9 matches found
CVE-2025-9279: Uncontrolled Resource Consumption
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles EtherNet/IP Step Limit Storm tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds...
CVE-2025-9283: Uncontrolled Resource Consumption
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles EtherNet/IP Step Limits Storms tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds...
CVE-2025-9278: Uncontrolled Resource Consumption
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. After running a Burp Suite active scan, the device loses ICMP connectivity, causing the web application to become inaccessible...
CVE-2025-9466: Uncontrolled Resource Consumption
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles EtherNet/IP and CIP grammar tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds...
CVE-2025-9464: Uncontrolled Resource Consumption
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. This vulnerability is triggered during fuzzing of multiple CIP classes, which causes the CIP port to become unresponsive...
CVE-2025-9465: Uncontrolled Resource Consumption
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles Comprehensive grammar tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds...
CVE-2025-9282: Uncontrolled Resource Consumption
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles Comprehensive limited storm tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds...
CVE-2025-9281: Uncontrolled Resource Consumption
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles Comprehensive step limit storm tests, the device reboots...
CVE-2025-9280: Uncontrolled Resource Consumption
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. Fuzzing performed using Defensics causes the device to become unresponsive, requiring a reboot...