Lucene search

K
icsIndustrial Control Systems Cyber Emergency Response TeamICSA-22-137-01
HistoryMay 17, 2022 - 12:00 p.m.

Circutor COMPACT DC-S BASIC

2022-05-1712:00:00
Industrial Control Systems Cyber Emergency Response Team
www.cisa.gov
52

5.5 Medium

CVSS2

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

SINGLE

Confidentiality Impact

NONE

Integrity Impact

PARTIAL

Availability Impact

PARTIAL

AV:N/AC:L/Au:S/C:N/I:P/A:P

8.1 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

LOW

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

NONE

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H

8.7 High

AI Score

Confidence

High

0.001 Low

EPSS

Percentile

31.8%

1. EXECUTIVE SUMMARY

  • CVSS v3 6.8 ***ATTENTION: **Exploitable remotely/low attack complexity
  • **Vendor:**Circutor
  • Equipment: COMPACT DC-S BASIC
  • Vulnerability: Stack-based Buffer Overflow

2. RISK EVALUATION

Successful exploitation of this vulnerability could cause a buffer overflow condition resulting in remote code execution.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Circutor COMPACT DC-S BASIC, a smart metering concentrator, are affected:

  • Circutor COMPACT DC-S BASIC: CIR_CDC_v1.2.17

3.2 VULNERABILITY OVERVIEW

3.2.1 STACK-BASED BUFFER OVERFLOW CWE-121

A buffer overflow vulnerability has been detected in the firewall function of the device management web portal. The device runs a CGI binary (index.cgi) to offer a management web application. Once authenticated with valid credentials in this web portal, a potential attacker could submit any “Address” value and it would be copied to a second variable with a “strcpy” vulnerable function without checking its length. Because of this, it is possible to send a long address value to overflow the process stack, controlling the function return address.

CVE-2022-1669 has been assigned to this vulnerability. A CVSS v3 base score of 6.8 has been assigned; the CVSS vector string is (AV:N/AC:H/PR:L/UI:N/S:U/C:N/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • **COUNTRIES/AREAS DEPLOYED:**Worldwide
  • COMPANY HEADQUARTERS LOCATION: Spain

3.4 RESEARCHER

Angel Garcia Moreno reported this vulnerability to CISA.

4. MITIGATIONS

Circutor has not responded to requests to work with CISA to mitigate this vulnerability. Users of these affected products are invited to contact Circutor customer support for additional information.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

  • Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls and isolate them from the business network.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target this vulnerability.

References

5.5 Medium

CVSS2

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

SINGLE

Confidentiality Impact

NONE

Integrity Impact

PARTIAL

Availability Impact

PARTIAL

AV:N/AC:L/Au:S/C:N/I:P/A:P

8.1 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

LOW

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

NONE

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H

8.7 High

AI Score

Confidence

High

0.001 Low

EPSS

Percentile

31.8%

Related for ICSA-22-137-01