An Improper Authentication issue was discovered in WAGO PFC200 Series 3S CoDeSys Runtime versions 2.3.X and 2.4.X. An attacker can execute different unauthenticated remote operations because of the CoDeSys Runtime application, which is available via network by default on Port 2455. An attacker could execute some unauthenticated commands such as reading, writing, or deleting arbitrary files, or manipulate the PLC application during runtime by sending specially-crafted TCP packets to Port 2455.
This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.
#%NASL_MIN_LEVEL 80900
##
# (C) Tenable, Inc.
##
include('compat.inc');
if (description)
{
script_id(500921);
script_version("1.4");
script_set_attribute(attribute:"plugin_modification_date", value:"2024/03/04");
script_cve_id("CVE-2018-5459");
script_name(english:"WAGO PFC200 Series Improper Authentication (CVE-2018-5459)");
script_set_attribute(attribute:"synopsis", value:
"The remote OT asset is affected by a vulnerability.");
script_set_attribute(attribute:"description", value:
"An Improper Authentication issue was discovered in WAGO PFC200 Series
3S CoDeSys Runtime versions 2.3.X and 2.4.X. An attacker can execute
different unauthenticated remote operations because of the CoDeSys
Runtime application, which is available via network by default on Port
2455. An attacker could execute some unauthenticated commands such as
reading, writing, or deleting arbitrary files, or manipulate the PLC
application during runtime by sending specially-crafted TCP packets to
Port 2455.
This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.");
script_set_attribute(attribute:"see_also", value:"https://ics-cert.us-cert.gov/advisories/ICSA-18-044-01");
script_set_attribute(attribute:"solution", value:
"The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original
can be found at CISA.gov.
WAGO released a security patch with FW11 available at:
http://global.wago.com/media/2_products/security/Sec-Advisory_CoDeSys.pdf");
script_set_cvss_base_vector("CVSS2#AV:N/AC:L/Au:N/C:P/I:P/A:P");
script_set_cvss_temporal_vector("CVSS2#E:U/RL:OF/RC:C");
script_set_cvss3_base_vector("CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H");
script_set_cvss3_temporal_vector("CVSS:3.0/E:U/RL:O/RC:C");
script_set_attribute(attribute:"cvss_score_source", value:"CVE-2018-5459");
script_set_attribute(attribute:"exploitability_ease", value:"No known exploits are available");
script_cwe_id(287);
script_set_attribute(attribute:"vuln_publication_date", value:"2018/02/13");
script_set_attribute(attribute:"patch_publication_date", value:"2018/02/13");
script_set_attribute(attribute:"plugin_publication_date", value:"2023/03/29");
script_set_attribute(attribute:"plugin_type", value:"remote");
script_set_attribute(attribute:"cpe", value:"cpe:/o:wago:pfc200_firmware");
script_set_attribute(attribute:"generated_plugin", value:"current");
script_end_attributes();
script_category(ACT_GATHER_INFO);
script_family(english:"Tenable.ot");
script_copyright(english:"This script is Copyright (C) 2023-2024 and is owned by Tenable, Inc. or an Affiliate thereof.");
script_dependencies("tenable_ot_api_integration.nasl");
script_require_keys("Tenable.ot/Wago");
exit(0);
}
include('tenable_ot_cve_funcs.inc');
get_kb_item_or_exit('Tenable.ot/Wago');
var asset = tenable_ot::assets::get(vendor:'Wago');
var vuln_cpes = {
"cpe:/o:wago:pfc200_firmware" :
{"versionEndExcluding" : "02.07.07\(10\)", "family" : "ControllerPFC200"}
};