Lucene search
+L

Rockwell Automation ControlLogix Ethernet Modules Insecure Default Initialization of Resource (CVE-2025-7353)

🗓️ 29 Jul 2026 00:00:00Reported by TenableType 
nessus
 nessus
🔗 www.tenable.com👁 3 Views

Rockwell ControlLogix Ethernet modules ship with web debugger enabled by default, enabling remote memory dumps, memory modification, and execution control.

Related
Refs
Code
#%NASL_MIN_LEVEL 80900
##
# (C) Tenable, Inc.
##

include('compat.inc');

if (description)
{
  script_id(505887);
  script_version("1.1");
  script_set_attribute(attribute:"plugin_modification_date", value:"2026/07/29");

  script_cve_id("CVE-2025-7353");
  script_xref(name:"ICSA", value:"25-226-28");

  script_name(english:"Rockwell Automation ControlLogix Ethernet Modules Insecure Default Initialization of Resource (CVE-2025-7353)");

  script_set_attribute(attribute:"synopsis", value:
"The remote OT asset is affected by a vulnerability.");
  script_set_attribute(attribute:"description", value:
"The affected ControlLogix Ethernet modules ship with a web-based
debugger (WDB) agent enabled by default. A remote attacker who can
reach the module using a specific IP address can connect to the WDB
agent and perform memory dumps, modify memory, and control the
execution flow of the module.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.");
  # https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1732.html
  script_set_attribute(attribute:"see_also", value:"http://www.nessus.org/u?3042e2bb");
  script_set_attribute(attribute:"see_also", value:"https://www.cisa.gov/news-events/ics-advisories/icsa-25-226-28");
  script_set_attribute(attribute:"solution", value:
"The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original
can be found at CISA.gov.

Rockwell Automation recommends that ControlLogix Ethernet Module users update to Version 12.001 if possible. If users
are unable to upgrade to Version 12.001, security best practices should be applied.");
  script_set_cvss3_base_vector("CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H");
  script_set_attribute(attribute:"cvss_score_source", value:"CVE-2025-7353");

  script_cwe_id(1188);

  script_set_attribute(attribute:"vuln_publication_date", value:"2025/08/14");
  script_set_attribute(attribute:"patch_publication_date", value:"2025/08/14");
  script_set_attribute(attribute:"plugin_publication_date", value:"2026/07/29");

  script_set_attribute(attribute:"plugin_type", value:"remote");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:rockwellautomation:1756-en2t_series_d_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:rockwellautomation:1756-en2f_series_c_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:rockwellautomation:1756-en2tr_series_c_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:rockwellautomation:1756-en3tr_series_b_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:rockwellautomation:1756-en2tp_series_a_firmware");
  script_set_attribute(attribute:"generated_plugin", value:"former");
  script_end_attributes();

  script_category(ACT_GATHER_INFO);
  script_family(english:"Tenable.ot");

  script_copyright(english:"This script is Copyright (C) 2026 and is owned by Tenable, Inc. or an Affiliate thereof.");

  script_dependencies("tenable_ot_api_integration.nasl");
  script_require_keys("Tenable.ot/Rockwell");

  exit(0);
}


include('tenable_ot_cve_funcs.inc');

get_kb_item_or_exit('Tenable.ot/Rockwell');

var asset = tenable_ot::assets::get(vendor:'Rockwell');

var vuln_cpes = {
    "cpe:/o:rockwellautomation:1756-en2t_series_d_firmware" :
        {"versionEndExcluding" : "12.001", "family" : "ControlLogix"},
    "cpe:/o:rockwellautomation:1756-en2f_series_c_firmware" :
        {"versionEndExcluding" : "12.001", "family" : "ControlLogix"},
    "cpe:/o:rockwellautomation:1756-en2tr_series_c_firmware" :
        {"versionEndExcluding" : "12.001", "family" : "ControlLogix"},
    "cpe:/o:rockwellautomation:1756-en3tr_series_b_firmware" :
        {"versionEndExcluding" : "12.001", "family" : "ControlLogix"},
    "cpe:/o:rockwellautomation:1756-en2tp_series_a_firmware" :
        {"versionEndExcluding" : "12.001", "family" : "ControlLogix"}
};

tenable_ot::cve::compare_and_report(asset:asset, cpes:vuln_cpes, severity:SECURITY_HOLE);

Data

Build on a solid foundation with Vulners data

We provide the essential building blocks for cybersecurity solutions with comprehensive, structured, and constantly updated vulnerability and exploits data

Api

Power your application with Vulners API

The Vulners REST API offers reliable, high-performance access to vulnerability intelligence, with 99.9% SLA uptime and CDN-backed data delivery for seamless global access

App

Assess and manage vulnerabilities with Vulners tools

Built on top of Vulners' database and SDK, end-user solutions give security professionals and developers lightweight and powerful tools for vulnerability remediation

29 Jul 2026 00:00Current
7.4High risk
Vulners AI Score7.4
CVSS 49.3
EPSS0.0081
SSVC
3