169 matches found
CVE-2022-32527
The PT-2022-3182 and related records confirm CVE-2022-32527 affects Schneider Electric IGSS Data Server (IGSSdataServer.exe) with a CWE-120 vulnerability: a buffer copy without checking input size causes a stack-based overflow that could enable remote code execution via crafted alarm cache data m...
CVE-2022-32525
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted alarm data messages. Affected Products: IGSS Data Server - IGSSdataServer.exe Versions...
CVE-2022-32523
CVE-2022-32523 affects IGSS Data Server (IGSSdataServer.exe) prior to version 15.0.0.22170. It is a CWE-120 buffer copy without checking input size, causing a stack-based buffer overflow that could enable remote code execution when handling specially crafted online data request messages. Referenc...
CVE-2022-32527: Buffer Copy without Checking Size of Input
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted alarm cache data messages. Affected Products: IGSS Data Server - IGSSdataServer.exe...
CVE-2022-32528: Missing Authentication for Critical Function
A CWE-306: Missing Authentication for Critical Function vulnerability exists that could cause access to manipulate and read specific files in the IGSS project report directory, potentially leading to a denial-of-service condition when an attacker sends specific messages. Affected Products: IGSS...
CVE-2022-32522: Buffer Copy without Checking Size of Input
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted mathematically reduced data request messages. Affected Products: IGSS Data Server -...
CVE-2022-32528
A CWE-306: Missing Authentication for Critical Function vulnerability exists that could cause access to manipulate and read specific files in the IGSS project report directory, potentially leading to a denial-of-service condition when an attacker sends specific messages. Affected Products: IGSS...
CVE-2022-32524: Buffer Copy without Checking Size of Input
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted time reduced data messages. Affected Products: IGSS Data Server - IGSSdataServer.exe...
Schneider Electric IGSS Data Server Out-of-bounds Write (CVE-2022-32526)
Binary data schneiderelectricigsscve-2022-32526.nbin...
Schneider Electric IGSS Data Server Buffer Overflow Vulnerability
Schneider Electric IGSS Data Server is a data server for the Interactive Graphics Scada system from Schneider Electric France. prior to Schneider Electric IGSS Data Server version 15.0.0.22074 A buffer overflow vulnerability exists, which stems from the presence of a boundary error in the...
Schneider Electric IGSS Data Server Access Control Error Vulnerability (CNVD-2023-38195)
The Schneider Electric IGSS Data Server is a data server for the interactive graphical Scada system from Schneider Electric, France. An Access Control Error vulnerability exists in Schneider Electric IGSS Data Server versions prior to 15.0.0.22140, which stems from the application's lack of...
Schneider Electric IGSS Data Server Buffer Overflow Vulnerability (CNVD-2023-38194)
The Schneider Electric Igss Data Server is a data server for the interactive graphical Scada system from Schneider Electric France. A buffer overflow vulnerability exists in versions prior to Schneider Electric IGSS Data Server 15.0.0.22140, which originates from a boundary error when processing...
Schneider Electric IGSS Data Server alarm data buffer overflow vulnerability
The Schneider Electric Igss Data Server is a data server for the interactive graphical Scada system from Schneider Electric France. A buffer overflow vulnerability exists in Schneider Electric IGSS Data Server versions prior to 15.0.0.22140, which stems from a boundary error when processing...
Schneider Electric IGSS Data Server 访问控制错误漏洞
The Schneider Electric IGSS Data Server is a data server for the interactive graphical Scada system from Schneider Electric, France. An Access Control Error vulnerability exists in Schneider Electric IGSS Data Server versions prior to 15.0.0.22140, which stems from the application's lack of...
Schneider Electric IGSS Data Server 缓冲区错误漏洞
The Schneider Electric IGSS Data Server is a data server for the Interactive Graphics Scada System from Schneider Electric France. A buffer error vulnerability exists in versions prior to Schneider Electric IGSS Data Server 15.0.0.22140, which stems from an application boundary error. A remote...
Schneider Electric IGSS Data Server 缓冲区错误漏洞
The Schneider Electric IGSS Data Server is a data server for the Interactive Graphics Scada System from Schneider Electric France. A buffer error vulnerability exists in versions prior to Schneider Electric IGSS Data Server 15.0.0.22140, which stems from an application boundary error. A remote...
Schneider Electric IGSS Data Server 缓冲区错误漏洞
The Schneider Electric IGSS Data Server is a data server for the Interactive Graphics Scada System from Schneider Electric France. A buffer error vulnerability exists in versions prior to Schneider Electric IGSS Data Server 15.0.0.22140, which stems from an application boundary error. A remote...
PT-2022-3201 · Unknown · Igss Data Server
Name of the Vulnerable Software and Affected Versions: IGSS Data Server - IGSSdataServer.exe versions prior to V15.0.0.22170 Description: A buffer copy without checking the size of input vulnerability exists, potentially leading to a stack-based buffer overflow and remote code execution when an...
PT-2022-3197 · Unknown · Igss Data Server
Name of the Vulnerable Software and Affected Versions: IGSS Data Server versions prior to V15.0.0.22170 Description: The issue is related to a buffer copy without checking the size of input data, which could cause a stack-based buffer overflow. This might lead to remote code execution when an...
PT-2022-3203 · Unknown · Igss Data Server
Name of the Vulnerable Software and Affected Versions: IGSS Data Server versions prior to V15.0.0.22170 Description: The issue is related to a missing authentication procedure for critical functions in the IGSS Data Server, part of the Interactive Graphical SCADA System. This could allow a remote...