Schneider Electric Modicon M221 Information Management Errors (CVE-2018-7790)

2023-03-0100:00:00
This script is Copyright (C) 2023-2024 and is owned by Tenable, Inc. or an Affiliate thereof.
www.tenable.com
11
schneider electric
modicon m221
information management errors
cve-2018-7790
vulnerability
unauthorized users
replay
authentication sequences
original program
plc
fix
somachine basic
v1.6.2.0
sp2

9.5 High

AI Score

Confidence

High

0.002 Low

EPSS

Percentile

60.2%

An Information Management Error vulnerability exists in Schneider Electric’s Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to replay authentication sequences. If an attacker exploits this vulnerability and connects to a Modicon M221, the attacker can upload the original program from the PLC.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

#%NASL_MIN_LEVEL 80900
##
# (C) Tenable, Inc.
##

include('compat.inc');

if (description)
{
  script_id(500858);
  script_version("1.8");
  script_set_attribute(attribute:"plugin_modification_date", value:"2024/03/04");

  script_cve_id("CVE-2018-7790");

  script_name(english:"Schneider Electric Modicon M221 Information Management Errors (CVE-2018-7790)");

  script_set_attribute(attribute:"synopsis", value:
"The remote OT asset is affected by a vulnerability.");
  script_set_attribute(attribute:"description", value:
"An Information Management Error vulnerability exists in Schneider
Electric's Modicon M221 product (all references, all versions prior to
firmware V1.6.2.0). The vulnerability allows unauthorized users to
replay authentication sequences. If an attacker exploits this
vulnerability and connects to a Modicon M221, the attacker can upload
the original program from the PLC.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.");
  script_set_attribute(attribute:"see_also", value:"http://www.securityfocus.com/bid/105182");
  script_set_attribute(attribute:"see_also", value:"https://www.cisa.gov/news-events/ics-advisories/icsa-18-240-01");
  # https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2018-235-01
  script_set_attribute(attribute:"see_also", value:"http://www.nessus.org/u?f8a96d9c");
  script_set_attribute(attribute:"solution", value:
"The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original
can be found at CISA.gov.

A fix for these vulnerabilities is implemented in Modicon M221 Firmware v1.6.2.0, delivered within SoMachine Basic v1.6
SP2, which is available for download below, or by using Schneider Electric Software Update tool:

https://www.schneider-electric.com/en/download/document/SoMachineBasicV1.6SP2/

As a temporary mitigation, Modicon M221 users should take the following measures:

- Set up a firewall blocking all remote/external access to Port 502.
- Within the Modicon M221 application, users must disable all unused protocols, especially programming protocol, as
described in section “Configuring Ethernet Network” of SoMachine Basic online help. This will prevent remote programming
of the M221 PLC.

Schneider Electric’s security notice SEVD-2018-235-01 is available at the following location:

https://www.schneider-electric.com/en/download/document/SEVD-2018-235-01/");
  script_set_cvss_base_vector("CVSS2#AV:N/AC:L/Au:N/C:P/I:P/A:P");
  script_set_cvss_temporal_vector("CVSS2#E:U/RL:OF/RC:C");
  script_set_cvss3_base_vector("CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H");
  script_set_cvss3_temporal_vector("CVSS:3.0/E:U/RL:O/RC:C");
  script_set_attribute(attribute:"cvss_score_source", value:"CVE-2018-7790");

  script_set_attribute(attribute:"exploitability_ease", value:"No known exploits are available");
  script_set_attribute(attribute:"exploit_available", value:"false");
  script_cwe_id(294);

  script_set_attribute(attribute:"vuln_publication_date", value:"2018/08/29");
  script_set_attribute(attribute:"patch_publication_date", value:"2018/08/29");
  script_set_attribute(attribute:"plugin_publication_date", value:"2023/03/01");

  script_set_attribute(attribute:"plugin_type", value:"remote");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:schneider-electric:modicon_m221_series_firmware");
  script_set_attribute(attribute:"generated_plugin", value:"current");
  script_end_attributes();

  script_category(ACT_GATHER_INFO);
  script_family(english:"Tenable.ot");

  script_copyright(english:"This script is Copyright (C) 2023-2024 and is owned by Tenable, Inc. or an Affiliate thereof.");

  script_dependencies("tenable_ot_api_integration.nasl");
  script_require_keys("Tenable.ot/Schneider");

  exit(0);
}


include('tenable_ot_cve_funcs.inc');

get_kb_item_or_exit('Tenable.ot/Schneider');

var asset = tenable_ot::assets::get(vendor:'Schneider');

var vuln_cpes = {
    "cpe:/o:schneider-electric:modicon_m221_series_firmware" :
        {"versionEndExcluding" : "1.6.2.0", "family" : "ModiconM221"}
};

tenable_ot::cve::compare_and_report(asset:asset, cpes:vuln_cpes, severity:SECURITY_HOLE);
VendorProductVersionCPE
schneider-electricmodicon_m221_series_firmwarecpe:/o:schneider-electric:modicon_m221_series_firmware

9.5 High

AI Score

Confidence

High

0.002 Low

EPSS

Percentile

60.2%

Related for TENABLE_OT_SCHNEIDER_CVE-2018-7790.NASL