Lucene search

K
nessusThis script is Copyright (C) 2023 and is owned by Tenable, Inc. or an Affiliate thereof.TENABLE_OT_SIEMENS_CVE-2013-3634.NASL
HistoryJan 25, 2023 - 12:00 a.m.

Siemens SCALANCE Privilege Escalation (CVE-2013-3634)

2023-01-2500:00:00
This script is Copyright (C) 2023 and is owned by Tenable, Inc. or an Affiliate thereof.
www.tenable.com
8
siemens
scalance
snmpv3
privilege escalation
vulnerability
tenable.ot

AI Score

6.8

Confidence

Low

EPSS

0.002

Percentile

53.5%

A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (Versions < V5.0.0 for CVE-2013-3633 and versions < V4.5.0 for CVE-2013-3634), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.1.0). The implementation of SNMPv3 does not check the user credentials sufficiently. Therefore, an attacker is able to execute SNMP commands without correct credentials.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

#%NASL_MIN_LEVEL 80900
##
# (C) Tenable, Inc.
##

include('compat.inc');

if (description)
{
  script_id(500759);
  script_version("1.5");
  script_set_attribute(attribute:"plugin_modification_date", value:"2023/12/14");

  script_cve_id("CVE-2013-3634");

  script_name(english:"Siemens SCALANCE Privilege Escalation (CVE-2013-3634)");

  script_set_attribute(attribute:"synopsis", value:
"The remote OT asset is affected by a vulnerability.");
  script_set_attribute(attribute:"description", value:
"A vulnerability has been identified in SCALANCE X-200 switch family
(incl. SIPLUS NET variants) (Versions < V5.0.0 for CVE-2013-3633 and
versions < V4.5.0 for CVE-2013-3634), SCALANCE X-200IRT switch family
(incl. SIPLUS NET variants) (All versions < V5.1.0). The
implementation of SNMPv3 does not check the user credentials
sufficiently. Therefore, an attacker is able to execute SNMP commands
without correct credentials.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.");
  script_set_attribute(attribute:"see_also", value:"https://cert-portal.siemens.com/productcert/pdf/ssa-170686.pdf");
  script_set_attribute(attribute:"see_also", value:"https://www.cisa.gov/news-events/ics-advisories/icsa-13-149-01");
  script_set_attribute(attribute:"solution", value:
"The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original
can be found at CISA.gov.

Siemens recommends updating these products:

- SCALANCE X-200 switch family: Update to v5.0.0 (released in 2013), or any later version (currently v5.2.4) 
- SCALANCE X-200IRT switch family: Update to v5.1.0 (released in 2013), or any later version (currently v5.4.2)

If it is not possible to install the firmware update, mitigate the SNMP vulnerability by either disabling SNMP or
completely disabling read-write access.

As a general security measure, Siemens strongly recommends protecting network access to devices with appropriate
mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends configuring the
environment according to SiemensҀ™

Operational Guidelines for Industrial Security and to follow the recommendations in the product manuals.

Additional information on industrial security by Siemens can be found at:

https://www.siemens.com/industrialsecurity

For more information on this vulnerability and more detailed mitigation instructions, please see Siemens security
advisory SSA-170686 at the following location:

http://www.siemens.com/cert/advisories");
  script_set_cvss_base_vector("CVSS2#AV:N/AC:L/Au:N/C:P/I:P/A:P");
  script_set_cvss_temporal_vector("CVSS2#E:U/RL:OF/RC:C");
  script_set_cvss3_base_vector("CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H");
  script_set_cvss3_temporal_vector("CVSS:3.0/E:U/RL:O/RC:C");
  script_set_attribute(attribute:"cvss_score_source", value:"CVE-2013-3634");

  script_set_attribute(attribute:"exploitability_ease", value:"No known exploits are available");
  script_set_attribute(attribute:"exploit_available", value:"false");
  script_cwe_id(20);

  script_set_attribute(attribute:"vuln_publication_date", value:"2013/05/24");
  script_set_attribute(attribute:"patch_publication_date", value:"2013/05/24");
  script_set_attribute(attribute:"plugin_publication_date", value:"2023/01/25");

  script_set_attribute(attribute:"plugin_type", value:"remote");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:scalance_x200_series_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:siemens:scalance_x200irt_series_firmware");
  script_set_attribute(attribute:"generated_plugin", value:"former");
  script_end_attributes();

  script_category(ACT_GATHER_INFO);
  script_family(english:"Tenable.ot");

  script_copyright(english:"This script is Copyright (C) 2023 and is owned by Tenable, Inc. or an Affiliate thereof.");

  script_dependencies("tenable_ot_api_integration.nasl");
  script_require_keys("Tenable.ot/Siemens");

  exit(0);
}


include('tenable_ot_cve_funcs.inc');

get_kb_item_or_exit('Tenable.ot/Siemens');

var asset = tenable_ot::assets::get(vendor:'Siemens');

var vuln_cpes = {
    "cpe:/o:siemens:scalance_x200_series_firmware" :
        {"versionEndExcluding" : "4.5.0", "family" : "SCALANCEX200"},
    "cpe:/o:siemens:scalance_x200irt_series_firmware" :
        {"versionEndExcluding" : "5.1.0", "family" : "SCALANCEX200IRT"}
};

tenable_ot::cve::compare_and_report(asset:asset, cpes:vuln_cpes, severity:SECURITY_HOLE);

AI Score

6.8

Confidence

Low

EPSS

0.002

Percentile

53.5%

Related for TENABLE_OT_SIEMENS_CVE-2013-3634.NASL