Siemens SIMATIC WinCC (TIA Portal) 13.x < 13 SP1 Upd2 Multiple Vulnerabilities (SSA-487246)

2015-04-1700:00:00
This script is Copyright (C) 2015-2024 and is owned by Tenable, Inc. or an Affiliate thereof.
www.tenable.com
7

6.8 Medium

CVSS2

Attack Vector

NETWORK

Attack Complexity

MEDIUM

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

PARTIAL

Availability Impact

PARTIAL

AV:N/AC:M/Au:N/C:P/I:P/A:P

0.007 Low

EPSS

Percentile

80.7%

The version of Siemens SIMATIC WinCC (TIA Portal) installed on the remote host is 13.x prior to version 13 service pack 1 update 2 (1300.102.401.5). It is, therefore, affected by multiple vulnerabilities :

  • A man-in-the-middle attacker with access to the network path between an HMI panel and a PLC can conduct a denial of service attack against the HMI panel by sending specially crafted packets to the HMI on TCP port 102.
    This vulnerability affects SIMATIC WinCC Comfort Panels and SIMATIC WinCC Runtime Advanced. (CVE-2015-2822)

  • A remote attacker, by obtaining password hashes for SIMATIC WinCC users, can use the hashes to successfully authenticate as a valid user. (CVE-2015-2823)

Binary data scada_siemens_tia_wincc_SSA-487246.nbin
VendorProductVersionCPE
siemenssimatic_tiaportalcpe:/a:siemens:simatic_tiaportal
siemenswincccpe:/a:siemens:wincc

6.8 Medium

CVSS2

Attack Vector

NETWORK

Attack Complexity

MEDIUM

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

PARTIAL

Availability Impact

PARTIAL

AV:N/AC:M/Au:N/C:P/I:P/A:P

0.007 Low

EPSS

Percentile

80.7%

Related for SCADA_SIEMENS_TIA_WINCC_SSA-487246.NBIN