Lucene search

K
icsIndustrial Control Systems Cyber Emergency Response TeamICSA-23-285-12
HistoryOct 12, 2023 - 12:00 p.m.

Weintek cMT3000 HMI Web CGI

2023-10-1212:00:00
Industrial Control Systems Cyber Emergency Response Team
www.cisa.gov
15
weintek
cmt3000
hmi
cgi
stack-based buffer overflow
os command injection
vulnerability
exploitable
control flow
login authentication
arbitrary commands
cve-2023-38584
cvss
cwe-121
cwe-78
critical manufacturing
taiwan
update instructions
security bulletin
cisa

9.8 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

0.001 Low

EPSS

Percentile

38.1%

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 9.8 *ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Weintek
  • Equipment: cMT3000 CMI Web CGI
  • Vulnerabilities: Stack-based Buffer Overflow, OS Command Injection

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to hijack control flow and bypass login authentication or execute arbitrary commands.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Weintek products are affected:

  • cMT-FHD: OS version 20210210 or prior.
  • cMT-HDM: OS version 20210204 or prior.
  • cMT3071: OS version 20210218 or prior.
  • cMT3072: OS version 20210218 or prior.
  • cMT3103: OS version 20210218 or prior.
  • cMT3090: OS version 20210218 or prior.
  • cMT3151: OS version 20210218 or prior.

3.2 Vulnerability Overview

3.2.1 STACK-BASED BUFFER OVERFLOW CWE-121

In Weintek’s cMT3000 HMI Web CGI device, the cgi-bin command_wb.cgi contains a stack-based buffer overflow, which could allow an anonymous attacker to hijack control flow and bypass login authentication.

CVE-2023-38584 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.2 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND (‘OS COMMAND INJECTION’) CWE-78

In Weintek’s cMT3000 HMI Web CGI device, an anonymous attacker can execute arbitrary commands after login to the device.

CVE-2023-40145 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.3 STACK-BASED BUFFER OVERFLOW CWE-121

In Weintek’s cMT3000 HMI Web CGI device, the cgi-bin codesys.cgi contains a stack-based buffer overflow, which could allow an anonymous attacker to hijack control flow and bypass login authentication.

CVE-2023-43492 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Taiwan

3.4 RESEARCHER

Hank Chen (PSIRT and Threat Research of TXOne Networks) reported these vulnerabilities to CISA.

4. MITIGATIONS

Weintek recommends users follow their Upgrade Instructions to update the following products to the latest versions:

  • cMT-FHD: OS version 20210211
  • cMT-HDM: OS version 20210205
  • cMT3071: OS version 20210219
  • cMT3072: OS version 20210219
  • cMT3103: OS version 20210219
  • cMT3090: OS version 20210219
  • cMT3151: OS version 20210219

For additional information, refer to Weintek’s security bulletin.

CISA recommends users take defensive measures to minimize the risk of exploitation of this these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • October 12, 2023: Initial Publication

References

9.8 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

0.001 Low

EPSS

Percentile

38.1%

Related for ICSA-23-285-12