CVE
CVE
added 2012/02/03 8:0 p.m.58 views

CVE-2011-4512

CVE-2011-4512 is a CRLF/header-injection vulnerability in the Siemens SIMATIC WinCC/HMI web server. Affected products include WinCC flexible 2004/2005/2007/2008 before SP3; WinCC V11 (TIA Portal) before SP2 Update 1; multiple SIMATIC HMI panels (TP/OP/MP/Comfort/Mobile); WinCC V11 Runtime Advance...

5CVSS6.9AI score0.01704EPSS
SaveExploits0References2Affected Software1
Cvelist
Cvelist
added 2012/02/03 8:0 p.m.35 views

CVE-2011-4508

The HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 aka TIA portal before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime generates predictable authentication token...

6.6AI score0.03119EPSS
SaveExploits0References2
CVE
CVE
added 2012/02/03 8:0 p.m.74 views

CVE-2011-4508

CVE-2011-4508: Insecure, predictable authentication token generation in Siemens WinCC/HMI web servers (WinCC flexible 2004–2008 before SP3; WinCC V11 before SP2 Update 1; and related HMI panels) allows remote attackers to bypass authentication by crafting cookies. Affected components include HMI ...

9.3CVSS6.8AI score0.03119EPSS
SaveExploits0References2Affected Software1
CVE
CVE
added 2012/02/03 8:0 p.m.65 views

CVE-2011-4876

CVE-2011-4876 is a directory traversal vulnerability in Siemens WinCC family runtimes (WinCC flexible 2004–2008, WinCC V11/TIA Portal, and related SIMATIC HMI panels) where the runtime loader HmiLoad fails to validate strings during Transfer Mode. This allows remote attackers to access or modify ...

9.3CVSS6.9AI score0.09847EPSS
SaveExploits1References9Affected Software1
Cvelist
Cvelist
added 2012/02/03 8:0 p.m.39 views

CVE-2011-4513

Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 aka TIA portal; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allow user-assisted remote attackers to execute arbitrary code via a crafted project file,...

7.5AI score0.04846EPSS
SaveExploits0References2
CVE
CVE
added 2012/02/03 8:0 p.m.61 views

CVE-2011-4513

CVE-2011-4513 affects Siemens WinCC Flexible (2004–2008), WinCC V11 (TIA Portal), SIMATIC HMI panels (TP/OP/MP/Comfort/Mobile), and WinCC Runtime Advanced/Flexible Runtime. The vulnerability allows user-assisted remote attackers to execute arbitrary code via a crafted project file, related to the...

10CVSS7.8AI score0.04846EPSS
SaveExploits0References2Affected Software1
CVE
CVE
added 2012/02/03 8:0 p.m.62 views

CVE-2011-4879

Siemens WinCC/HMI Web Server vulnerability CVE-2011-4879: the HMI web server (miniweb.exe) fails to properly handle URIs beginning with 0xfa, enabling remote memory reads or DoS via crafted POST requests. Affected products include WinCC flexible 2004–2008 (pre-SP3), WinCC V11 (TIA Portal) before ...

8.5CVSS6.9AI score0.12545EPSS
SaveExploits1References8Affected Software1
Kaspersky
Kaspersky
added 2012/01/24 12:0 a.m.58 views

KLA10394 Multiple vulnerabilities in Siemens

Multiple critical vulnerabilities have been found in Siemens products. Malicious users can exploit these vulnerabilities to read & modify arbitrary files, cause denial of service, execute arbitrary code, bypass authentication, obtain access and inject arbitrary HTTP headers. Below is a complete...

10CVSS8.4AI score0.14013EPSS
SaveExploits1References5
OpenVAS
OpenVAS
added 2011/12/23 12:0 a.m.52 views

Multiple Siemens SIMATIC Products Authentication Bypass Vulnerabilities

Multiple Siemens SIMATIC products are affected by vulnerabilities that allow attackers to bypass authentication. SPDX-FileCopyrightText: 2011 Greenbone AG Some text descriptions might be excerpted from a referenced sources, and are Copyright C by the respective right holders...

10CVSS6.7AI score0.03119EPSS
SaveExploits0References3
securityvulns
securityvulns
added 2011/12/05 12:0 a.m.79 views

Vulnerabilities in Siemens SIMATIC WinCC flexible 2008 SP2

Luigi Auriemma Application: Siemens SIMATIC WinCC flexible Runtime http://www.automation.siemens.com/mcms/human-machine-interface/en/visualization-software/wincc-flexible/wincc-flexible-runtime/Pages/Default.aspx Versions: 2008 SP2 + security patch 1 Platforms: Windows Bugs: A HmiLoad strings sta...

1.6AI score
SaveExploits0
securityvulns
securityvulns
added 2011/12/05 12:0 a.m.31 views

Siemens SIMATIC WinCC flexible multiple security vulnerabilities

HmiLoad and miniweb multiple security vulnerabilities...

1.6AI score
SaveExploits0References1Affected Software1
exploitpack
exploitpack
added 2011/11/28 12:0 a.m.42 views

Siemens SIMATIC WinCC Flexible (Runtime) - Multiple Vulnerabilities

Siemens SIMATIC WinCC Flexible Runtime - Multiple Vulnerabilities Luigi Auriemma Application: Siemens SIMATIC WinCC flexible Runtime http://www.automation.siemens.com/mcms/human-machine-interface/en/visualization-software/wincc-flexible/wincc-flexible-runtime/Pages/Default.aspx Versions: 2008 SP2...

0.5AI score
SaveExploits0
Exploit DB
Exploit DB
added 2011/11/28 12:0 a.m.75 views

Siemens SIMATIC WinCC Flexible (Runtime) - Multiple Vulnerabilities

Luigi Auriemma Application: Siemens SIMATIC WinCC flexible Runtime http://www.automation.siemens.com/mcms/human-machine-interface/en/visualization-software/wincc-flexible/wincc-flexible-runtime/Pages/Default.aspx Versions: 2008 SP2 + security patch 1 Platforms: Windows Bugs: A HmiLoad strings sta...

9.3CVSS5.2AI score0.14013EPSS
SaveExploits1
ThreatPost
ThreatPost
added 2011/11/22 5:7 p.m.23 views

Was The Three Character Password Used To Hack South Houston's Water Treatment Plant A Siemens Default?

Siemens said on Tuesday that it is working with the U.S. Department of Homeland Security to investigate a cyber intrusion into a water treatment plant in South Houston, Texas, but couldn’t confirm that a default, three digit password hard coded into an application used to control the company’s...

8.6AI score
SaveExploits0References5
NVD
NVD
added 2011/09/16 12:35 p.m.21 views

CVE-2011-3321

Heap-based buffer overflow in the Siemens WinCC Runtime Advanced Loader, as used in SIMATIC WinCC flexible Runtime and SIMATIC WinCC TIA Portal Runtime Advanced, allows remote attackers to cause a denial of service memory corruption or possibly execute arbitrary code via a crafted packet to TCP...

9.3CVSS8.3AI score0.0707EPSS
SaveExploits0References5
Prion
Prion
added 2011/09/16 12:35 p.m.18 views

Heap overflow

Heap-based buffer overflow in the Siemens WinCC Runtime Advanced Loader, as used in SIMATIC WinCC flexible Runtime and SIMATIC WinCC TIA Portal Runtime Advanced, allows remote attackers to cause a denial of service memory corruption or possibly execute arbitrary code via a crafted packet to TCP...

9.3CVSS9AI score0.0707EPSS
SaveExploits0References5
Cvelist
Cvelist
added 2011/09/15 9:0 p.m.28 views

CVE-2011-3321

Heap-based buffer overflow in the Siemens WinCC Runtime Advanced Loader, as used in SIMATIC WinCC flexible Runtime and SIMATIC WinCC TIA Portal Runtime Advanced, allows remote attackers to cause a denial of service memory corruption or possibly execute arbitrary code via a crafted packet to TCP...

8.3AI score0.0707EPSS
SaveExploits0References5
CVE
CVE
added 2011/09/15 9:0 p.m.64 views

CVE-2011-3321

CVE-2011-3321 affects Siemens WinCC flexible Runtime and SIMATIC WinCC (TIA Portal) Runtime Advanced Loader. The issue is a heap-based buffer overflow in the loader’s handling of inputs on 2308/TCP, enabling remote attackers to cause memory corruption and potentially execute arbitrary code or cau...

9.3CVSS8.6AI score0.0707EPSS
SaveExploits0References5Affected Software2
ThreatPost
ThreatPost
added 2011/06/08 3:57 p.m.10 views

Many Stuxnet Vulnerabilities Still Unpatched

The media storm over the Stuxnet worm may have passed, but many of the software holes that were used by the worm remain unpatched and leave Siemens customers open to a wide range of potentially damaging cyber attacks, according to industrial control system expert Ralph Langner. Writing on his...

0.4AI score
SaveExploits0References7
ICS
ICS
added 2011/06/04 6:0 a.m.41 views

Siemens WinCC Flexible Runtime Heap Overflow

Overview ICS-CERT originally released Advisory ICSA-11-244-01P on the US-CERT secure Portal on September 01, 2011. This web page release was delayed to allow users sufficient time to download and install the update. Independent security researchers Billy Rios and Terry McCorkle have reported a...

9.3CVSS8AI score0.0707EPSS