Lucene search
+L

348 matches found

The Hacker News
The Hacker News
•added 2022/08/16 10:57 a.m.•68 views

New Evil PLC Attack Weaponizes PLCs to Breach OT and Enterprise Networks

Cybersecurity researchers have elaborated a novel attack technique that weaponizes programmable logic controllers PLCs to gain an initial foothold in engineering workstations and subsequently invade the operational technology OT networks. Dubbed "Evil PLC" attack by industrial security firm...

0.5AI score
SaveExploits0
BDU FSTEC
BDU FSTEC
•added 2022/08/15 12:00 a.m.•35 views

The vulnerability of the Modbus TCP protocol implementation in microprogrammed software for programmable logic controllers from Schneider Electric, such as Modicon M340, M580, MC80, Modicon Momentum MDI, Legacy Modicon Quantum/Premium, allows a intruder to trigger a service failure.

The vulnerability of the Modbus TCP protocol implementation in microprogrammed logic controllers from Schneider Electric, such as Modicon M340, M580, MC80, Modicon Momentum MDI, and Legacy Modicon Quantum/Premium, is related to a potential integer overflow. Exploiting this vulnerability could all...

7.8CVSS7.3AI score0.00754EPSS
SaveExploits0References2Affected Software2
BDU FSTEC
BDU FSTEC
•added 2022/08/15 12:00 a.m.•20 views

The vulnerability of the Modbus TCP protocol implementation in microprogrammed software for programmable logic controllers from Schneider Electric, such as Modicon M340, M580, MC80, Modicon Momentum MDI, Legacy Modicon Quantum, allows a intruder to gain unauthorized access to protected information.

The vulnerability of the Modbus TCP protocol implementation in microprogrammed logic controllers from Schneider Electric, such as Modicon M340, M580, MC80, Modicon Momentum MDI, and Legacy Modicon Quantum, is related to errors in information processing. Exploiting this vulnerability can allow an...

7.8CVSS7.2AI score0.0063EPSS
SaveExploits0References2Affected Software3
NVD
NVD
•added 2022/07/26 10:15 p.m.•29 views

CVE-2022-31206

The Omron SYSMAC Nx product family PLCs NJ series, NY series, NX series, and PMAC series through 2022-005-18 lack cryptographic authentication. These PLCs are programmed using the SYMAC Studio engineering software which compiles IEC 61131-3 conformant POU code to native machine code for execution...

9.8CVSS0.01086EPSS
SaveExploits0References2
OSV
OSV
•added 2022/07/26 10:15 p.m.•20 views

CVE-2022-31206

The Omron SYSMAC Nx product family PLCs NJ series, NY series, NX series, and PMAC series through 2022-005-18 lack cryptographic authentication. These PLCs are programmed using the SYMAC Studio engineering software which compiles IEC 61131-3 conformant POU code to native machine code for execution...

9.8CVSS7.9AI score0.01086EPSS
SaveExploits0References2
attackerkb
attackerkb
•added 2022/07/26 10:15 p.m.•9 views

CVE-2022-31204

Omron CS series, CJ series, and CP series PLCs through 2022-05-18 use cleartext passwords. They feature a UM Protection setting that allows users or system integrators to configure a password in order to restrict sensitive engineering operations such as project/logic uploads and downloads. This...

7.5CVSS7.1AI score0.00651EPSS
SaveExploits0References3
attackerkb
attackerkb
•added 2022/07/26 10:15 p.m.•7 views

CVE-2022-31205

In Omron CS series, CJ series, and CP series PLCs through 2022-05-18, the password for access to the Web UI is stored in memory area D1449...D1452 and can be read out using the Omron FINS protocol without any further authentication...

7.5CVSS7.1AI score0.00662EPSS
SaveExploits0References3
attackerkb
attackerkb
•added 2022/07/26 10:15 p.m.•23 views

CVE-2022-31207

The Omron SYSMAC Cx product family PLCs CS series, CJ series, and CP series through 2022-05-18 lack cryptographic authentication. They utilize the Omron FINS 9600/TCP protocol for engineering purposes, including downloading projects and control logic to the PLC. This protocol has authentication...

9.8CVSS7.6AI score0.0097EPSS
SaveExploits0References3
NVD
NVD
•added 2022/07/26 10:15 p.m.•33 views

CVE-2022-31204

Omron CS series, CJ series, and CP series PLCs through 2022-05-18 use cleartext passwords. They feature a UM Protection setting that allows users or system integrators to configure a password in order to restrict sensitive engineering operations such as project/logic uploads and downloads. This...

7.5CVSS0.00651EPSS
SaveExploits0References2
NVD
NVD
•added 2022/07/26 10:15 p.m.•26 views

CVE-2022-31207

The Omron SYSMAC Cx product family PLCs CS series, CJ series, and CP series through 2022-05-18 lack cryptographic authentication. They utilize the Omron FINS 9600/TCP protocol for engineering purposes, including downloading projects and control logic to the PLC. This protocol has authentication...

9.8CVSS0.0097EPSS
SaveExploits0References2
NVD
NVD
•added 2022/07/26 10:15 p.m.•28 views

CVE-2022-29958

JTEKT TOYOPUC PLCs through 2022-04-29 do not ensure data integrity. They utilize the unauthenticated CMPLink/TCP protocol for engineering purposes, including downloading projects and control logic to the PLC. Control logic is downloaded to the PLC on a block-by-block basis with a given memory...

9.8CVSS0.00592EPSS
SaveExploits0References2
attackerkb
attackerkb
•added 2022/07/26 10:15 p.m.•5 views

CVE-2022-29951

JTEKT TOYOPUC PLCs through 2022-04-29 mishandle authentication. They utilize the CMPLink/TCP protocol configurable on ports 1024-65534 on either TCP or UDP for a wide variety of engineering purposes such as starting and stopping the PLC, downloading and uploading projects, and changing...

9.1CVSS7.2AI score0.01286EPSS
SaveExploits0References3
Prion
Prion
•added 2022/07/26 10:15 p.m.•39 views

Default credentials

Omron CS series, CJ series, and CP series PLCs through 2022-05-18 use cleartext passwords. They feature a UM Protection setting that allows users or system integrators to configure a password in order to restrict sensitive engineering operations such as project/logic uploads and downloads. This...

5CVSS8AI score0.00651EPSS
SaveExploits0References2Affected Software7
Prion
Prion
•added 2022/07/26 10:15 p.m.•29 views

Memory corruption

JTEKT TOYOPUC PLCs through 2022-04-29 do not ensure data integrity. They utilize the unauthenticated CMPLink/TCP protocol for engineering purposes, including downloading projects and control logic to the PLC. Control logic is downloaded to the PLC on a block-by-block basis with a given memory...

7.5CVSS9.7AI score0.00592EPSS
SaveExploits0References2
Prion
Prion
•added 2022/07/26 10:15 p.m.•29 views

Design/Logic Flaw

The Omron SYSMAC Nx product family PLCs NJ series, NY series, NX series, and PMAC series through 2022-005-18 lack cryptographic authentication. These PLCs are programmed using the SYMAC Studio engineering software which compiles IEC 61131-3 conformant POU code to native machine code for execution...

7.5CVSS9.8AI score0.01086EPSS
SaveExploits0References2Affected Software25
Prion
Prion
•added 2022/07/26 10:15 p.m.•27 views

Authentication flaw

JTEKT TOYOPUC PLCs through 2022-04-29 mishandle authentication. They utilize the CMPLink/TCP protocol configurable on ports 1024-65534 on either TCP or UDP for a wide variety of engineering purposes such as starting and stopping the PLC, downloading and uploading projects, and changing...

6.4CVSS9.2AI score0.01286EPSS
SaveExploits0References2
Prion
Prion
•added 2022/07/26 10:15 p.m.•34 views

Authentication flaw

In Omron CS series, CJ series, and CP series PLCs through 2022-05-18, the password for access to the Web UI is stored in memory area D1449...D1452 and can be read out using the Omron FINS protocol without any further authentication...

5CVSS8AI score0.00662EPSS
SaveExploits0References2Affected Software6
Cvelist
Cvelist
•added 2022/07/26 9:28 p.m.•33 views

CVE-2022-31207

The Omron SYSMAC Cx product family PLCs CS series, CJ series, and CP series through 2022-05-18 lack cryptographic authentication. They utilize the Omron FINS 9600/TCP protocol for engineering purposes, including downloading projects and control logic to the PLC. This protocol has authentication...

10AI score0.0097EPSS
SaveExploits0References2
Cvelist
Cvelist
•added 2022/07/26 9:28 p.m.•35 views

CVE-2022-31205

In Omron CS series, CJ series, and CP series PLCs through 2022-05-18, the password for access to the Web UI is stored in memory area D1449...D1452 and can be read out using the Omron FINS protocol without any further authentication...

8.2AI score0.00662EPSS
SaveExploits0References2
CVE
CVE
•added 2022/07/26 9:28 p.m.•102 views

CVE-2022-31204

CVE-2022-31204 affects Omron SYSMAC CS/CJ/CP Series and NJ/NX Series PLCs prior to the listed mitigations. The root cause is cleartext transmission of the engineering password used for UM Protection (Program Area Protect/Program Area Protect Clear), enabling unauthorized access to restricted engi...

7.5CVSS7.2AI score0.00651EPSS
SaveExploits0References2Affected Software1
Rows per page