Lucene search
+L

833 matches found

Prion
Prion
added 2012/02/03 8:55 p.m.19 views

Code injection

Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 aka TIA portal; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allow user-assisted remote attackers to execute arbitrary code via a crafted project file,...

10CVSS8.1AI score0.04846EPSS
SaveExploits0References2Affected Software3
Prion
Prion
added 2012/02/03 8:55 p.m.17 views

Default credentials

The HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 aka TIA portal; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime has an improperly selected default password for the administrator account...

10CVSS7.1AI score0.0217EPSS
SaveExploits0References2Affected Software3
Prion
Prion
added 2012/02/03 8:55 p.m.28 views

Cross site scripting

Cross-site scripting XSS vulnerability in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 aka TIA portal before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime...

4.3CVSS5.9AI score0.01509EPSS
SaveExploits0References2Affected Software3
Prion
Prion
added 2012/02/03 8:55 p.m.19 views

Authentication flaw

The HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 aka TIA portal before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime generates predictable authentication token...

9.3CVSS7.2AI score0.03119EPSS
SaveExploits0References2Affected Software3
CVE
CVE
added 2012/02/03 8:0 p.m.62 views

CVE-2011-4879

Siemens WinCC/HMI Web Server vulnerability CVE-2011-4879: the HMI web server (miniweb.exe) fails to properly handle URIs beginning with 0xfa, enabling remote memory reads or DoS via crafted POST requests. Affected products include WinCC flexible 2004–2008 (pre-SP3), WinCC V11 (TIA Portal) before ...

8.5CVSS6.9AI score0.12545EPSS
SaveExploits1References8Affected Software1
Cvelist
Cvelist
added 2012/02/03 8:0 p.m.39 views

CVE-2011-4510

Cross-site scripting XSS vulnerability in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 aka TIA portal before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime...

5.5AI score0.01509EPSS
SaveExploits0References2
CVE
CVE
added 2012/02/03 8:0 p.m.91 views

CVE-2011-4509

CVE-2011-4509 affects Siemens WinCC/WinCC flexible products (2004–2008, WinCC V11, and related SIMATIC HMI panels). The root cause is an improperly selected default administrator password, which enables remote attackers to gain access by brute-forcing via many HTTP requests. Public citations in c...

10CVSS6.7AI score0.0217EPSS
SaveExploits0References2Affected Software1
CVE
CVE
added 2012/02/03 8:0 p.m.60 views

CVE-2011-4514

CVE-2011-4514 concerns the TELNET daemon in Siemens WinCC flexible (2004–2008) and WinCC V11 (TIA Portal), plus related SIMATIC HMI panels, which does not perform authentication, enabling remote access via TCP sessions. Affected products include WinCC flexible 2004/2005/2007/2008, WinCC V11, TP/O...

10CVSS6.6AI score0.03522EPSS
SaveExploits0References2Affected Software1
Cvelist
Cvelist
added 2012/02/03 8:0 p.m.35 views

CVE-2011-4509

The HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 aka TIA portal; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime has an improperly selected default password for the administrator account...

6.5AI score0.0217EPSS
SaveExploits0References2
CVE
CVE
added 2012/02/03 8:0 p.m.64 views

CVE-2011-4511

CVE-2011-4511 is a cross-site scripting (XSS) vulnerability in the Siemens SIMATIC WinCC HMI web server. Affected products (per ICS-CERT) include WinCC flexible 2004/2005/2007/2008 (before SP3), WinCC V11 (TIA Portal) before SP2 Update 1, and multiple SIMATIC HMI panels plus WinCC V11 Runtime Adv...

4.3CVSS5.7AI score0.01509EPSS
SaveExploits0References2Affected Software1
Cvelist
Cvelist
added 2012/02/03 8:0 p.m.32 views

CVE-2011-4511

Cross-site scripting XSS vulnerability in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 aka TIA portal before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime...

5.5AI score0.01509EPSS
SaveExploits0References2
CVE
CVE
added 2012/02/03 8:0 p.m.58 views

CVE-2011-4878

Siemens WinCC/HMI Web Server is vulnerable to a directory traversal in the HMI web server component (miniweb.exe) affecting WinCC flexible 2004–2008, WinCC V11 (TIA Portal) before SP2 Update 1, and related SIMATIC HMI panels and runtimes. Root cause: improper validation of HTTP/URI strings allows...

7.8CVSS6.8AI score0.12067EPSS
SaveExploits1References8Affected Software1
CVE
CVE
added 2012/02/03 8:0 p.m.61 views

CVE-2011-4877

CVE-2011-4877 affects Siemens WinCC flexible products (2004–2008) and related SIMATIC HMI panels, WinCC V11 Runtime Advanced, and WinCC flexible Runtime. The issue lies in HmiLoad in the runtime loader; when Transfer Mode is enabled, sending crafted data over TCP can cause a remote denial of serv...

7.1CVSS6.7AI score0.07527EPSS
SaveExploits1References8Affected Software1
CVE
CVE
added 2012/02/03 8:0 p.m.68 views

CVE-2011-4875

CVE-2011-4875 corresponds to a stack-based buffer overflow in the HmiLoad runtime loader of Siemens WinCC flexible (versions 2004, 2005, 2007, 2008) and WinCC V11 (TIA Portal) including SIMATIC HMI panels and WinCC V11 Runtime Advanced. The root cause is improper handling/validation of Unicode st...

9.3CVSS8.2AI score0.14013EPSS
SaveExploits1References8Affected Software1
CVE
CVE
added 2012/02/03 8:0 p.m.60 views

CVE-2011-4510

CVE-2011-4510 and CVE-2011-4511 describe cross-site scripting (XSS) in the Siemens SIMATIC WinCC/HMI Web server. Affected products include WinCC flexible 2004–2008 (before SP3), WinCC V11 (TIA Portal) before SP2 Update 1, and multiple SIMATIC HMI panels, plus WinCC V11 Runtime Advanced and WinCC ...

4.3CVSS5.7AI score0.01509EPSS
SaveExploits0References2Affected Software1
Cvelist
Cvelist
added 2012/02/03 8:0 p.m.31 views

CVE-2011-4879

miniweb.exe in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 aka TIA portal before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime does not properly handle UR...

6.6AI score0.12545EPSS
SaveExploits1References8
Cvelist
Cvelist
added 2012/02/03 8:0 p.m.30 views

CVE-2011-4876

Directory traversal vulnerability in HmiLoad in the runtime loader in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 aka TIA portal; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime, when Transfer Mode is...

6.6AI score0.09847EPSS
SaveExploits1References9
Cvelist
Cvelist
added 2012/02/03 8:0 p.m.31 views

CVE-2011-4877

HmiLoad in the runtime loader in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 aka TIA portal; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime, when Transfer Mode is enabled, allows remote attackers to cau...

6.5AI score0.07527EPSS
SaveExploits1References8
Cvelist
Cvelist
added 2012/02/03 8:0 p.m.31 views

CVE-2011-4878

Directory traversal vulnerability in miniweb.exe in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 aka TIA portal before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexibl...

6.6AI score0.12067EPSS
SaveExploits1References8
Cvelist
Cvelist
added 2012/02/03 8:0 p.m.28 views

CVE-2011-4875

Stack-based buffer overflow in HmiLoad in the runtime loader in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 aka TIA portal; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime, when Transfer Mode is enabled,...

7.9AI score0.14013EPSS
SaveExploits1References8
Rows per page