Lucene search
+L

Siemens SIMATIC S7-1500 Improper Input Validation (CVE-2025-46836)

🗓️ 13 Nov 2025 00:00:00Reported by TenableType 
nessus
 nessus
🔗 www.tenable.com👁 11 Views

Siemens SIMATIC S7-1500 CVE-2025-46836 improper input validation in net-tools interface parsing; patch 2.20.

Related
Refs
Code
#%NASL_MIN_LEVEL 80900
##
# (C) Tenable, Inc.
##

include('compat.inc');

if (description)
{
  script_id(503955);
  script_version("1.2");
  script_set_attribute(attribute:"plugin_modification_date", value:"2026/02/14");

  script_cve_id("CVE-2025-46836");
  script_xref(name:"ICSA", value:"25-162-05");
  script_xref(name:"ICSA", value:"23-348-10");

  script_name(english:"Siemens SIMATIC S7-1500 Improper Input Validation (CVE-2025-46836)");

  script_set_attribute(attribute:"synopsis", value:
"The remote OT asset is affected by a vulnerability.");
  script_set_attribute(attribute:"description", value:
"net-tools is a collection of programs that form the base set of the
NET-3 networking distribution for the Linux operating system. Inn
versions up to and including 2.10, the Linux network utilities (like
ifconfig) from the net-tools package do not properly validate the
structure of /proc files when showing interfaces. `get_name()` in
`interface.c` copies interface labels from `/proc/net/dev` into a
fixed 16-byte stack buffer without bounds checking, leading to
possible arbitrary code execution or crash. The known attack path does
not require privilege but also does not provide privilege escalation
in this scenario. A patch is available and expected to be part of
version 2.20.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.");
  script_set_attribute(attribute:"see_also", value:"https://cert-portal.siemens.com/productcert/html/ssa-082556.html");
  script_set_attribute(attribute:"see_also", value:"https://www.cisa.gov/news-events/ics-advisories/icsa-23-348-10");
  script_set_attribute(attribute:"see_also", value:"https://www.cisa.gov/news-events/ics-advisories/icsa-25-162-05");
  script_set_attribute(attribute:"solution", value:
"The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original
can be found at CISA.gov.

Siemens is preparing fixed versions and reports that currently, no fix is available.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To
operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens'
operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-082556 in HTML and CSAF.");
  script_set_cvss3_base_vector("CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H");
  script_set_attribute(attribute:"cvss_score_source", value:"CVE-2025-46836");

  script_set_attribute(attribute:"exploitability_ease", value:"No known exploits are available");
  script_cwe_id(20);

  script_set_attribute(attribute:"vuln_publication_date", value:"2025/06/10");
  script_set_attribute(attribute:"patch_publication_date", value:"2025/06/10");
  script_set_attribute(attribute:"plugin_publication_date", value:"2025/11/13");

  script_set_attribute(attribute:"plugin_type", value:"remote");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:simatic_s7-1500_cpu_firmware:3.1.5");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:siplus_s7-1500_cpu_firmware:3.1.5");
  script_set_attribute(attribute:"generated_plugin", value:"former");
  script_end_attributes();

  script_category(ACT_GATHER_INFO);
  script_family(english:"Tenable.ot");

  script_copyright(english:"This script is Copyright (C) 2025-2026 and is owned by Tenable, Inc. or an Affiliate thereof.");

  script_dependencies("tenable_ot_api_integration.nasl");
  script_require_keys("Tenable.ot/Siemens");

  exit(0);
}


include('tenable_ot_cve_funcs.inc');

get_kb_item_or_exit('Tenable.ot/Siemens');

var asset = tenable_ot::assets::get(vendor:'Siemens');

var vuln_cpes = {
    "cpe:/o:siemens:simatic_s7-1500_cpu_firmware:3.1.5" :
        {"versionStartIncluding" : "3.1.5", "family" : "S71500", "orderNumbers" : ['6ES7518-4FX00-1AB0', '6ES7518-4AX00-1AC0', '6ES7518-4FX00-1AC0', '6ES7518-4AX00-1AB0']},
    "cpe:/o:siemens:siplus_s7-1500_cpu_firmware:3.1.5" :
        {"versionStartIncluding" : "3.1.5", "family" : "S71500", "orderNumbers" : ['6AG1518-4AX00-4AC0']}
};

tenable_ot::cve::compare_and_report(asset:asset, cpes:vuln_cpes, severity:SECURITY_HOLE);

Data

Build on a solid foundation with Vulners data

We provide the essential building blocks for cybersecurity solutions with comprehensive, structured, and constantly updated vulnerability and exploits data

Api

Power your application with Vulners API

The Vulners REST API offers reliable, high-performance access to vulnerability intelligence, with 99.9% SLA uptime and CDN-backed data delivery for seamless global access

App

Assess and manage vulnerabilities with Vulners tools

Built on top of Vulners' database and SDK, end-user solutions give security professionals and developers lightweight and powerful tools for vulnerability remediation

14 Feb 2026 00:00Current
7.3High risk
Vulners AI Score7.3
CVSS 3.16.6
EPSS0.00191
SSVC
11