Default configuration
The WBM web application on firmwares prior to 03.02.02 and 03.01.07 on the WAGO PFC100 and PFC2000, respectively, runs on a lighttpd web server and makes use of the FastCGI module, which is intended to provide high performance for all Internet applications without the penalties of Web server APIs...
CVE-2019-5149
The WBM web application on firmwares prior to 03.02.02 and 03.01.07 on the WAGO PFC100 and PFC2000, respectively, runs on a lighttpd web server and makes use of the FastCGI module, which is intended to provide high performance for all Internet applications without the penalties of Web server APIs...
CVE-2019-5149
The CVE-2019-5149 issue affects WAGO PFC100 and PFC2000 devices running WBM over a lighttpd server with FastCGI. The default mod_fastcgi configuration limits concurrent php-cgi processes to two (min-procs 1, max-procs 2), enabling an attacker to exhaust resources and cause a denial of service of ...
WAGO PFC100/200 Web-Based Management (WBM) Authentication Timing Information Disclosure Vulnerability
Summary An exploitable timing discrepancy vulnerability exists in the authentication functionality of the Web-Based Management WBM web application on WAGO PFC100/200 controllers. The WBM application makes use of the PHP crypt function which can be exploited to disclose hashed user credentials...
CVE-2014-5432
Baxter SIGMA Spectrum Infusion System version 6.05 model 35700BAX with wireless battery module WBM version 16 is remotely accessible via Port 22/SSH without authentication. A remote attacker may be able to make unauthorized configuration changes to the WBM, as well as issue commands to access...
CVE-2014-5432
Baxter SIGMA Spectrum Infusion System version 6.05 model 35700BAX with wireless battery module WBM version 16 is remotely accessible via Port 22/SSH without authentication. A remote attacker may be able to make unauthorized configuration changes to the WBM, as well as issue commands to access...
CVE-2014-5433
An unauthenticated remote attacker may be able to execute commands to view wireless account credentials that are stored in cleartext on Baxter SIGMA Spectrum Infusion System version 6.05 model 35700BAX with wireless battery module WBM version 16, which may allow an attacker to gain access the hos...
CVE-2014-5434
Baxter SIGMA Spectrum Infusion System version 6.05 model 35700BAX with wireless battery module WBM version 16 has a default account with hard-coded credentials used with the FTP protocol. Baxter asserts no files can be transferred to or from the WBM using this account. Baxter has released a new...
CVE-2018-12979
An issue was discovered on WAGO e!DISPLAY 762-3000 through 762-3003 devices with firmware before FW 02. Weak permissions allow an authenticated user to overwrite critical files by abusing the unrestricted file upload in the WBM...
Unrestricted file upload
An issue was discovered on WAGO e!DISPLAY 762-3000 through 762-3003 devices with firmware before FW 02. Weak permissions allow an authenticated user to overwrite critical files by abusing the unrestricted file upload in the WBM...
CVE-2014-9563
CRLF injection vulnerability in the web-based management WBM interface in Unify former Siemens OpenStage SIP and OpenScape Desk Phone IP V3 devices before R3.32.0 allows remote authenticated users to modify the root password and consequently access the debug port using the serial interface via th...
OmniPCX Office远程信息泄露漏洞
BUGTRAQ ID: 28758 CVECAN ID: CVE-2008-1331 阿尔卡特的OmniPCX Office是一套为中小型企业设计的统一通信解决方案。 OmniPCX Office的Internet Access服务所使用的一个CGI脚本没有正确地过滤某些特定参数,允许远程攻击者从Internet检索敏感信息。 Alcatel-Lucent OmniPCX Office = 210/061.1 临时解决方法: 如果您不能立刻安装补丁或者升级,NSFOCUS建议您采取以下措施以降低威胁: 禁止从Internet的WBM/WCA访问 对于R2.1到R4.1版本:...