Lucene search

K
icsIndustrial Control Systems Cyber Emergency Response TeamICSA-23-033-01
HistoryFeb 02, 2023 - 12:00 p.m.

Delta Electronics DIAScreen

2023-02-0212:00:00
Industrial Control Systems Cyber Emergency Response Team
www.cisa.gov
14
cvss v3 7.8
low attack complexity
remote code execution
buffer overflow
memory restrictions
out-of-bounds write
cwe-121
cwe-119
cwe-787
cve-2023-0249
cve-2023-0250
cve-2023-0251
energy sector
worldwide deployment
taiwan
trend micro
zero day initiative
cisa recommendations

CVSS3

7.8

Attack Vector

LOCAL

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

REQUIRED

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H

EPSS

0.001

Percentile

29.7%

1. EXECUTIVE SUMMARY

  • CVSS v3 7.8 *ATTENTION: Low attack complexity
  • Vendor: Delta Electronics
  • **Equipment:**DIAScreen
  • Vulnerabilities: Stack-based Buffer Overflow, Improper Restriction of Operations within the Bounds of a Memory Buffer, Out-of-bounds Write

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow remote code execution.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of DIAScreen, a software configuration tool for Delta devices, are affected:

  • DIAScreen: versions 1.2.1.23 and prior

3.2 VULNERABILITY OVERVIEW

3.2.1 STACK-BASED BUFFER OVERFLOW CWE-121

Delta Electronics DIAScreen versions 1.2.1.23 and prior are vulnerable to a stack-based buffer overflow, which could allow an attacker to remotely execute arbitrary code.

CVE-2023-0250 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.2 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

Delta Electronics DIAScreen versions 1.2.1.23 and prior are vulnerable to a buffer overflow through improper restrictions of operations within memory, which could allow an attacker to remotely execute arbitrary code.

CVE-2023-0251 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.3 OUT-OF-BOUNDS WRITE CWE-787

Delta Electronics DIAScreen versions 1.2.1.23 and prior are vulnerable to an out-of-bounds write, which could allow an attacker to remotely execute arbitrary code.

CVE-2023-0249 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Taiwan

3.4 RESEARCHER

Natnael Samson (@NattiSamson) and YuLin Sung, working with Trend Micro’s Zero Day Initiative, reported these vulnerabilities to CISA.

4. MITIGATIONS

Delta Electronics released version 1.3.0 of DIAScreen (login required) and recommends users install this update on all affected systems.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:

  • Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls and isolate them from business networks.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities. These vulnerabilities are not exploitable remotely.

References

CVSS3

7.8

Attack Vector

LOCAL

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

REQUIRED

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H

EPSS

0.001

Percentile

29.7%

Related for ICSA-23-033-01