Siemens SIMATIC S7-1500 NULL Pointer Dereference(CVE-2025-38214)
10
#%NASL_MIN_LEVEL 80900
##
# (C) Tenable, Inc.
##
include('compat.inc');
if (description)
{
script_id(505287);
script_version("1.2");
script_set_attribute(attribute:"plugin_modification_date", value:"2026/03/24");
script_cve_id("CVE-2025-38214");
script_name(english:"Siemens SIMATIC S7-1500 NULL Pointer Dereference(CVE-2025-38214)");
script_set_attribute(attribute:"synopsis", value:
"The remote OT asset is affected by a vulnerability.");
script_set_attribute(attribute:"description", value:
"In the Linux kernel, the following vulnerability has been resolved:
fbdev: Fix fb_set_var to prevent null-ptr-deref in fb_videomode_to_var
If fb_add_videomode() in fb_set_var() fails to allocate memory for
fb_videomode, later it may lead to a null-ptr dereference in
fb_videomode_to_var(), as the fb_info is registered while not having
the mode in modelist that is expected to be there, i.e. the one that
is described in fb_info->var.
================================================================
general protection fault, probably for non-canonical address
0xdffffc0000000001: 0000 [#1] PREEMPT SMP KASAN NOPTI KASAN: null-
ptr-deref in range [0x0000000000000008-0x000000000000000f] CPU: 1
PID: 30371 Comm: syz-executor.1 Not tainted 5.10.226-syzkaller #0
Hardware name: QEMU Standard PC (i440FX + PIIX, 1996), BIOS 1.12.0-1
04/01/2014 RIP: 0010:fb_videomode_to_var+0x24/0x610
drivers/video/fbdev/core/modedb.c:901 Call Trace:
display_to_var+0x3a/0x7c0 drivers/video/fbdev/core/fbcon.c:929
fbcon_resize+0x3e2/0x8f0 drivers/video/fbdev/core/fbcon.c:2071
resize_screen drivers/tty/vt/vt.c:1176 [inline]
vc_do_resize+0x53a/0x1170 drivers/tty/vt/vt.c:1263
fbcon_modechanged+0x3ac/0x6e0 drivers/video/fbdev/core/fbcon.c:2720
fbcon_update_vcs+0x43/0x60 drivers/video/fbdev/core/fbcon.c:2776
do_fb_ioctl+0x6d2/0x740 drivers/video/fbdev/core/fbmem.c:1128
fb_ioctl+0xe7/0x150 drivers/video/fbdev/core/fbmem.c:1203 vfs_ioctl
fs/ioctl.c:48 [inline] __do_sys_ioctl fs/ioctl.c:753 [inline]
__se_sys_ioctl fs/ioctl.c:739 [inline] __x64_sys_ioctl+0x19a/0x210
fs/ioctl.c:739 do_syscall_64+0x33/0x40 arch/x86/entry/common.c:46
entry_SYSCALL_64_after_hwframe+0x67/0xd1
================================================================
The reason is that fb_info->var is being modified in fb_set_var(), and
then fb_videomode_to_var() is called. If it fails to add the mode to
fb_info->modelist, fb_set_var() returns error, but does not restore
the old value of fb_info->var. Restore fb_info->var on failure the
same way it is done earlier in the function. Found by Linux
Verification Center (linuxtesting.org) with Syzkaller.
This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.");
script_set_attribute(attribute:"see_also", value:"https://cert-portal.siemens.com/productcert/html/ssa-082556.html");
script_set_attribute(attribute:"solution", value:
"Refer to the vendor advisory.");
script_set_cvss_base_vector("CVSS2#AV:L/AC:L/Au:S/C:N/I:N/A:C");
script_set_cvss_temporal_vector("CVSS2#E:U/RL:OF/RC:C");
script_set_cvss3_base_vector("CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H");
script_set_cvss3_temporal_vector("CVSS:3.0/E:U/RL:O/RC:C");
script_set_attribute(attribute:"cvss_score_source", value:"CVE-2025-38214");
script_set_attribute(attribute:"exploitability_ease", value:"No known exploits are available");
script_set_attribute(attribute:"exploit_available", value:"false");
script_cwe_id(476);
script_set_attribute(attribute:"vuln_publication_date", value:"2025/06/10");
script_set_attribute(attribute:"patch_publication_date", value:"2025/06/10");
script_set_attribute(attribute:"plugin_publication_date", value:"2026/03/23");
script_set_attribute(attribute:"plugin_type", value:"remote");
script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:simatic_s7-1500_cpu_firmware:3.1.5");
script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:siplus_s7-1500_cpu_firmware");
script_end_attributes();
script_category(ACT_GATHER_INFO);
script_family(english:"Tenable.ot");
script_copyright(english:"This script is Copyright (C) 2026 and is owned by Tenable, Inc. or an Affiliate thereof.");
script_dependencies("tenable_ot_api_integration.nasl");
script_require_keys("Tenable.ot/Siemens");
exit(0);
}
include('tenable_ot_cve_funcs.inc');
get_kb_item_or_exit('Tenable.ot/Siemens');
var asset = tenable_ot::assets::get(vendor:'Siemens');
var vuln_cpes = {
"cpe:/o:siemens:simatic_s7-1500_cpu_firmware:3.1.5" :
{"versionStartIncluding" : "3.1.5", "family" : "S71500", "orderNumbers" : ['6ES7518-4AX00-1AB0', '6ES7518-4AX00-1AC0', '6ES7518-4FX00-1AB0', '6ES7518-4FX00-1AC0']},
"cpe:/o:siemens:siplus_s7-1500_cpu_firmware" :
{"family" : "S71500", "orderNumbers" : ['6AG1518-4AX00-4AC0']}
};
tenable_ot::cve::compare_and_report(asset:asset, cpes:vuln_cpes, severity:SECURITY_WARNING);
Data
Build on a solid foundation with Vulners data
We provide the essential building blocks for cybersecurity solutions with comprehensive, structured, and constantly updated vulnerability and exploits data
Api
Power your application with Vulners API
The Vulners REST API offers reliable, high-performance access to vulnerability intelligence, with 99.9% SLA uptime and CDN-backed data delivery for seamless global access
App
Assess and manage vulnerabilities with Vulners tools
Built on top of Vulners' database and SDK, end-user solutions give security professionals and developers lightweight and powerful tools for vulnerability remediation
24 Mar 2026 00:00Current
6Medium risk
Vulners AI Score6
CVSS 3.15.5
EPSS0.00164