Lucene search

K
icsIndustrial Control Systems Cyber Emergency Response TeamICSA-21-334-04
HistoryNov 30, 2021 - 12:00 p.m.

Johnson Controls CEM Systems AC2000

2021-11-3012:00:00
Industrial Control Systems Cyber Emergency Response Team
www.cisa.gov
20

7.8 High

CVSS3

Attack Vector

LOCAL

Attack Complexity

LOW

Privileges Required

LOW

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

7.9 High

AI Score

Confidence

High

7.2 High

CVSS2

Access Vector

LOCAL

Access Complexity

LOW

Authentication

NONE

Confidentiality Impact

COMPLETE

Integrity Impact

COMPLETE

Availability Impact

COMPLETE

AV:L/AC:L/Au:N/C:C/I:C/A:C

0.971 High

EPSS

Percentile

99.7%

1. EXECUTIVE SUMMARY

  • CVSS v3 7.8 ***ATTENTION: **Low attack complexity
  • **Vendor:**Controlled Electronic Management Systems, Ltd., a subsidiary of Johnson Controls, Inc.
  • **Equipment:**CEM Systems AC2000
  • **Vulnerability:**Off-by-one Error

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow a local attacker to obtain “super user” access on the underlying Linux operating system.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Controlled Electronic Management Systems Ltd. CEM Systems AC2000, an access control system, are affected:

  • CEM Systems AC2000: All versions prior to Version 10.6

3.2 VULNERABILITY OVERVIEW

3.2.1 OFF-BY-ONE ERROR CWE-193

The affected product has an off-by-one error vulnerability, which may allow an attacker to achieve “super user” access on the operating system.

CVE-2021-3156 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • **COUNTRIES/AREAS DEPLOYED:**Worldwide
  • COMPANY HEADQUARTERS LOCATION: Ireland

3.4 RESEARCHER

Johnson Controls, Inc. reported this vulnerability to CISA.

4. MITIGATIONS

Johnson Controls recommends users with AC2000 versions prior to 10.6 simply remove sudo. To do this, users may either contact a CEM support team or login to their Linux servers as root and type the following command: rpm -e sudo.

Note: AC2000 v10.6 includes a fixed version of sudo.

For more detailed mitigation instructions, please see Johnson Controls Product Security Advisory JCI-PSA-2021-20 v1

Aligning with CISA recommendations, Johnson Controls recommends taking steps to minimize risks to all building automation systems.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely.

References

7.8 High

CVSS3

Attack Vector

LOCAL

Attack Complexity

LOW

Privileges Required

LOW

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

7.9 High

AI Score

Confidence

High

7.2 High

CVSS2

Access Vector

LOCAL

Access Complexity

LOW

Authentication

NONE

Confidentiality Impact

COMPLETE

Integrity Impact

COMPLETE

Availability Impact

COMPLETE

AV:L/AC:L/Au:N/C:C/I:C/A:C

0.971 High

EPSS