52 matches found
CVE-2022-24044
A vulnerability has been identified in Desigo DXR2 All versions V01.21.142.5-22, Desigo PXC3 All versions V01.21.142.4-18, Desigo PXC4 All versions V02.20.142.10-10884, Desigo PXC5 All versions V02.20.142.10-10884. The login functionality of the application does not employ any countermeasures...
CVE-2022-24043
Siemens Desigo DXR2, PXC3, PXC4 and PXC5 are affected by CVE-2022-24043 due to a login-side-channel: the system does not normalize response times between failed logins with wrong usernames and correct usernames, enabling username enumeration. Affected versions are: Desigo DXR2 < v01.21.142.5-2...
CVE-2022-24042
CVE-2022-24042 affects Siemens Desigo DXR2, PXC3, PXC4, and PXC5 devices. The vulnerability is that the web application AuthToken does not expire after the defined auto logoff delay, enabling an attacker to capture a token and reuse old session credentials or session IDs for authorization. Affect...
CVE-2022-24042
A vulnerability has been identified in Desigo DXR2 All versions V01.21.142.5-22, Desigo PXC3 All versions V01.21.142.4-18, Desigo PXC4 All versions V02.20.142.10-10884, Desigo PXC5 All versions V02.20.142.10-10884. The web application returns an AuthToken that does not expire at the defined auto...
CVE-2022-24041
CVE-2022-24041 affects Siemens Desigo DXR2, PXC3, PXC4 and PXC5 devices. The vulnerability stems from storing PBKDF2 password hashes with a low iteration count, enabling an attacker with user-profile access to retrieve other accounts’ password hashes and perform offline cracking to recover plaint...
CVE-2022-24041
A vulnerability has been identified in Desigo DXR2 All versions V01.21.142.5-22, Desigo PXC3 All versions V01.21.142.4-18, Desigo PXC4 All versions V02.20.142.10-10884, Desigo PXC5 All versions V02.20.142.10-10884. The web application stores the PBKDF2 derived key of users passwords with a low...
CVE-2022-24040
A vulnerability has been identified in Desigo DXR2 All versions V01.21.142.5-22, Desigo PXC3 All versions V01.21.142.4-18, Desigo PXC4 All versions V02.20.142.10-10884, Desigo PXC5 All versions V02.20.142.10-10884. The web application fails to enforce an upper bound to the cost factor of the PBKD...
CVE-2022-24040
CVE-2022-24040 affects Siemens Desigo DXR2, PXC3, PXC4 and PXC5: the web app does not enforce an upper bound on PBKDF2 cost factor during account creation/update. An attacker with user-profile access can trigger a DoS by setting an excessively high PBKDF2 cost and attempting login, causing high C...
CVE-2021-41545
A vulnerability has been identified in Desigo DXR2 All versions V01.21.142.5-22, Desigo PXC3 All versions V01.21.142.4-18, Desigo PXC4 All versions V02.20.142.10-10884, Desigo PXC5 All versions V02.20.142.10-10884. When the controller receives a specific BACnet protocol packet, an exception cause...
CVE-2021-41545
CVE-2021-41545 affects Siemens Desigo DXR2, PXC3, PXC4 and PXC5 controllers. When a device receives a specific BACnet packet, an exception can cause the BACnet communication function to enter an out-of-work state, potentially leading to a factory reset. Affected versions are: DXR2 all versions be...
多款Siemens产品资源管理错误漏洞
Desigo DXR2 controllers are programmable automation stations to support the standard control needs of end HVAC equipment and TRA Total Room Automation applications. the Desigo PXC3 series of automation stations can be used in buildings where functionality and flexibility are more demanding. Use...
多款Siemens产品安全漏洞
Desigo DXR2 controllers are programmable automation stations to support the standard control needs of end HVAC equipment and TRA Total Room Automation applications. the Desigo PXC3 series of automation stations can be used in buildings where functionality and flexibility are more demanding. Use...