Siemens Industrial Products Improper Input Validation (CVE-2017-12741)

2022-02-0700:00:00
This script is Copyright (C) 2022-2024 and is owned by Tenable, Inc. or an Affiliate thereof.
www.tenable.com
12

7.8 High

CVSS2

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

NONE

Confidentiality Impact

NONE

Integrity Impact

NONE

Availability Impact

COMPLETE

AV:N/AC:L/Au:N/C:N/I:N/A:C

7.5 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

NONE

Integrity Impact

NONE

Availability Impact

HIGH

CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

0.003 Low

EPSS

Percentile

68.2%

A vulnerability has been identified in Development/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controller, Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200, Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200P, SIMATIC Compact Field Unit, SIMATIC ET200AL, SIMATIC ET200M (incl. SIPLUS variants), SIMATIC ET200MP IM155-5 PN BA (incl. SIPLUS variants), SIMATIC ET200MP IM155-5 PN HF (incl. SIPLUS variants), SIMATIC ET200MP IM155-5 PN ST (incl.
SIPLUS variants), SIMATIC ET200S (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN BA (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN HA (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN HF (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN HS (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN ST (incl. SIPLUS variants), SIMATIC ET200ecoPN, 16DI, DC24V, 8xM12 (6ES7141-6BH00-0AB0), SIMATIC ET200ecoPN, 16DO DC24V/1,3A, 8xM12 (6ES7142-6BH00-0AB0), SIMATIC ET200ecoPN, 4AO U/I 4xM12 (6ES7145-6HD00-0AB0), SIMATIC ET200ecoPN, 8 DIO, DC24V/1,3A, 8xM12 (6ES7147-6BG00-0AB0), SIMATIC ET200ecoPN, 8 DO, DC24V/2A, 8xM12 (6ES7142-6BR00-0AB0), SIMATIC ET200ecoPN, 8AI RTD/TC 8xM12 (6ES7144-6KD50-0AB0), SIMATIC ET200ecoPN, 8AI; 4 U/I; 4 RTD/TC 8xM12 (6ES7144-6KD00-0AB0), SIMATIC ET200ecoPN, 8DI, DC24V, 4xM12 (6ES7141-6BF00-0AB0), SIMATIC ET200ecoPN, 8DI, DC24V, 8xM12 (6ES7141-6BG00-0AB0), SIMATIC ET200ecoPN, 8DO, DC24V/0,5A, 4xM12 (6ES7142-6BF50-0AB0), SIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 4xM12 (6ES7142-6BF00-0AB0), SIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 8xM12 (6ES7142-6BG00-0AB0), SIMATIC ET200ecoPN: IO-Link Master (6ES7148-6JA00-0AB0), SIMATIC ET200pro, SIMATIC PN/PN Coupler (incl. SIPLUS NET variants), SIMATIC S7-1200 CPU family (incl. SIPLUS variants), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants), SIMATIC S7-1500 Software Controller, SIMATIC S7-200 SMART, SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants), SIMATIC S7-400 H V6 CPU family and below (incl. SIPLUS variants), SIMATIC S7-400 PN/DP V6 CPU family and below (incl. SIPLUS variants), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants), SIMATIC TDC CP51M1, SIMATIC TDC CPU555, SIMATIC WinAC RTX (F) 2010, SIMOCODE pro V EIP (incl. SIPLUS variants), SIMOCODE pro V PN (incl. SIPLUS variants), SIMOTION C, SIMOTION D (incl. SIPLUS variants), SIMOTION D4xx V4.4 for SINAMICS SM150i-2 w. PROFINET (incl.
SIPLUS variants), SIMOTION P V4.4 and V4.5, SIMOTION P V5, SINAMICS DCM w. PN, SINAMICS DCP w. PN, SINAMICS G110M w. PN, SINAMICS G120(C/P/D) w. PN (incl. SIPLUS variants), SINAMICS G130 V4.7 w. PN, SINAMICS G130 V4.8 w. PN, SINAMICS G150 V4.7 w. PN, SINAMICS G150 V4.8 w. PN, SINAMICS GH150 V4.7 w. PROFINET, SINAMICS GL150 V4.7 w. PROFINET, SINAMICS GM150 V4.7 w. PROFINET, SINAMICS S110 w. PN, SINAMICS S120 V4.7 SP1 w. PN (incl. SIPLUS variants), SINAMICS S120 V4.7 w. PN (incl. SIPLUS variants), SINAMICS S120 V4.8 w. PN (incl. SIPLUS variants), SINAMICS S120 prior to V4.7 w. PN (incl.
SIPLUS variants), SINAMICS S150 V4.7 w. PN, SINAMICS S150 V4.8 w. PN, SINAMICS SL150 V4.7.0 w. PROFINET, SINAMICS SL150 V4.7.4 w. PROFINET, SINAMICS SL150 V4.7.5 w. PROFINET, SINAMICS SM120 V4.7 w. PROFINET, SINAMICS V90 w. PN, SINUMERIK 840D sl, SIRIUS Soft Starter 3RW44 PN. Specially crafted packets sent to port 161/udp could cause a Denial-of-Service condition. The affected devices must be restarted manually.

This plugin only works with Tenable.ot. Please visit https://www.tenable.com/products/tenable-ot for more information.

#%NASL_MIN_LEVEL 70300
##
# (C) Tenable Network Security, Inc.
##

include('deprecated_nasl_level.inc');
include('compat.inc');

if (description)
{
  script_id(500271);
  script_version("1.8");
  script_set_attribute(attribute:"plugin_modification_date", value:"2024/03/04");

  script_cve_id("CVE-2017-12741");
  script_xref(name:"CEA-ID", value:"CEA-2019-0227");

  script_name(english:"Siemens Industrial Products Improper Input Validation (CVE-2017-12741)");

  script_set_attribute(attribute:"synopsis", value:
"The remote OT asset is affected by a vulnerability.");
  script_set_attribute(attribute:"description", value:
"A vulnerability has been identified in Development/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controller,
Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200, Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200P,
SIMATIC Compact Field Unit, SIMATIC ET200AL, SIMATIC ET200M (incl. SIPLUS variants), SIMATIC ET200MP IM155-5 PN BA
(incl. SIPLUS variants), SIMATIC ET200MP IM155-5 PN HF (incl. SIPLUS variants), SIMATIC ET200MP IM155-5 PN ST (incl.
SIPLUS variants), SIMATIC ET200S (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN BA (incl. SIPLUS variants), SIMATIC
ET200SP IM155-6 PN HA (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN HF (incl. SIPLUS variants), SIMATIC ET200SP
IM155-6 PN HS (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN ST (incl. SIPLUS variants), SIMATIC ET200ecoPN, 16DI,
DC24V, 8xM12 (6ES7141-6BH00-0AB0), SIMATIC ET200ecoPN, 16DO DC24V/1,3A, 8xM12 (6ES7142-6BH00-0AB0), SIMATIC ET200ecoPN,
4AO U/I 4xM12 (6ES7145-6HD00-0AB0), SIMATIC ET200ecoPN, 8 DIO, DC24V/1,3A, 8xM12 (6ES7147-6BG00-0AB0), SIMATIC
ET200ecoPN, 8 DO, DC24V/2A, 8xM12 (6ES7142-6BR00-0AB0), SIMATIC ET200ecoPN, 8AI RTD/TC 8xM12 (6ES7144-6KD50-0AB0),
SIMATIC ET200ecoPN, 8AI; 4 U/I; 4 RTD/TC 8xM12 (6ES7144-6KD00-0AB0), SIMATIC ET200ecoPN, 8DI, DC24V, 4xM12
(6ES7141-6BF00-0AB0), SIMATIC ET200ecoPN, 8DI, DC24V, 8xM12 (6ES7141-6BG00-0AB0), SIMATIC ET200ecoPN, 8DO, DC24V/0,5A,
4xM12 (6ES7142-6BF50-0AB0), SIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 4xM12 (6ES7142-6BF00-0AB0), SIMATIC ET200ecoPN, 8DO,
DC24V/1,3A, 8xM12 (6ES7142-6BG00-0AB0), SIMATIC ET200ecoPN: IO-Link Master (6ES7148-6JA00-0AB0), SIMATIC ET200pro,
SIMATIC PN/PN Coupler (incl. SIPLUS NET variants), SIMATIC S7-1200 CPU family (incl. SIPLUS variants), SIMATIC S7-1500
CPU family (incl. related ET200 CPUs and SIPLUS variants), SIMATIC S7-1500 Software Controller, SIMATIC S7-200 SMART,
SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants), SIMATIC S7-400 H V6 CPU family and below
(incl. SIPLUS variants), SIMATIC S7-400 PN/DP V6 CPU family and below (incl. SIPLUS variants), SIMATIC S7-400 PN/DP V7
CPU family (incl. SIPLUS variants), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants), SIMATIC TDC CP51M1, SIMATIC
TDC CPU555, SIMATIC WinAC RTX (F) 2010, SIMOCODE pro V EIP (incl. SIPLUS variants), SIMOCODE pro V PN (incl. SIPLUS
variants), SIMOTION C, SIMOTION D (incl. SIPLUS variants), SIMOTION D4xx V4.4 for SINAMICS SM150i-2 w. PROFINET (incl.
SIPLUS variants), SIMOTION P V4.4 and V4.5, SIMOTION P V5, SINAMICS DCM w. PN, SINAMICS DCP w. PN, SINAMICS G110M w. PN,
SINAMICS G120(C/P/D) w. PN (incl. SIPLUS variants), SINAMICS G130 V4.7 w. PN, SINAMICS G130 V4.8 w. PN, SINAMICS G150
V4.7 w. PN, SINAMICS G150 V4.8 w. PN, SINAMICS GH150 V4.7 w. PROFINET, SINAMICS GL150 V4.7 w. PROFINET, SINAMICS GM150
V4.7 w. PROFINET, SINAMICS S110 w. PN, SINAMICS S120 V4.7 SP1 w. PN (incl. SIPLUS variants), SINAMICS S120 V4.7 w. PN
(incl. SIPLUS variants), SINAMICS S120 V4.8 w. PN (incl. SIPLUS variants), SINAMICS S120 prior to V4.7 w. PN (incl.
SIPLUS variants), SINAMICS S150 V4.7 w. PN, SINAMICS S150 V4.8 w. PN, SINAMICS SL150 V4.7.0 w. PROFINET, SINAMICS SL150
V4.7.4 w. PROFINET, SINAMICS SL150 V4.7.5 w. PROFINET, SINAMICS SM120 V4.7 w. PROFINET, SINAMICS V90 w. PN, SINUMERIK
840D sl, SIRIUS Soft Starter 3RW44 PN. Specially crafted packets sent to port 161/udp could cause a Denial-of-Service
condition. The affected devices must be restarted manually.  

This plugin only works with Tenable.ot. Please visit
https://www.tenable.com/products/tenable-ot for more information.");
  script_set_attribute(attribute:"see_also", value:"https://cert-portal.siemens.com/productcert/pdf/ssa-346262.pdf");
  script_set_attribute(attribute:"see_also", value:"https://cert-portal.siemens.com/productcert/pdf/ssa-546832.pdf");
  script_set_attribute(attribute:"see_also", value:"https://www.cisa.gov/news-events/ics-advisories/icsa-17-339-01");
  script_set_attribute(attribute:"see_also", value:"https://www.securityfocus.com/bid/101964");
  script_set_attribute(attribute:"see_also", value:"https://cert-portal.siemens.com/productcert/pdf/ssa-141614.pdf");
  script_set_attribute(attribute:"solution", value:
"The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original
can be found at CISA.gov.

Siemens has provided firmware updates for the following products to fix this vulnerability:

- Development/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controller: Update to v4.1.1 Patch 05
- Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200P: Update to v4.5
- Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200: Update to v4.5
- SIMATIC ET 200MP IM155-5 PN BA (incl. SIPLUS variants): Update to v4.0.2
- SIMATIC ET 200MP IM155-5 PN HF (incl. SIPLUS variants): Update to v4.2
- SIMATIC ET 200MP IM155-5 PN ST (incl. SIPLUS variants): Update to v4.1
- SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants): Update to v1.1.0
- SIMATIC ET 200SP IM 155-6 PN HF (incl. SIPLUS variants): Update to v4.2.0
- SIMATIC ET 200SP IM 155-6 PN HS (incl. SIPLUS variants): Update to v4.0.1
- SIMATIC PN/PN Coupler (incl. SIPLUS NET variants): Update to v4.2.0
- SIMATIC S7-200 Smart: Update to v2.03.01
- SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants): Update to v3.X.16
- SIMATIC S7-400 H v6 CPU family and below (incl. SIPLUS variants): Update v6.0.8
- SIMATIC S7-400 PN/DP v6 CPU family and below (incl. SIPLUS variants): Update to v6.0.6
- SIMATIC S7-400 PN/DP v7 CPU family (incl. SIPLUS variants): Update to v7.0.2
- SIMATIC S7-410 v8 CPU family (incl. SIPLUS variants): Update to v8.2.1
- SIMATIC S7-1200 CPU family (incl. SIPLUS variants): Update to v4.2.3
- SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants): Upgrade to v2.0 and newer
- SIMATIC S7-1500 Software Controller: Upgrade to v2.0 and newer
- SIMATIC TDC CP51M1: Update to v1.1.8
- SIMATIC TDC CPU555: Update to v1.1.1
- SIMATIC WinAC RTX (F) 2010: Update to SP3 and apply BIOS and Microsoft Windows updates
- SIMOCODE pro V PN (incl. SIPLUS variants): Update to v2.1.1
- SIMOTION C: Update to v5.1 HF1
- SIMOTION D (incl. SIPLUS variants): Update to v5.1 HF1
- SIMOTION P v4.4 and 4.5: Update to v4.5 HF5 (please contact a Siemens representative for information on how to obtain
this update)
- SIMOTION P v5: Update to v5.1 HF1 (please contact a Siemens representative for information on how to obtain this
update)
- SINAMICS DCM w. PN: Update to v1.4 SP1 HF6
- SINAMICS DCP w. PN: Update to v1.2 HF2
- SINAMICS G110M w. PN: Update to v4.7 SP9 HF1
- SINAMICS G120(C/P/D) w. PN (incl. SIPLUS variants): Update to v4.7 SP9 HF1
- SINAMICS G130 v4.7 w. PN: Update to v4.7 HF29
- SINAMICS G130 v4.8 w. PN: Update to v4.8 HF4
- SINAMICS G150 v4.7 w. PN: Update to v4.7 HF29
- SINAMICS G150 v4.8 w. PN: Update to v4.8 HF4
- SINAMICS S110 w. PN: Update to v4.4 SP3 HF6
- SINAMICS S120 v4.7 SP1 w. PN (incl. SIPLUS variants): Update to latest version of v5.1 SP1
- SINAMICS S120 v4.7 w. PN (incl. SIPLUS variants): Update to v4.7 HF29
- SINAMICS S120 v4.8 w. PN: Update to v4.8 HF5
- SINAMICS S120 prior to v4.7 w. PN (incl. SIPLUS variants): Update to latest version of v5.1 SP1
- SINAMICS S150 v4.7 w.PN: Update to v4.7 HF29
- SINAMICS S150 v4.8 w.PN: Update to v4.8 HF4
- SINAMICS v90: Update to v1.02
- SINUMERIK 840D sl: Update to 4.8 SP3 (obtain update from a Siemens service organization)

Siemens is preparing further updates and recommends the following mitigations until patches are available:

- Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates
the vulnerability
- Protect network access to Port 161/UDP of affected devices
- Apply cell protection concept
- Use VPN for protecting network communication between cells
- Apply defense-in-depth

Siemens recommends users configure the operational environment according to the Siemens Operational Guidelines for
Industrial Security.

For more information on the vulnerability and more detailed mitigation instructions, please see Siemens Security
Advisory SSA-346262");
  script_set_cvss_base_vector("CVSS2#AV:N/AC:L/Au:N/C:N/I:N/A:C");
  script_set_cvss_temporal_vector("CVSS2#E:U/RL:OF/RC:C");
  script_set_cvss3_base_vector("CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H");
  script_set_cvss3_temporal_vector("CVSS:3.0/E:U/RL:O/RC:C");
  script_set_attribute(attribute:"cvss_score_source", value:"CVE-2017-12741");

  script_set_attribute(attribute:"exploitability_ease", value:"No known exploits are available");
  script_set_attribute(attribute:"exploit_available", value:"false");
  script_cwe_id(400);

  script_set_attribute(attribute:"vuln_publication_date", value:"2017/12/26");
  script_set_attribute(attribute:"patch_publication_date", value:"2017/12/26");
  script_set_attribute(attribute:"plugin_publication_date", value:"2022/02/07");

  script_set_attribute(attribute:"plugin_type", value:"remote");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:simatic_et_200al_firmware:-");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:simatic_et_200ecopn_firmware:-");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:simatic_et_200m_firmware:-");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:simatic_et_200mp_firmware:-");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:simatic_et_200pro_firmware:-");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:simatic_et_200s_firmware:-");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:simatic_et_200sp_firmware:-");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:simatic_s7-1200_firmware:-");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:simatic_s7-1500_controller_firmware:2.0");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:simatic_s7-1500_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:simatic_s7-200_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:simatic_s7-300_firmware:-");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:simatic_s7-400h_v6_firmware:6.0.8");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:simatic_s7-400pn%2fdp_v7_firmware:-");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:simatic_s7-400pn_v6_firmware:6.0.6");
  script_set_attribute(attribute:"generated_plugin", value:"former");
  script_end_attributes();

  script_category(ACT_GATHER_INFO);
  script_family(english:"Tenable.ot");

  script_copyright(english:"This script is Copyright (C) 2022-2024 and is owned by Tenable, Inc. or an Affiliate thereof.");

  script_dependencies("tenable_ot_api_integration.nasl");
  script_require_keys("Tenable.ot/Siemens");

  exit(0);
}


include('tenable_ot_cve_funcs.inc');

get_kb_item_or_exit('Tenable.ot/Siemens');

var asset = tenable_ot::assets::get(vendor:'Siemens');

var vuln_cpes = {
    "cpe:/o:siemens:simatic_s7-200_firmware" :
        {"versionEndExcluding" : "2.03.01", "family" : "S7200"},
    "cpe:/o:siemens:simatic_s7-400pn_v6_firmware:6.0.6" :
        {"versionStartIncluding" : "6.0", "versionEndExcluding" : "6.0.6", "family" : "S7400"},
    "cpe:/o:siemens:simatic_s7-400h_v6_firmware:6.0.8" :
        {"versionStartIncluding" : "6.0", "versionEndExcluding" : "6.0.8", "family" : "S7400"},
    "cpe:/o:siemens:simatic_s7-400pn%2fdp_v7_firmware:-" :
        {"versionStartIncluding" : "7.0", "versionEndExcluding" : "7.02", "family" : "S7400"},
    "cpe:/o:siemens:simatic_s7-300_firmware:-" :
        {"versionEndExcluding" : "3.x.16", "family" : "S7300"},
    "cpe:/o:siemens:simatic_s7-1200_firmware:-" :
        {"versionEndExcluding" : "4.2.3", "family" : "S71200"},
    "cpe:/o:siemens:simatic_s7-1500_firmware" :
        {"versionEndExcluding" : "2.0", "family" : "S71500"},
    "cpe:/o:siemens:simatic_s7-1500_controller_firmware:2.0" :
        {"versionEndIncluding" : "2.0", "versionStartIncluding" : "2.0", "family" : "S71500"},
    "cpe:/o:siemens:simatic_et_200al_firmware:-" :
        {"family" : "ET200"},
    "cpe:/o:siemens:simatic_et_200ecopn_firmware:-" :
        {"family" : "ET200"},
    "cpe:/o:siemens:simatic_et_200m_firmware:-" :
        {"family" : "ET200M"},
    "cpe:/o:siemens:simatic_et_200mp_firmware:-" :
        {"family" : "ET200"},
    "cpe:/o:siemens:simatic_et_200pro_firmware:-" :
        {"family" : "ET200"},
    "cpe:/o:siemens:simatic_et_200s_firmware:-" :
        {"family" : "ET200"},
    "cpe:/o:siemens:simatic_et_200sp_firmware:-" :
        {"family" : "ET200SP"}
};

tenable_ot::cve::compare_and_report(asset:asset, cpes:vuln_cpes, severity:SECURITY_HOLE);
VendorProductVersionCPE
siemenssimatic_et_200al_firmware-cpe:/o:siemens:simatic_et_200al_firmware:-
siemenssimatic_et_200ecopn_firmware-cpe:/o:siemens:simatic_et_200ecopn_firmware:-
siemenssimatic_et_200m_firmware-cpe:/o:siemens:simatic_et_200m_firmware:-
siemenssimatic_et_200mp_firmware-cpe:/o:siemens:simatic_et_200mp_firmware:-
siemenssimatic_et_200pro_firmware-cpe:/o:siemens:simatic_et_200pro_firmware:-
siemenssimatic_et_200s_firmware-cpe:/o:siemens:simatic_et_200s_firmware:-
siemenssimatic_et_200sp_firmware-cpe:/o:siemens:simatic_et_200sp_firmware:-
siemenssimatic_s7-1200_firmware-cpe:/o:siemens:simatic_s7-1200_firmware:-
siemenssimatic_s7-1500_controller_firmware2.0cpe:/o:siemens:simatic_s7-1500_controller_firmware:2.0
siemenssimatic_s7-1500_firmwarecpe:/o:siemens:simatic_s7-1500_firmware
Rows per page:
1-10 of 151

7.8 High

CVSS2

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

NONE

Confidentiality Impact

NONE

Integrity Impact

NONE

Availability Impact

COMPLETE

AV:N/AC:L/Au:N/C:N/I:N/A:C

7.5 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

NONE

Integrity Impact

NONE

Availability Impact

HIGH

CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

0.003 Low

EPSS

Percentile

68.2%

Related for TENABLE_OT_SIEMENS_CVE-2017-12741.NASL