Lucene search

K
icsIndustrial Control Systems Cyber Emergency Response TeamICSA-21-070-01
HistoryMar 11, 2021 - 12:00 p.m.

Schneider Electric IGSS SCADA Software

2021-03-1112:00:00
Industrial Control Systems Cyber Emergency Response Team
www.cisa.gov
35

9.3 High

CVSS2

Attack Vector

NETWORK

Attack Complexity

MEDIUM

Authentication

NONE

Confidentiality Impact

COMPLETE

Integrity Impact

COMPLETE

Availability Impact

COMPLETE

AV:N/AC:M/Au:N/C:C/I:C/A:C

7.8 High

CVSS3

Attack Vector

LOCAL

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

REQUIRED

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H

8.4 High

AI Score

Confidence

High

0.003 Low

EPSS

Percentile

65.8%

1. EXECUTIVE SUMMARY

  • CVSS v3 7.8 ***ATTENTION: **Low skill level to exploit
  • Vendor: Schneider Electric
  • Equipment: IGSS (Interactive Graphical SCADA System)
  • Vulnerabilities: Improper Restriction of Operations within the Bounds of a Memory Buffer

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could result in remote code execution.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following products and versions are affected:

  • IGSS Definition (Def.exe) Version 15.0.0.21041 and prior

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

This vulnerability could result in loss of data or remote code execution when a malicious CGF (configuration group file) file is imported into an IGSS Definition.

CVE-2021-22709 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.2 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

This vulnerability could result in loss of data or remote code execution when a malicious CGF file is imported into an IGSS Definition.

CVE-2021-22710 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.3 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

This vulnerability could result in arbitrary read or write conditions due to missing validation of input data when a malicious CGF file is imported into an IGSS Definition.

CVE-2021-22711 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.4 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

This vulnerability could result in arbitrary read or write conditions due to an unchecked pointer address when a malicious CGF file is imported into an IGSS Definition.

CVE-2021-22712 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Critical Manufacturing, Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: France

3.4 RESEARCHER

Kimiya, working with Trend Microโ€™s Zero Day Initiative, reported these vulnerabilities to CISA.

4. MITIGATIONS

Schneider Electric has provided Version 15.0.0.21042 of the IGSS Definition module: Def.exe to address these vulnerabilities. The update is available for download through IGSS Master > Update IGSS Software or from the Schneider Electric support page.

If users choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:

  • Avoid importing CGF files from untrusted sources.

For more information, see the Schneider Electric security notification.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01Bโ€“Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

\No known public exploits specifically target these vulnerabilities. These vulnerabilities are not exploitable remotely.

References

9.3 High

CVSS2

Attack Vector

NETWORK

Attack Complexity

MEDIUM

Authentication

NONE

Confidentiality Impact

COMPLETE

Integrity Impact

COMPLETE

Availability Impact

COMPLETE

AV:N/AC:M/Au:N/C:C/I:C/A:C

7.8 High

CVSS3

Attack Vector

LOCAL

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

REQUIRED

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H

8.4 High

AI Score

Confidence

High

0.003 Low

EPSS

Percentile

65.8%