS
Save
CVE
CVE
•added 2021/09/30 10:41 a.m.•76 views

CVE-2021-41298

CVE-2021-41298 – ECOA BAS controller is vulnerable to insecure direct object references (IDOR). The issue allows remote attackers with general user privileges to bypass authorization and access hidden resources or execute privileged functions. Affected products include ECOA ECS Router Controller ...

8.8CVSS8.8AI score0.0087EPSS
Save
CVE
CVE
•added 2021/09/30 10:40 a.m.•71 views

CVE-2021-41295

The ECOA BAS controller , an intelligent lighting control solution, contains a Cross-Site Request Forgery (CSRF) vulnerability. An authenticated attacker can remotely leverage a malicious web page to submit forged requests, enabling the execution of CRUD commands (GET, POST, PUT, DELETE) to perfo...

8.8CVSS8.9AI score0.00429EPSS
SaveIn wildWeb