Lucene search
+L

Rockwell Automation CompactLogix Exposure of Sensitive System Information to an Unauthorized Control Sphere (CVE-2026-9307)

🗓️ 29 Jul 2026 00:00:00Reported by TenableType 
nessus
 nessus
🔗 www.tenable.com👁 7 Views

CompactLogix 5370 exposes CIP Connection Identifiers to unauthenticated users, enabling malicious packets.

Related
Refs
Code
ReporterTitlePublishedViews
Family
circl
Circl
CVE-2026-9307
16 Jun 202605:00
circl
cve
CVE
CVE-2026-9307
16 Jun 202613:42
cve
cvelist
Cvelist
CVE-2026-9307 Rockwell Automation CompactLogix 5370 Controllers – Multiple Vulnerabilities
16 Jun 202613:42
cvelist
euvd
EUVD
EUVD-2026-37118
16 Jun 202613:42
euvd
nvd
NVD
CVE-2026-9307
16 Jun 202615:16
nvd
ptsecurity
Positive Technologies
PT-2026-49718
16 Jun 202600:00
ptsecurity
vulnrichment
Vulnrichment
CVE-2026-9307 Rockwell Automation CompactLogix 5370 Controllers – Multiple Vulnerabilities
16 Jun 202613:42
vulnrichment
#%NASL_MIN_LEVEL 80900
##
# (C) Tenable, Inc.
##

include('compat.inc');

if (description)
{
  script_id(505886);
  script_version("1.3");
  script_set_attribute(attribute:"plugin_modification_date", value:"2026/07/30");

  script_cve_id("CVE-2026-9307");
  script_xref(name:"ICSA", value:"26-167-04");

  script_name(english:"Rockwell Automation CompactLogix Exposure of Sensitive System Information to an Unauthorized Control Sphere (CVE-2026-9307)");

  script_set_attribute(attribute:"synopsis", value:
"The remote OT asset is affected by a vulnerability.");
  script_set_attribute(attribute:"description", value:
"A sensitive information disclosure security issue exists within the
affected CompactLogix 5370 controllers. The controller's web server
exposes CIP Connection IDs on the diagnostics webpage, which are
accessible to any unauthenticated user on the network. This
information can be leveraged by an attacker to construct malicious
packets, leading to a denial-of-service condition.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.");
  # https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1776.html
  script_set_attribute(attribute:"see_also", value:"http://www.nessus.org/u?74a39431");
  script_set_attribute(attribute:"see_also", value:"https://www.cisa.gov/news-events/ics-advisories/icsa-26-167-04");
  script_set_attribute(attribute:"solution", value:
"The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original
can be found at CISA.gov.");
  script_set_cvss3_base_vector("CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N");
  script_set_cvss3_temporal_vector("CVSS:3.0/E:U/RL:O/RC:C");
  script_set_attribute(attribute:"cvss4_vector", value:"CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:L/VI:N/VA:N/SC:N/SI:N/SA:N");
  script_set_attribute(attribute:"cvss4_threat_vector", value:"CVSS:4.0/E:U");
  script_set_attribute(attribute:"cvss_score_source", value:"CVE-2026-9307");

  script_set_attribute(attribute:"exploitability_ease", value:"No known exploits are available");
  script_set_attribute(attribute:"exploit_available", value:"false");
  script_cwe_id(497);

  script_set_attribute(attribute:"vuln_publication_date", value:"2026/06/16");
  script_set_attribute(attribute:"patch_publication_date", value:"2026/06/16");
  script_set_attribute(attribute:"plugin_publication_date", value:"2026/07/29");

  script_set_attribute(attribute:"plugin_type", value:"remote");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:rockwellautomation:compactlogix_5370_l1_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:rockwellautomation:compactlogix_5370_l2_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:rockwellautomation:compactlogix_5370_l3_firmware");
  script_set_attribute(attribute:"generated_plugin", value:"former");
  script_end_attributes();

  script_category(ACT_GATHER_INFO);
  script_family(english:"Tenable.ot");

  script_copyright(english:"This script is Copyright (C) 2026 and is owned by Tenable, Inc. or an Affiliate thereof.");

  script_dependencies("tenable_ot_api_integration.nasl");
  script_require_keys("Tenable.ot/Rockwell");

  exit(0);
}


include('tenable_ot_cve_funcs.inc');

get_kb_item_or_exit('Tenable.ot/Rockwell');

var asset = tenable_ot::assets::get(vendor:'Rockwell');

var vuln_cpes = {
    "cpe:/o:rockwellautomation:compactlogix_5370_l1_firmware" :
        {"versionEndExcluding" : "38.011", "family" : "CompactLogix5370"},
    "cpe:/o:rockwellautomation:compactlogix_5370_l2_firmware" :
        {"versionEndExcluding" : "38.011", "family" : "CompactLogix5370"},
    "cpe:/o:rockwellautomation:compactlogix_5370_l3_firmware" :
        {"versionEndExcluding" : "38.011", "family" : "CompactLogix5370"}
};

tenable_ot::cve::compare_and_report(asset:asset, cpes:vuln_cpes, severity:SECURITY_WARNING);

Data

Build on a solid foundation with Vulners data

We provide the essential building blocks for cybersecurity solutions with comprehensive, structured, and constantly updated vulnerability and exploits data

Api

Power your application with Vulners API

The Vulners REST API offers reliable, high-performance access to vulnerability intelligence, with 99.9% SLA uptime and CDN-backed data delivery for seamless global access

App

Assess and manage vulnerabilities with Vulners tools

Built on top of Vulners' database and SDK, end-user solutions give security professionals and developers lightweight and powerful tools for vulnerability remediation

30 Jul 2026 00:00Current
5.5Medium risk
Vulners AI Score5.5
CVSS 46.3
EPSS0.00298
SSVC
7