Siemens LOGO! 8 BM Use of Hard-Coded Cryptographic Key (CVE-2020-25233)
A vulnerability has been identified in LOGO! 8 BM incl. SIPLUS variants All versions V8.3. The firmware update of affected devices contains the private RSA key that is used as a basis for encryption of communication with the device. This plugin only works with Tenable.ot. Please visit...
Siemens LOGO! Insufficiently Protected Credentials (CVE-2017-12734)
A vulnerability has been identified in LOGO! 8 BM incl. SIPLUS variants All versions V1.81.2. An attacker with network access to the integrated web server on port 80/tcp could obtain the session ID of an active user session. A user must be logged in to the web interface. Siemens recommends to use...
Siemens LOGO! 8 BM Use of Hard-Coded Cryptographic Key (CVE-2020-25231)
A vulnerability has been identified in LOGO! 8 BM incl. SIPLUS variants All versions V8.3, LOGO! Soft Comfort All versions V8.3. The encryption of program data for the affected devices uses a static key. An attacker could use this key to extract confidential information from protected program...
Siemens LOGO! Missing Authentication For Critical Function (CVE-2020-7589)
A vulnerability has been identified in LOGO! 8 BM incl. SIPLUS variants All versions. The vulnerability could lead to an attacker reading and modifying the device configuration and obtain project files from affected devices. The security vulnerability could be exploited by an unauthenticated...
Siemens LOGO! Insufficient Verification of Data Authenticity (CVE-2022-36360)
A vulnerability has been identified in LOGO! 8 BM incl. SIPLUS variants All versions V8.3. Affected devices load firmware updates without checking the authenticity. Furthermore the integrity of the unencrypted firmware is only verified by a non-cryptographic method. This could allow an attacker t...
Siemens LOGO! Web Server Buffer Copy Without Checking Size of Input (CVE-2020-7593)
A vulnerability has been identified in LOGO! 8 BM incl. SIPLUS variants V1.81.01 - V1.81.03, LOGO! 8 BM incl. SIPLUS variants V1.82.01, LOGO! 8 BM incl. SIPLUS variants V1.82.02. A buffer overflow vulnerability exists in the Web Server functionality of the device. A remote unauthenticated attacke...
Siemens LOGO! 8 BM Plaintext Storage of a Password (CVE-2019-10921)
A vulnerability has been identified in LOGO! 8 BM incl. SIPLUS variants All versions V8.3. Unencrypted storage of passwords in the project could allow an attacker with access to port 10005/tcp to obtain passwords of the device. The security vulnerability could be exploited by an unauthenticated...
Siemens LOGO! 8 BM Use of Hard-Coded Cryptographic Key (CVE-2020-25234)
A vulnerability has been identified in LOGO! 8 BM incl. SIPLUS variants All versions V8.3, LOGO! Soft Comfort All versions V8.3. The LOGO! program files generated and used by the affected components offer the possibility to save user-defined functions UDF in a password protected way. This...
Siemens LOGO! 8 BM Missing Authentication For Critical Function (CVE-2019-10919)
A vulnerability has been identified in LOGO! 8 BM incl. SIPLUS variants All versions V8.3. Attackers with access to port 10005/tcp could perform device reconfigurations and obtain project files from the devices. The system manual recommends to protect access to this port. The security vulnerabili...
Siemens LOGO! 8 BM Devices Improper Input Validation (CVE-2022-36362)
A vulnerability has been identified in LOGO! 8 BM incl. SIPLUS variants All versions. Affected devices do not conduct certain validations when interacting with them. This could allow an unauthenticated remote attacker to manipulate the devices IP address, which means the device would not be...
Siemens LOGO! 8 BM Missing Authentication For Critical Function (CVE-2020-25228)
A vulnerability has been identified in LOGO! 8 BM incl. SIPLUS variants All versions V8.3. A service available on port 10005/tcp of the affected devices could allow complete access to all services without authorization. An attacker could gain full control over an affected device, if he has access...
Siemens LOGO! Channel Accessible By Non-Endpoint (CVE-2017-12735)
A vulnerability has been identified in LOGO! 8 BM incl. SIPLUS variants All versions V8.3. An attacker who performs a Man-in- the-Middle attack between the LOGO! BM and other devices could potentially decrypt and modify network traffic. This plugin only works with Tenable.ot. Please visit...
Siemens LOGO! 8 BM Use of a Broken or Risky Cryptographic Algorithm (CVE-2020-25230)
A vulnerability has been identified in LOGO! 8 BM incl. SIPLUS variants All versions V8.3. Due to the usage of an outdated cipher mode on port 10005/tcp, an attacker could extract the encryption key from a captured communication with the device. This plugin only works with Tenable.ot. Please visi...
BM IT CMS 1.0 Insecure Settings
==================================================================================================================================== | Title : BM IT CMS v1.0 Insecure Settings Vulnerability | | Author : indoushka | | Tested on : windows 10 Français V.Pro / browser : Mozilla firefox 69.032-bit | |...
bm-marcyletoile.fr Cross Site Scripting vulnerability OBB-3492308
Following the coordinated and responsible vulnerability disclosure guidelines of the ISO 29147 standard, Open Bug Bounty has: a. verified the vulnerability and confirmed its existence; b. notified the website operator about its existence. Technical details of the vulnerability are currently hidde...
bm-bukovel.com Cross Site Scripting vulnerability OBB-3356514
Following the coordinated and responsible vulnerability disclosure guidelines of the ISO 29147 standard, Open Bug Bounty has: a. verified the vulnerability and confirmed its existence; b. notified the website operator about its existence. Technical details of the vulnerability are currently hidde...
Siemens LOGO! 8 BM input validation error vulnerability
A security vulnerability exists in Siemens LOGO! 8 BM, a programming software for the Windows platform used in industrial environments from Siemens, Germany. The vulnerability stems from the inability to properly validate offset values defined in TCP packets when calling methods. An attacker coul...
Siemens LOGO! 8 BM Input Validation Error Vulnerability (CNVD-2022-89766)
A security vulnerability exists in Siemens LOGO! 8 BM, a programming software for industrial environments for the Windows platform from Siemens, Germany, which stems from the fact that certain authentication is not performed when interacting with them. An unauthenticated remote attacker could...
CVE-2022-36360
A vulnerability has been identified in LOGO! 8 BM incl. SIPLUS variants All versions V8.3. Affected devices load firmware updates without checking the authenticity. Furthermore the integrity of the unencrypted firmware is only verified by a non-cryptographic method. This could allow an attacker t...
CVE-2022-36360