Siemens SIMATIC CP 1543-1 Improper Input Validation (CVE-2016-8562)

2022-03-1500:00:00
This script is Copyright (C) 2022-2024 and is owned by Tenable, Inc. or an Affiliate thereof.
www.tenable.com
29

5.7 Medium

AI Score

Confidence

High

A vulnerability has been identified in SIMATIC CP 1543-1 (All versions < V2.0.28), SIPLUS NET CP 1543-1 (All versions < V2.0.28). Under special conditions it was possible to write SNMP variables on port 161/udp which should be read-only and should only be configured with TIA-Portal. A write to these variables could reduce the availability or cause a denial-of-service.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

#%NASL_MIN_LEVEL 70300
##
# (C) Tenable, Inc.
##

include('deprecated_nasl_level.inc');
include('compat.inc');

if (description)
{
  script_id(500605);
  script_version("1.6");
  script_set_attribute(attribute:"plugin_modification_date", value:"2024/03/04");

  script_cve_id("CVE-2016-8562");
  script_xref(name:"CISA-KNOWN-EXPLOITED", value:"2022/03/24");

  script_name(english:"Siemens SIMATIC CP 1543-1 Improper Input Validation (CVE-2016-8562)");

  script_set_attribute(attribute:"synopsis", value:
"The remote OT asset is affected by a vulnerability.");
  script_set_attribute(attribute:"description", value:
"A vulnerability has been identified in SIMATIC CP 1543-1 (All versions
< V2.0.28), SIPLUS NET CP 1543-1 (All versions < V2.0.28). Under
special conditions it was possible to write SNMP variables on port
161/udp which should be read-only and should only be configured with
TIA-Portal. A write to these variables could reduce the availability
or cause a denial-of-service.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.");
  # http://www.siemens.com/cert/pool/cert/siemens_security_advisory_ssa-672373.pdf
  script_set_attribute(attribute:"see_also", value:"http://www.nessus.org/u?f16a23d8");
  script_set_attribute(attribute:"see_also", value:"http://www.securityfocus.com/bid/94436");
  script_set_attribute(attribute:"see_also", value:"https://ics-cert.us-cert.gov/advisories/ICSA-16-327-01");
  script_set_attribute(attribute:"see_also", value:"https://cert-portal.siemens.com/productcert/pdf/ssa-672373.pdf");
  script_set_attribute(attribute:"solution", value:
"The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original
can be found at CISA.gov.

Siemens has released updates for the affected products and recommends users update to the latest versions.:

- SIMATIC CP 1543-1: Update to v2.0.28 or later version 
- SIPLUS NET CP 1543-1: Update to v2.0.28 or later version

As a general security measure, Siemens strongly recommends protecting network access to devices with appropriate
mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends configuring the
environment according to Siemens’ operational guidelines for industrial security, and following the recommendations in
the product manuals.

Additional information on industrial security by Siemens can be found at: https://www.siemens.com/industrialsecurity

For more information on this vulnerability and more detailed mitigation instructions, please see Siemens Security
Advisory SSA-672373");
  script_set_cvss_base_vector("CVSS2#AV:N/AC:M/Au:S/C:N/I:N/A:P");
  script_set_cvss_temporal_vector("CVSS2#E:F/RL:OF/RC:C");
  script_set_cvss3_base_vector("CVSS:3.0/AV:N/AC:H/PR:L/UI:N/S:U/C:N/I:N/A:H");
  script_set_cvss3_temporal_vector("CVSS:3.0/E:F/RL:O/RC:C");
  script_set_attribute(attribute:"cvss_score_source", value:"CVE-2016-8562");

  script_set_attribute(attribute:"exploitability_ease", value:"Exploits are available");
  script_set_attribute(attribute:"exploit_available", value:"true");
  script_cwe_id(20);

  script_set_attribute(attribute:"vuln_publication_date", value:"2016/11/18");
  script_set_attribute(attribute:"patch_publication_date", value:"2016/11/18");
  script_set_attribute(attribute:"plugin_publication_date", value:"2022/03/15");

  script_set_attribute(attribute:"plugin_type", value:"remote");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:simatic_cp_1543-1_firmware:-");
  script_end_attributes();

  script_category(ACT_GATHER_INFO);
  script_family(english:"Tenable.ot");

  script_copyright(english:"This script is Copyright (C) 2022-2024 and is owned by Tenable, Inc. or an Affiliate thereof.");

  script_dependencies("tenable_ot_api_integration.nasl");
  script_require_keys("Tenable.ot/Siemens");

  exit(0);
}


include('tenable_ot_cve_funcs.inc');

get_kb_item_or_exit('Tenable.ot/Siemens');

var asset = tenable_ot::assets::get(vendor:'Siemens');

var vuln_cpes = {
    "cpe:/o:siemens:simatic_cp_1543-1_firmware:-" :
        {"family" : "S71500", "versionEndExcluding" : "2.0.28"}
};

tenable_ot::cve::compare_and_report(asset:asset, cpes:vuln_cpes, severity:SECURITY_NOTE);
VendorProductVersionCPE
siemenssimatic_cp_1543-1_firmware-cpe:/o:siemens:simatic_cp_1543-1_firmware:-

5.7 Medium

AI Score

Confidence

High

Related for TENABLE_OT_SIEMENS_CVE-2016-8562.NASL