Lucene search
+L

13 matches found

BDU FSTEC
BDU FSTEC
•added 2024/11/26 12:00 a.m.•19 views

Hitachi Energy MicroSCADA X SYS600 Session Interception

The vulnerability of the software used in Hitachi Energy’s equipment monitoring and control system, MicroSCADA X SYS600, involves bypassing the authentication process. Exploiting this vulnerability allows a malicious actor to intercept an already established session...

8.2CVSS5.5AI score0.00217EPSS
SaveExploits0References2Affected Software1
CISA
CISA
•added 2023/05/18 12:00 p.m.•26 views

CISA Releases Five Industrial Control Systems Advisories

CISA released five Industrial Control Systems ICS advisories on May 16, 2023. These advisories provide timely information about current security issues, vulnerabilities, and exploits surrounding ICS. ICSA-23-138-01 Carlo Gavazzi Powersoft ICSA-23-138-02 Mitsubishi Electric MELSEC WS ICSA-23-138-0...

7AI score
SaveExploits0References5
CISA
CISA
•added 2022/10/25 12:00 a.m.•21 views

CISA Releases Eight Industrial Control Systems Advisories

CISA has released eight 8 Industrial Control Systems ICS advisories on October 25, 2022. These advisories provide timely information about current security issues, vulnerabilities, and exploits surrounding ICS. CISA encourages users and administrators to review the newly released ICS advisory for...

0.8AI score
SaveExploits0References8
osv_cve
osv_cve
•added 2022/09/14 6:15 p.m.•21 views

CVE-2022-29922

Improper Input Validation vulnerability in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. The vulnerability may cause a denial-of-service on the...

7.5CVSS5.8AI score0.00791EPSS
SaveExploits0References1
osv_cve
osv_cve
•added 2022/09/14 6:15 p.m.•22 views

CVE-2022-29492

Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a...

7.5CVSS5.8AI score0.00746EPSS
SaveExploits0References1
NVD
NVD
•added 2022/09/14 6:15 p.m.•31 views

CVE-2022-29492

Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a...

7.5CVSS0.00746EPSS
SaveExploits0References1
NVD
NVD
•added 2022/09/14 6:15 p.m.•44 views

CVE-2022-2277

Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future to any remote ICCP...

7.5CVSS0.00768EPSS
SaveExploits0References2
Cvelist
Cvelist
•added 2022/09/14 5:02 p.m.•39 views

CVE-2022-2277 A vulnerability exists in the ICCP stack of the affected SYS600 versions due to validation flaw in the process that establishes the ICCP communication. The validation flaw will cause a denial-of-service when ICCP of SYS600 is request to forward any da ...

Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future to any remote ICCP...

7.5CVSS7.7AI score0.00768EPSS
SaveExploits0References1
Rapid7 Vulnerability Database (full)
Rapid7 Vulnerability Database (full)
•added 2022/09/14 12:00 a.m.•7 views

CVE-2022-29922: Improper Input Validation

Improper Input Validation vulnerability in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. The vulnerability may cause a denial-of-service on the...

7.5CVSS7.2AI score0.00791EPSS
SaveExploits0References3
Rapid7 Vulnerability Database (full)
Rapid7 Vulnerability Database (full)
•added 2022/09/14 12:00 a.m.•7 views

CVE-2022-2277: Improper Validation of Specified Quantity in Input

Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future to any remote ICCP...

7.5CVSS7.3AI score0.00768EPSS
SaveExploits0References3
Rapid7 Vulnerability Database (full)
Rapid7 Vulnerability Database (full)
•added 2022/09/14 12:00 a.m.•8 views

CVE-2022-1778: Improper Restriction of Operations within the Bounds of a Memory Buffer

Improper Input Validation vulnerability in Hitachi Energy MicroSCADA X SYS600 while reading a specific configuration file causes a buffer-overflow that causes a failure to start the SYS600. The configuration file can only be accessed by an administrator access. This issue affects: Hitachi Energy...

7.5CVSS6.2AI score0.00481EPSS
SaveExploits0References3
Rapid7 Vulnerability Database (full)
Rapid7 Vulnerability Database (full)
•added 2022/09/14 12:00 a.m.•9 views

CVE-2022-29492: Improper Input Validation

Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a...

7.5CVSS7.2AI score0.00746EPSS
SaveExploits0References3
Rapid7 Vulnerability Database (full)
Rapid7 Vulnerability Database (full)
•added 2022/09/12 12:00 a.m.•10 views

CVE-2022-29490: Improper Authorization

Improper Authorization vulnerability exists in the Workplace X WebUI of the Hitachi Energy MicroSCADA X SYS600 allows an authenticated user to execute any MicroSCADA internal scripts irrespective of the authenticated user's role. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10 t...

8.8CVSS8AI score0.00637EPSS
SaveExploits0References2
Rows per page
Query Builder