icsIndustrial Control Systems Cyber Emergency Response TeamICSA-21-210-02
HistoryJul 29, 2021 - 12:00 p.m.

Wibu-Systems CodeMeter Runtime

2021-07-2912:00:00
Industrial Control Systems Cyber Emergency Response Team
www.cisa.gov
52
codemeter runtime
vulnerabilities
buffer over-read
exploitation
mitigations
sever crash
remote attack
cve-2021-20094
cve-2021-20093
wibu-systems ag
tenable inc.
cisa recommendations
security advisories
siemens
network security

CVSS2

6.4

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

NONE

Availability Impact

PARTIAL

AV:N/AC:L/Au:N/C:P/I:N/A:P

CVSS3

9.1

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

NONE

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H

AI Score

9.3

Confidence

High

EPSS

0.093

Percentile

94.7%

1. EXECUTIVE SUMMARY

  • CVSS v3 9.1 ***ATTENTION: **Exploitable remotely/low attack complexity
  • Vendor: Wibu-Systems AG
  • Equipment: CodeMeter Runtime
  • Vulnerabilities: Buffer Over-read

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to read data from the heap of the CodeMeter Runtime network server, or crash the CodeMeter Runtime Server (i.e., CodeMeter.exe).

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of CodeMeter Runtime, a license manager, are affected:

  • CodeMeter Runtime: All versions prior to v7.21a

This license manager is used in the products of many different vendors.

3.2 VULNERABILITY OVERVIEW

3.2.1 BUFFER OVER-READ CWE-126

An attacker could send a specially crafted packet to the CodeMeter Runtime CmWAN server to cause a denial-of-service condition.

CVE-2021-20094 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.2 BUFFER OVER-READ CWE-126

An attacker could send a specially crafted packet that could crash the server or direct the CodeMeter Runtime Network Server to send back packets containing data from the heap.

CVE-2021-20093 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H).

3.3 BACKGROUND

  • **CRITICAL INFRASTRUCTURE SECTORS:**Multiple
  • **COUNTRIES/AREAS DEPLOYED:**Worldwide
  • **COMPANY HEADQUARTERS LOCATION:**Germany

3.4 RESEARCHER

Tenable, Inc., reported these vulnerabilities to CISA.

4. MITIGATIONS

Wibu-Systems recommends the following mitigations:

  • Update to Version 7.21a or later.

CVE-2021-20093:

  • Run CodeMeter as client only and use localhost as binding for the CodeMeter communication. With binding to localhost an attack is no longer possible via remote network connection. The network server is disabled by default.
  • If it is not possible to disable the network server, using a host-based firewall to restrict access to the CmLAN port can reduce the risk.

CVE-2021-20094:

  • The CmWAN server is disabled by default. Check if CmWAN is enabled and disable the feature if it is not needed.
  • Run the CmWAN server only behind a reverse proxy with user authentication to prevent attacks from unauthenticated users.
  • The risk of an unauthenticated attacker can be further reduced by using a host-based firewall that only allows the reverse proxy to access the CmWAN port.

For more information on this issue, please see Wibu security advisories: WIBU-210423-01, WIBU-210423-02

For more information on products dependent on the affected CodeMeter see the following vendor security advisories. As new instances are discovered/reported, they will be added to this list:

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

  • Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities.

References

CVSS2

6.4

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

NONE

Availability Impact

PARTIAL

AV:N/AC:L/Au:N/C:P/I:N/A:P

CVSS3

9.1

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

NONE

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H

AI Score

9.3

Confidence

High

EPSS

0.093

Percentile

94.7%

Related for ICSA-21-210-02