Lucene search

K
nessusThis script is Copyright (C) 2022-2024 and is owned by Tenable, Inc. or an Affiliate thereof.TENABLE_OT_SIEMENS_CVE-2016-4784.NASL
HistoryFeb 07, 2022 - 12:00 a.m.

Siemens SIPROTEC Information Disclosure (CVE-2016-4784)

2022-02-0700:00:00
This script is Copyright (C) 2022-2024 and is owned by Tenable, Inc. or an Affiliate thereof.
www.tenable.com
10
siemens siprotec
information disclosure
cve-2016-4784
firmware variant
profinet io
modbus tcp
dnp3 tcp
iec 104
en100 ethernet module
siprotec merging unit 6mu80
7sj686
7ut686
7sd686
7sj66
web server
remote attackers
tenable.ot.

CVSS2

5

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

NONE

Availability Impact

NONE

AV:N/AC:L/Au:N/C:P/I:N/A:N

CVSS3

5.3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

LOW

Integrity Impact

NONE

Availability Impact

NONE

CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N

AI Score

7

Confidence

Low

EPSS

0.005

Percentile

76.8%

A vulnerability has been identified in firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01;
Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02; SIPROTEC 7SJ686 : All versions < V 4.83; SIPROTEC 7UT686 : All versions < V 4.01; SIPROTEC 7SD686 : All versions < V 4.03; SIPROTEC 7SJ66 : All versions < V 4.20. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain sensitive device information if network access was obtained.

This plugin only works with Tenable.ot. Please visit https://www.tenable.com/products/tenable-ot for more information.

#%NASL_MIN_LEVEL 70300
##
# (C) Tenable Network Security, Inc.
##

include('deprecated_nasl_level.inc');
include('compat.inc');

if (description)
{
  script_id(500308);
  script_version("1.6");
  script_set_attribute(attribute:"plugin_modification_date", value:"2024/09/04");

  script_cve_id("CVE-2016-4784");
  script_xref(name:"ICSA", value:"16-140-02");
  script_xref(name:"ICSA", value:"17-187-03");

  script_name(english:"Siemens SIPROTEC Information Disclosure (CVE-2016-4784)");

  script_set_attribute(attribute:"synopsis", value:
"The remote OT asset is affected by a vulnerability.");
  script_set_attribute(attribute:"description", value:
"A vulnerability has been identified in firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01;
Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100
Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100
Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02; SIPROTEC 7SJ686 : All versions < V
4.83; SIPROTEC 7UT686 : All versions < V 4.01; SIPROTEC 7SD686 : All versions < V 4.03; SIPROTEC 7SJ66 : All versions <
V 4.20. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain sensitive
device information if network access was obtained.  

This plugin only works with Tenable.ot. Please visit
https://www.tenable.com/products/tenable-ot for more information.");
  # http://www.siemens.com/cert/pool/cert/siemens_security_advisory_ssa-547990.pdf
  script_set_attribute(attribute:"see_also", value:"http://www.nessus.org/u?04a75ef0");
  script_set_attribute(attribute:"see_also", value:"https://ics-cert.us-cert.gov/advisories/ICSA-16-140-02");
  script_set_attribute(attribute:"see_also", value:"http://www.securityfocus.com/bid/99471");
  script_set_attribute(attribute:"see_also", value:"http://www.securityfocus.com/bid/90773");
  # https://cert-portal.siemens.com/productcert/pdf/ssa-323211.pdf
  script_set_attribute(attribute:"see_also", value:"http://www.nessus.org/u?8b06cf13");
  script_set_attribute(attribute:"see_also", value:"https://ics-cert.us-cert.gov/advisories/ICSA-17-187-03");
  script_set_attribute(attribute:"solution", value:
"The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original
can be found at CISA.gov.

Siemens provides firmware update V4.27 for EN100 module included in SIPROTEC 4 and SIPROTEC Compact to fix the
vulnerabilities. The firmware updates can be found at the following locations on the Siemens website:

http://www.siemens.com/downloads/siprotec-4

http://www.siemens.com/downloads/siprotec-compact

For SIPROTEC Compact 7SJ80 with Ethernet Service Interface on Port A, Siemens provides firmware update V4.76. The
firmware update can be found at the following location on the Siemens website:

http://www.siemens.com/downloads/siprotec-compact

An attacker must have network access to the affected devices. For remaining affected products, Siemens recommends to
protect network access with appropriate mechanisms (e.g., firewalls, segmentation, VPN). It is advised to configure the
environment according to Siemens operational guidelines in order to run the devices in a protected IT environment.
Siemens provides guidance at the following location for operating the devices only within trusted networks:

http://www.siemens.com/gridsecurity

For more information on these vulnerabilities and more detailed mitigation instructions, please see Siemens Security
Advisory SSA-547990 at the following location:

http://www.siemens.com/cert/advisories");
  script_set_cvss_base_vector("CVSS2#AV:N/AC:L/Au:N/C:P/I:N/A:N");
  script_set_cvss_temporal_vector("CVSS2#E:U/RL:OF/RC:C");
  script_set_cvss3_base_vector("CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N");
  script_set_cvss3_temporal_vector("CVSS:3.0/E:U/RL:O/RC:C");
  script_set_attribute(attribute:"cvss_score_source", value:"CVE-2016-4784");

  script_set_attribute(attribute:"exploitability_ease", value:"No known exploits are available");
  script_set_attribute(attribute:"exploit_available", value:"false");
  script_cwe_id(200);

  script_set_attribute(attribute:"vuln_publication_date", value:"2016/05/31");
  script_set_attribute(attribute:"patch_publication_date", value:"2016/05/31");
  script_set_attribute(attribute:"plugin_publication_date", value:"2022/02/07");

  script_set_attribute(attribute:"plugin_type", value:"remote");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:siprotec_4_7sj686_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:siprotec_4_7ut686_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:siprotec_4_7sd686_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:siprotec_4_7sj66_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:siprotec_compact_7sj80_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:siprotec_compact_7rw80_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:siprotec_compact_7sj81_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:siprotec_compact_7sk81_firmware");
  script_set_attribute(attribute:"generated_plugin", value:"former");
  script_end_attributes();

  script_category(ACT_GATHER_INFO);
  script_family(english:"Tenable.ot");

  script_copyright(english:"This script is Copyright (C) 2022-2024 and is owned by Tenable, Inc. or an Affiliate thereof.");

  script_dependencies("tenable_ot_api_integration.nasl");
  script_require_keys("Tenable.ot/Siemens");

  exit(0);
}


include('tenable_ot_cve_funcs.inc');

get_kb_item_or_exit('Tenable.ot/Siemens');

var asset = tenable_ot::assets::get(vendor:'Siemens');

var vuln_cpes = {
  "cpe:/o:siemens:siprotec_4_7sj686_firmware" :
      {"versionEndExcluding" : "4.83", "family" : "Siprotec4"},
  "cpe:/o:siemens:siprotec_4_7ut686_firmware" :
      {"versionEndExcluding" : "4.01", "family" : "Siprotec4"},
  "cpe:/o:siemens:siprotec_4_7sd686_firmware" :
      {"versionEndExcluding" : "4.03", "family" : "Siprotec4"},
  "cpe:/o:siemens:siprotec_4_7sj66_firmware" :
      {"versionEndExcluding" : "4.20", "family" : "Siprotec4"},
  "cpe:/o:siemens:siprotec_compact_7sj80_firmware" :
      {"versionEndIncluding" : "4.75", "family" : "Siprotec"},
  "cpe:/o:siemens:siprotec_compact_7rw80_firmware" :
      {"family" : "Siprotec"},
  "cpe:/o:siemens:siprotec_compact_7sj81_firmware" :
      {"family" : "Siprotec"},
  "cpe:/o:siemens:siprotec_compact_7sk81_firmware" :
      {"family" : "Siprotec"}
};

tenable_ot::cve::compare_and_report(asset:asset, cpes:vuln_cpes, severity:SECURITY_WARNING);

CVSS2

5

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

NONE

Availability Impact

NONE

AV:N/AC:L/Au:N/C:P/I:N/A:N

CVSS3

5.3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

LOW

Integrity Impact

NONE

Availability Impact

NONE

CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N

AI Score

7

Confidence

Low

EPSS

0.005

Percentile

76.8%

Related for TENABLE_OT_SIEMENS_CVE-2016-4784.NASL