Lucene search
+L

52 matches found

Cvelist
Cvelist
added 2022/05/10 9:46 a.m.27 views

CVE-2022-24044

A vulnerability has been identified in Desigo DXR2 All versions V01.21.142.5-22, Desigo PXC3 All versions V01.21.142.4-18, Desigo PXC4 All versions V02.20.142.10-10884, Desigo PXC5 All versions V02.20.142.10-10884. The login functionality of the application does not employ any countermeasures...

7.5AI score0.00869EPSS
SaveExploits0References1
CVE
CVE
added 2022/05/10 9:46 a.m.115 views

CVE-2022-24043

Siemens Desigo DXR2, PXC3, PXC4 and PXC5 are affected by CVE-2022-24043 due to a login-side-channel: the system does not normalize response times between failed logins with wrong usernames and correct usernames, enabling username enumeration. Affected versions are: Desigo DXR2 < v01.21.142.5-2...

5.3CVSS5.1AI score0.01041EPSS
SaveExploits0References1Affected Software1
CVE
CVE
added 2022/05/10 9:46 a.m.123 views

CVE-2022-24042

CVE-2022-24042 affects Siemens Desigo DXR2, PXC3, PXC4, and PXC5 devices. The vulnerability is that the web application AuthToken does not expire after the defined auto logoff delay, enabling an attacker to capture a token and reuse old session credentials or session IDs for authorization. Affect...

9.1CVSS8.8AI score0.00945EPSS
SaveExploits0References1Affected Software1
Cvelist
Cvelist
added 2022/05/10 9:46 a.m.34 views

CVE-2022-24042

A vulnerability has been identified in Desigo DXR2 All versions V01.21.142.5-22, Desigo PXC3 All versions V01.21.142.4-18, Desigo PXC4 All versions V02.20.142.10-10884, Desigo PXC5 All versions V02.20.142.10-10884. The web application returns an AuthToken that does not expire at the defined auto...

9.1AI score0.00945EPSS
SaveExploits0References1
CVE
CVE
added 2022/05/10 9:46 a.m.126 views

CVE-2022-24041

CVE-2022-24041 affects Siemens Desigo DXR2, PXC3, PXC4 and PXC5 devices. The vulnerability stems from storing PBKDF2 password hashes with a low iteration count, enabling an attacker with user-profile access to retrieve other accounts’ password hashes and perform offline cracking to recover plaint...

6.5CVSS6.4AI score0.00463EPSS
SaveExploits0References1Affected Software1
Cvelist
Cvelist
added 2022/05/10 9:46 a.m.24 views

CVE-2022-24041

A vulnerability has been identified in Desigo DXR2 All versions V01.21.142.5-22, Desigo PXC3 All versions V01.21.142.4-18, Desigo PXC4 All versions V02.20.142.10-10884, Desigo PXC5 All versions V02.20.142.10-10884. The web application stores the PBKDF2 derived key of users passwords with a low...

6.6AI score0.00463EPSS
SaveExploits0References1
Cvelist
Cvelist
added 2022/05/10 9:46 a.m.27 views

CVE-2022-24040

A vulnerability has been identified in Desigo DXR2 All versions V01.21.142.5-22, Desigo PXC3 All versions V01.21.142.4-18, Desigo PXC4 All versions V02.20.142.10-10884, Desigo PXC5 All versions V02.20.142.10-10884. The web application fails to enforce an upper bound to the cost factor of the PBKD...

6.5AI score0.00822EPSS
SaveExploits0References1
CVE
CVE
added 2022/05/10 9:46 a.m.123 views

CVE-2022-24040

CVE-2022-24040 affects Siemens Desigo DXR2, PXC3, PXC4 and PXC5: the web app does not enforce an upper bound on PBKDF2 cost factor during account creation/update. An attacker with user-profile access can trigger a DoS by setting an excessively high PBKDF2 cost and attempting login, causing high C...

6.5CVSS6.3AI score0.00822EPSS
SaveExploits0References1Affected Software1
Cvelist
Cvelist
added 2022/05/10 9:46 a.m.26 views

CVE-2021-41545

A vulnerability has been identified in Desigo DXR2 All versions V01.21.142.5-22, Desigo PXC3 All versions V01.21.142.4-18, Desigo PXC4 All versions V02.20.142.10-10884, Desigo PXC5 All versions V02.20.142.10-10884. When the controller receives a specific BACnet protocol packet, an exception cause...

7.5AI score0.00894EPSS
SaveExploits0References1
CVE
CVE
added 2022/05/10 9:46 a.m.111 views

CVE-2021-41545

CVE-2021-41545 affects Siemens Desigo DXR2, PXC3, PXC4 and PXC5 controllers. When a device receives a specific BACnet packet, an exception can cause the BACnet communication function to enter an out-of-work state, potentially leading to a factory reset. Affected versions are: DXR2 all versions be...

7.5CVSS7.3AI score0.00894EPSS
SaveExploits0References1Affected Software1
CNNVD
CNNVD
added 2022/05/10 12:00 a.m.14 views

多款Siemens产品资源管理错误漏洞

Desigo DXR2 controllers are programmable automation stations to support the standard control needs of end HVAC equipment and TRA Total Room Automation applications. the Desigo PXC3 series of automation stations can be used in buildings where functionality and flexibility are more demanding. Use...

6.5CVSS6.6AI score0.00822EPSS
SaveExploits0References5
CNNVD
CNNVD
added 2022/05/10 12:00 a.m.12 views

多款Siemens产品安全漏洞

Desigo DXR2 controllers are programmable automation stations to support the standard control needs of end HVAC equipment and TRA Total Room Automation applications. the Desigo PXC3 series of automation stations can be used in buildings where functionality and flexibility are more demanding. Use...

7.5CVSS7.3AI score0.00894EPSS