424 matches found
CVE-2018-7846
CVE-2018-7846 affects Schneider Electric Modicon M580, M340, Quantum and Premium PLCs. The issue is a CWE-501 Trust Boundary Violation in the UMAS/Reservation mechanism: an unauthenticated brute-force attempt to the Modbus-based reservation session (one-byte session token) can allow unauthorized ...
CVE-2018-7851
CWE-119: Buffer errors vulnerability exists in Modicon M580 with firmware prior to V2.50, Modicon M340 with firmware prior to V3.01, BMxCRA312xx with firmware prior to V2.40, All firmware versions of Modicon Premium and 140CRA312xxx when sending a specially crafted Modbus packet, which could caus...
CVE-2019-6819
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists which could cause a possible Denial of Service when specific Modbus frames are sent to the controller in the products: Modicon M340 - firmware versions prior to V3.01, Modicon M580 - firmware versions prior to...
CVE-2019-6819
Schneider Electric Modicon M340 (pre-3.01), M580 (pre-2.80), and all Modicon Quantum and Premium firmware are affected by CVE-2019-6819 (CWE-754). A remote attacker can cause a denial-of-service by sending specially crafted Modbus frames. The Red Hat, Tenable OT, and CISA/ICS advisories corrobora...
CVE-2019-6819
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists which could cause a possible Denial of Service when specific Modbus frames are sent to the controller in the products: Modicon M340 - firmware versions prior to V3.01, Modicon M580 - firmware versions prior to...
CVE-2019-6821
CVE-2019-6821 affects Schneider Electric Modicon devices: M580 firmware versions before 2.30 (and M580 M340/Premium/Quantum family). The vulnerability is CWE-330: Use of Insufficiently Random Values, causing predictable TCP initial sequence numbers that can enable an attacker to hijack TCP connec...
CVE-2019-6821
CWE-330: Use of Insufficiently Random Values vulnerability, which could cause the hijacking of the TCP connection when using Ethernet communication in Modicon M580 firmware versions prior to V2.30, and all firmware versions of Modicon M340, Modicon Premium, Modicon Quantum...
Schneider Electric Modicon Configuration File Override Vulnerability
The Schneider Electric Modicon M580, M340 is a programmable automation controller. A security vulnerability exists in the Schneider Electric Modicon M580, M340 that allows remote attackers to exploit the vulnerability to submit a special request that could overwrite configuration files...
Modicon M580/M340/Premium/Quantum Insufficient Random Value Usage Vulnerability
The Schneider Electric Modicon M580 is a programmable automation controller.The Schneider Electric Modicon Premium is a large programmable logic controller PLC for discrete or process applications.The Schneider Electric Modicon Quantum is a large programmable logic controller PLC for process...
Modicon M580/M340/Premium/Quantum Improper Exception Checking Vulnerability
Modicon M340 is a programmable controller PLC for complex devices and small to medium-sized projects.Modicon Premium is a programmable controller PLC for complex control.Modicon Quantum is a programmable controller PLC for process control.Modicon M580 is a programmable automation controller PAC...
Schneider Electric Modicon Illegal Breakpoint Parameter Denial of Service Vulnerability
The Schneider Electric Modicon M580, M340 is a programmable automation controller. An illegal breakpoint parameter handling vulnerability exists in the Schneider Electric Modicon M580, M340, which allows remote attackers to exploit the vulnerability by submitting a special request, which can be...
Denial of Service Vulnerability in Multiple Schneider Electric Products (CNVD-2019-15891)
The Schneider Electric Modicon M580 is a programmable automation controller.The Schneider Electric Modicon Premium is a large programmable logic controller PLC for discrete or process applications.The Schneider Electric Modicon Quantum is a large programmable logic controller PLC for process...
Schneider Electric Modicon Out-of-Bounds Write Denial of Service Vulnerability
The Schneider Electric Modicon M580, M340 is a programmable automation controller. An out-of-bounds write vulnerability exists in the Schneider Electric Modicon M580, M340, which allows remote attackers to exploit the vulnerability by submitting a special request, which can be used in a...
Schneider Electric Modicon Illegal Memory Block Write Denial of Service Vulnerability
The Schneider Electric Modicon M580, M340 is a programmable automation controller. An illegal memory block write vulnerability exists in the Schneider Electric Modicon M580, M340, which allows remote attackers to exploit the vulnerability by submitting a specific request, which can be used in a...
PT-2019-11106
Name of the Vulnerable Software and Affected Versions: Modicon M580 affected versions not specified Modicon M340 affected versions not specified Modicon Quantum affected versions not specified Modicon Premium affected versions not specified Description: A denial of service issue exists due to an...
Denial of Service Vulnerability in Multiple Schneider Electric Products (CNVD-2019-15744)
The Schneider Electric Modicon M580 is a programmable automation controller.The Schneider Electric Modicon Premium is a large programmable logic controller PLC for discrete or process applications.The Schneider Electric Modicon Quantum is a large programmable logic controller PLC for process...
Denial of Service Vulnerability in Multiple Schneider Electric Products (CNVD-2019-15737)
The Schneider Electric Modicon M580 is a programmable automation controller.The Schneider Electric Modicon Premium is a large programmable logic controller PLC for discrete or process applications.The Schneider Electric Modicon Quantum is a large programmable logic controller PLC for process...
Schneider Electric Modicon M580 PAC Detection
Binary data 751068.prm...
Schneider Electric Modicon Controllers
1. EXECUTIVE SUMMARY CVSS v3 5.4 ATTENTION: Exploitable remotely/low skill level to exploit Vendor: Schneider Electric Equipment: Modicon M580, Modicon M340, Modicon Premium, and Modicon Quantum Vulnerability: Use of Insufficiently Random Values 2. RISK EVALUATION Successful exploitation of this...
PT-2019-2284
Name of the Vulnerable Software and Affected Versions Modicon M340 versions prior to V3.01 Modicon M580 versions prior to V2.80 Modicon Quantum all firmware versions Modicon Premium all firmware versions Description A vulnerability exists due to improper check for unusual or exceptional condition...