HistoryJan 11, 2023 - 12:00 p.m.

Hitachi Energy UNEM

2023-01-1112:00:00
Industrial Control Systems Cyber Emergency Response Team
www.cisa.gov
9
hitachi energy
unem products
inadequate encryption
hard-coded cryptographic key
cleartext transmission
vulnerabilities
remote exploit
cvss v3
des cypher
default key
public and private keys
message queue
sensitive information
availability issue

9.8 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

0.002 Low

EPSS

Percentile

59.7%

1. EXECUTIVE SUMMARY

  • CVSS v3 8.3 *ATTENTION: Exploitable remotely/low attack complexity
  • **Vendor:**Hitachi Energy
  • Equipment: UNEM
  • Vulnerabilities: Inadequate Encryption Strength, Use of Hard-coded Cryptographic Key, Cleartext Transmission of Sensitive Information.

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an unauthorized user to obtain sensitive information and gain access to the network elements managed by the UNEM and could cause availability issue on affected UNEM products.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Hitachi Energy reports these vulnerabilities affect the following UNEM products:

  • UNEM R16A
  • UNEM R15B
  • UNEM R15A
  • UNEM R14B
  • UNEM R14A
  • UNEM R11B
  • UNEM R11A
  • UNEM R10C
  • UNEM R9C

3.2 VULNERABILITY OVERVIEW

3.2.1 INADEQUATE ENCRYPTION STRENGTH CWE-326

Affected Hitachi Energy UNEM products use the DES cypher to encrypt user credentials used to access the network elements. DES is no longer considered secure because it uses a short 56-bit key, which could allow the cypher to be decrypted in a short time.

CVE-2021-40341 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N).

3.2.2 INADEQUATE ENCRYPTION STRENGTH CWE-326

Affected Hitachi Energy UNEM products use a DES implementation with a default key for encryption. An attacker that exploits this vulnerability could obtain sensitive information and gain access to the network elements managed by the UNEM.

CVE-2021-40342 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N).

3.2.3 USE OF HARD-CODED CRYPTOGRAPHIC KEY CWE-321

Affected Hitachi Energy UNEM products contain public and private keys used to sign and protect custom parameter set (CPS) files from modification. An attacker exploiting this vulnerability could change the CPS file and sign it, so that it is trusted as the legitimate CPS file.

CVE-2022-3927 has been assigned to this vulnerability. A CVSS v3 base score of 8.0 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:H/UI:N/S:C/C:H/I:H/A:H).

3.2.4 USE OF HARD-CODED CRYPTOGRAPHIC KEY CWE-321

In the message queue of affected Hitachi Energy UNEM products contains a hard-coded credential. An attacker that exploits this vulnerability could access data inside the internal message queue.

CVE-2022-3928 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N).

3.2.5 CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATION CWE-319

Communication between the client (UNEM User Interface) and the server application (UNEM Core) partially uses common object request broker architecture (CORBA) over TCP/IP. This protocol is not encrypted and could allow an unauthorized user to trace internal messages.

CVE-2022-3929 has been assigned to this vulnerability. A CVSS v3 base score of 8.3 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Switzerland

3.4 RESEARCHER

Hitachi Energy reported these vulnerabilities to CISA.

4. MITIGATIONS

Hitachi Energy remediated these vulnerabilities in UNEM R16A and recommends users upgrade to this version.

For CVE-2021-40341, CVE-2021-40342, UNEM R16A has partial remediation. The full remediation will be complete in an upcoming UNEM release.

Hitachi Energy recommends the following mitigation actions (refer to the mitigation factors/workarounds in Hitachi Energy’s advisory for details):

  • Secure the NMS CLIENT/SERVER communication.
  • Avoid embedded FOXCST with RADIUS authentication.
  • Securely handle exported files.

Hitachi Energy recommends the following security practices and firewall configurations to help protect a process control network from attacks originating from outside the network:

  • Physically protect process control systems from unauthorized direct access.
  • Do not directly connect control systems networks to the internet.
  • Separate process control systems from other networks using a firewall system with a minimal number of open ports.
  • Process control systems should not be used for internet surfing, instant messaging, or receiving emails.
  • Portable computers and removable storage media should be carefully scanned for viruses connecting to a control system.
  • Ensure that only authorized personnel have access to the system configuration files.

For more information, see Hitachi Energy advisory 8DBD000084.

Additional hardening guidelines for protecting the host operating system are published by β€œThe Center for Internet Security (CIS).”

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities. These vulnerabilities are exploitable remotely. These vulnerabilities have a low attack complexity.

References

9.8 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

0.002 Low

EPSS

Percentile

59.7%

Related for ICSA-23-005-01