HistoryDec 23, 2022 - 12:00 a.m.

Rockwell Automation GuardLogix and ControlLogix controllers Improper Input Validation (CVE-2022-3157)

2022-12-2300:00:00
This script is Copyright (C) 2022-2024 and is owned by Tenable, Inc. or an Affiliate thereof.
www.tenable.com
21
rockwell automation
controllers
vulnerability
cve-2022-3157
major non-recoverable fault (mnrf)
denial-of-service (dos)
tenable.ot
scanner

8.6 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

CHANGED

Confidentiality Impact

NONE

Integrity Impact

NONE

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H

0.001 Low

EPSS

Percentile

25.1%

A vulnerability exists in the Rockwell Automation controllers that allows a malformed CIP request to cause a major non- recoverable fault (MNRF) and a denial-of-service condition (DOS).

  • A vulnerability exists in the Rockwell Automation controllers that allows a malformed CIP request to cause a major non-recoverable fault (MNRF) and a denial-of-service condition (DOS). (CVE-2022-3157)

This plugin only works with Tenable.ot. Please visit https://www.tenable.com/products/tenable-ot for more information.

#%NASL_MIN_LEVEL 80900
##
# (C) Tenable, Inc.
##

include('compat.inc');

if (description)
{
  script_id(500717);
  script_version("1.9");
  script_set_attribute(attribute:"plugin_modification_date", value:"2024/03/04");

  script_cve_id("CVE-2022-3157");

  script_name(english:"Rockwell Automation GuardLogix and ControlLogix controllers Improper Input Validation (CVE-2022-3157)");

  script_set_attribute(attribute:"synopsis", value:
"The remote OT asset is affected by a vulnerability.");
  script_set_attribute(attribute:"description", value:
"A vulnerability exists in the Rockwell Automation controllers that allows a malformed CIP request to cause a major non-
recoverable fault (MNRF) and a denial-of-service condition (DOS).

  - A vulnerability exists in the Rockwell Automation controllers that allows a malformed CIP request to cause
    a major non-recoverable fault (MNRF) and a denial-of-service condition (DOS). (CVE-2022-3157)

This plugin only works with Tenable.ot. Please visit https://www.tenable.com/products/tenable-ot for more information.");
  # https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1137757
  script_set_attribute(attribute:"see_also", value:"http://www.nessus.org/u?c2e3a3c5");
  script_set_attribute(attribute:"see_also", value:"https://www.cisa.gov/news-events/ics-advisories/icsa-22-354-02");
  # https://www.rockwellautomation.com/en-us/support/advisory.PN1613.html
  script_set_attribute(attribute:"see_also", value:"http://www.nessus.org/u?ce802123");
  script_set_attribute(attribute:"solution", value:
"The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original
can be found at CISA.gov.

Rockwell Automation has released product updates addressing this vulnerability:

- For CompactLogix 5370, Compact GuardLogix 5370, ControlLogix 5570, GuardLogix 5570: Users should upgrade to versions
33.013, 34.011, or later.
- For ControlLogix 5570 redundancy: Users should upgrade to versions 33.052, 34.051, or later.

Rockwell Automation encourages users to apply mitigations on their security best practices web page to reduce risk.

Users should see the Rockwell Automation security advisory for more information.");
  script_set_cvss_base_vector("CVSS2#AV:N/AC:L/Au:N/C:N/I:N/A:C");
  script_set_cvss_temporal_vector("CVSS2#E:U/RL:OF/RC:C");
  script_set_cvss3_base_vector("CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H");
  script_set_cvss3_temporal_vector("CVSS:3.0/E:U/RL:O/RC:C");
  script_set_attribute(attribute:"cvss_score_source", value:"CVE-2022-3157");

  script_set_attribute(attribute:"exploitability_ease", value:"No known exploits are available");
  script_set_attribute(attribute:"exploit_available", value:"false");

  script_set_attribute(attribute:"vuln_publication_date", value:"2022/12/16");
  script_set_attribute(attribute:"patch_publication_date", value:"2022/12/16");
  script_set_attribute(attribute:"plugin_publication_date", value:"2022/12/23");

  script_set_attribute(attribute:"plugin_type", value:"remote");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:rockwellautomation:compact_guardlogix_5370_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:rockwellautomation:compact_guardlogix_5380_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:rockwellautomation:compactlogix_5370_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:rockwellautomation:controllogix_5570_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:rockwellautomation:controllogix_5570_redundancy_firmware");
  script_set_attribute(attribute:"cpe", value:"cpe:/o:rockwellautomation:guardlogix_5570_firmware");
  script_set_attribute(attribute:"generated_plugin", value:"current");
  script_end_attributes();

  script_category(ACT_GATHER_INFO);
  script_family(english:"Tenable.ot");

  script_copyright(english:"This script is Copyright (C) 2022-2024 and is owned by Tenable, Inc. or an Affiliate thereof.");

  script_dependencies("tenable_ot_api_integration.nasl");
  script_require_keys("Tenable.ot/Rockwell");

  exit(0);
}


include('tenable_ot_cve_funcs.inc');

get_kb_item_or_exit('Tenable.ot/Rockwell');

var asset = tenable_ot::assets::get(vendor:'Rockwell');

var vuln_cpes = {
    "cpe:/o:rockwellautomation:compactlogix_5370_firmware" :
        {"versionEndIncluding" : "33", "versionStartIncluding" : "20", "family" : "CompactLogix5370"},
    "cpe:/o:rockwellautomation:compact_guardlogix_5370_firmware" :
        {"versionEndIncluding" : "33", "versionStartIncluding" : "28", "family" : "GuardLogix5370"},
    "cpe:/o:rockwellautomation:compact_guardlogix_5380_firmware" :
        {"versionEndIncluding" : "33", "versionStartIncluding" : "28", "family" : "GuardLogix5380"},
    "cpe:/o:rockwellautomation:controllogix_5570_firmware" :
        {"versionEndIncluding" : "33", "versionStartIncluding" : "20", "family" : "ControlLogix5570"},
    "cpe:/o:rockwellautomation:controllogix_5570_redundancy_firmware" :
        {"versionEndIncluding" : "33", "versionStartIncluding" : "20", "family" : "ControlLogix5570"},
    "cpe:/o:rockwellautomation:guardlogix_5570_firmware" :
        {"versionEndIncluding" : "33", "versionStartIncluding" : "20", "family" : "GuardLogix5570"}
};

tenable_ot::cve::compare_and_report(asset:asset, cpes:vuln_cpes, severity:SECURITY_HOLE);
VendorProductVersionCPE
rockwellautomationcompact_guardlogix_5370_firmwarecpe:/o:rockwellautomation:compact_guardlogix_5370_firmware
rockwellautomationcompact_guardlogix_5380_firmwarecpe:/o:rockwellautomation:compact_guardlogix_5380_firmware
rockwellautomationcompactlogix_5370_firmwarecpe:/o:rockwellautomation:compactlogix_5370_firmware
rockwellautomationcontrollogix_5570_firmwarecpe:/o:rockwellautomation:controllogix_5570_firmware
rockwellautomationcontrollogix_5570_redundancy_firmwarecpe:/o:rockwellautomation:controllogix_5570_redundancy_firmware
rockwellautomationguardlogix_5570_firmwarecpe:/o:rockwellautomation:guardlogix_5570_firmware

8.6 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

CHANGED

Confidentiality Impact

NONE

Integrity Impact

NONE

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H

0.001 Low

EPSS

Percentile

25.1%

Related for TENABLE_OT_ROCKWELL_CVE-2022-3157.NASL