19 matches found
CVE-2019-18247
An attacker may use a specially crafted message to force Relion 650 series versions 1.3.0.5 and prior or Relion 670 series versions 1.2.3.18, 2.0.0.11, 2.1.0.1 and prior to reboot, which could cause a denial of service...
Hitachi Relion多款产品 安全漏洞
Hitachi Relion 650, among others, is a software for protection, control, measurement and monitoring of power distribution and transmission grids from Hitachi, Japan. A security vulnerability exists in various Hitachi Relion products, which stems from improper prioritization of network traffic and...
PT-2025-26714 · Sam600-Io +1 · Sam600-Io +1
Name of the Vulnerable Software and Affected Versions: Relion 670/650 and SAM600-IO series device affected versions not specified Description: A denial-of-service issue exists due to improper prioritization of network traffic over protection mechanisms. This could cause critical functions, such a...
Hitachi Energy Relion 670/650/SAM600-IO Initialization of a Resource with an Insecure Default (CVE-2021-35535)
Insecure Boot Image vulnerability in Hitachi Energy Relion Relion 670/650/SAM600-IO series allows an attacker who manages to get access to the front network port and to cause a reboot sequences of the device may exploit the vulnerability, where there is a tiny time gap during the booting process...
ABB Relion 670 Series 和 Relion 650 Series数据伪造问题漏洞
The ABB Relion 670 Series is a transmission protection control device from ABB Switzerland. A security vulnerability exists in the Relion 670, 650, and SAM600-IO series due to an incorrect access control included in the signature verification of Hitachi Energy Relion update packages. A tampered...
Hitachi Energy Relion 670, 650 and SAM600-IO Series
1. EXECUTIVE SUMMARY CVSS v3 4.5 ATTENTION: Exploitable remotely/low attack complexity Vendor: Hitachi Energy Equipment: Relion 670, 650, and SAM600-IO Series Vulnerability: Insufficient Verification of Data Authenticity 2. RISK EVALUATION Successful exploitation of this vulnerability could cause...
Hitachi Energy Relion 670, 650 and SAM600-IO Improper Input Validation (CVE-2021-27196)
Improper Input Validation vulnerability in Hitachi ABB Power Grids Relion 670 Series, Relion 670/650 Series, Relion 670/650/SAM600-IO, Relion 650, REB500, RTU500 Series, FOX615 TEGO1, MSM, GMS600, PWC600 allows an attacker with access to the IEC 61850 network with knowledge of how to reproduce th...
Hitachi Energy GMS600, PWC600, and Relion
1. EXECUTIVE SUMMARY CVSS v3 7.2 ATTENTION: Exploitable remotely/low attack complexity Vendor: Hitachi Energy Equipment: GMS600, PWC600, and Relion 670/650/SAM600-IO Vulnerability: Improper Access Controls 2. UPDATE INFORMATION This updated advisory is a follow-up to the original advisory titled...
CVE-2021-35534
Insufficient security control vulnerability in internal database access mechanism of Hitachi Energy Relion 670/650/SAM600-IO, Relion 650, GMS600, PWC600 allows attacker who successfully exploited this vulnerability, of which the product does not sufficiently restrict access to an internal databas...
Hitachi Energy Relion 系列安全漏洞
Hitachi Energy Relion is a Swiss Hitachi Energy company used to protect, control, measure and monitor for power systems. A security vulnerability exists in the Hitachi Energy Relion Relion 670/650/SAM600-IO Series that allows an attacker to gain access to the front-end network port and cause a...
PT-2021-20958 · Hitachi Energy · Relion 670/650/Sam600-Io +2
Name of the Vulnerable Software and Affected Versions: Hitachi Energy Relion 670 Series versions 2.2.2 through 2.2.3.2 Hitachi Energy Relion 670/650 Series versions 2.2.0 through 2.2.4 Hitachi Energy Relion 670/650/SAM600-IO version 2.2.1 Description: The issue is related to an Insecure Boot Imag...
CVE-2021-27196
CVE-2021-27196 affects Hitachi Energy Relion 670/650 series and related IEC 61850 interfaces. The issue is caused by improper input validation that allows an attacker with IEC 61850 network access to trigger a reboot, rendering affected devices inoperable for about 60 seconds. Affected products a...
PT-2021-17315 · Hitachi Abb Power Grids · Msm +9
Name of the Vulnerable Software and Affected Versions: Hitachi ABB Power Grids Relion 670 Series versions 1.1 through 2.2.3 Hitachi ABB Power Grids Relion 670/650 Series version 2.2.0 Hitachi ABB Power Grids Relion 670/650/SAM600-IO version 2.2.1 Hitachi ABB Power Grids Relion 650 versions 1.1...
Hitachi Energy Relion 670, 650 and SAM600-IO
1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable remotely/low attack complexity Vendor: Hitachi Energy Equipment: Relion 670, 650, and SAM600-IO Vulnerabilities: Improper Input Validation 2. UPDATE INFORMATION This updated advisory is a follow-up to the original advisory titled...
Denial of service
An attacker may use a specially crafted message to force Relion 650 series versions 1.3.0.5 and prior or Relion 670 series versions 1.2.3.18, 2.0.0.11, 2.1.0.1 and prior to reboot, which could cause a denial of service...
CVE-2019-18247
CVE-2019-18247 affects ABB Relion 650/670 Series due to improper input validation. ABB Relion 650 series versions 1.3.0.5 and prior; Relion 670 series versions 1.2.3.18, 2.0.0.11, 2.1.0.1 and prior may reboot when processing a specially crafted message, causing a denial of service. Public sources...
CVE-2019-18247
An attacker may use a specially crafted message to force Relion 650 series versions 1.3.0.5 and prior or Relion 670 series versions 1.2.3.18, 2.0.0.11, 2.1.0.1 and prior to reboot, which could cause a denial of service...
ABB Relion 650 and 670 Series
1. EXECUTIVE SUMMARY CVSS v3 5.3 ATTENTION: Exploitable remotely/low skill level to exploit Vendor: ABB Equipment: Relion 650 and 670 Series Vulnerability: Improper Input Validation 2. RISK EVALUATION Successful exploitation of this vulnerability may allow an attacker to reboot the device,...
ABB Relion 650 Series OpenSSL Vulnerability (Update A)
OVERVIEW --------- Begin Update A Part 1 of 2-------- This updated advisory is a follow-up to the original advisory titled ICSA-14-126-01 ABB Relion 650 Series OpenSSL Vulnerability, that was published May 06, 2014, on the NCCIC/ICS-CERT web site. ABB has identified an OpenSSL vulnerability in it...