Lucene search

K
icsIndustrial Control Systems Cyber Emergency Response TeamICSA-23-264-06
HistorySep 21, 2023 - 12:00 p.m.

Rockwell Automation FactoryTalk View Machine Edition

2023-09-2112:00:00
Industrial Control Systems Cyber Emergency Response Team
www.cisa.gov
8
cvss v3 9.8
exploitable remotely
vendor rockwell automation
improper input validation
panelview plus
cwe-20
cve-2023-2071
critical manufacturing
worldwide deployment
united states headquarters location
yuval gordon
cps research
microsoft threat intelligence community
security patches
security best practices
cisa
vpns
impact analysis
control systems security

9.8 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

0.001 Low

EPSS

Percentile

32.5%

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 9.8 *ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Rockwell Automation
  • Equipment: FactoryTalk View Machine Edition
  • Vulnerability: Improper Input Validation

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to execute code remotely with specially crafted malicious packets or by using a self-made library to bypass security checks.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Rockwell Automation products are affected:

  • FactoryTalk View Machine Edition: v13.0
  • FactoryTalk View Machine Edition: v12.0 and prior

3.2 Vulnerability Overview

3.2.1 Improper Input Validation CWE-20

FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets. The device has the functionality, through a CIP class, to execute exported functions from libraries. There is a routine that restricts it to execute specific functions from two dynamic link library files. By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.

CVE-2023-2071 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Yuval Gordon, CPS Research, and the Microsoft Threat Intelligence Community reported this vulnerability to Rockwell Automation.

4. MITIGATIONS

Rockwell recommends updating FactoryTalk View Machine Edition with v12.0 & v13.0 patch

Users of the affected versions are encouraged by Rockwell Automation to upgrade to corrected firmware revisions. Users are also strongly encouraged to implement Rockwell Automation’s suggested security best practices to minimize the risk of the vulnerability.

For more information and to see Rockwell’s detection rules, see Rockwell Automation’s Security Advisory.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

September 21, 2023: Initial Publication

References

9.8 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

0.001 Low

EPSS

Percentile

32.5%

Related for ICSA-23-264-06