Lucene search

K
icsIndustrial Control Systems Cyber Emergency Response TeamICSA-19-024-02
HistoryJan 24, 2019 - 12:00 p.m.

PHOENIX CONTACT FL SWITCH

2019-01-2412:00:00
Industrial Control Systems Cyber Emergency Response Team
www.cisa.gov
71

9.8 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

8 High

AI Score

Confidence

Low

6.8 Medium

CVSS2

Access Vector

NETWORK

Access Complexity

MEDIUM

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

PARTIAL

Availability Impact

PARTIAL

AV:N/AC:M/Au:N/C:P/I:P/A:P

0.028 Low

EPSS

Percentile

90.5%

1. EXECUTIVE SUMMARY

  • CVSS v3 8.8

  • ATTENTION: Exploitable remotely/low skill level to exploit

  • Vendor: PHOENIX CONTACT

  • Equipment: FL SWITCH

  • Vulnerabilities: Cross-site Request Forgery, Improper Restriction of Excessive Authentication Attempts, Cleartext Transmission of Sensitive Information, Resource Exhaustion, Incorrectly Specified Destination in a Communication Channel, Insecure Storage of Sensitive Information, and Memory Corruption

2. RISK EVALUATION

Successful exploitation of these vulnerabilities may allow attackers to have user privileges, gain access to the switch, read user credentials, deny access to the switch, or perform man-in-the-middle attacks.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Phoenix Contact reports the vulnerabilities affect the following products:

  • FL SWITCH 3xxx, 4xxx and 48xx versions prior to Version 1.35.

3.2 VULNERABILITY OVERVIEW

3.2.1 CROSS-SITE REQUEST FORGERY (CSRF) CWE-352

This vulnerability may allow an attacker to trick the web browser into transmitting unwanted commands.

CVE-2018-13993 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.2 IMPROPER RESTRICTION OF EXCESSIVE AUTHENTICATION ATTEMPTS CWE-307

The switch lacks a login time-out feature to prevent high-speed automated username and password combination guessing. An attacker may gain access by brute forcing of usernames and passwords.

CVE-2018-13990 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:L/A:L).

3.2.3 CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATION CWE-319

The default setting of the Web UI (HTTP) allows user credentials to be transmitted unencrypted.

CVE-2018-13992 has been assigned to this vulnerability. A CVSS v3 base score of 8.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:L/A:N).

3.2.4 UNCONTROLLED RESOURCE CONSUMPTION (RESOURCE EXHAUSTION) CWE-400

An attacker can initiate a web denial-of-service attack by producing an excessive number of Web UI connections.

CVE-2018-13994 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.5 INSECURE STORAGE OF SENSITIVE INFORMATION CWE-922

An attacker may extract the switch’s default private keys from its firmware image.

CVE-2018-13991 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.2.6 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER (MEMORY CORRUPTION) CWE-119

Buffer errors in the existing switch security library may allow a denial-of-service condition.

CVE-2017-3735 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.3 BACKGROUND

  • **CRITICAL INFRASTRUCTURE SECTORS:**Communications, Critical Manufacturing, Information Technology
  • **COUNTRIES/AREAS DEPLOYED:**Worldwide
  • **COMPANY HEADQUARTERS LOCATION:**Germany

3.4 RESEARCHER

Phoenix Contact, working with Evgeniy Druzhinin, Ilya Karpov, and Georgy Zaytsev of Positive Technologies, reported the vulnerabilities to CERT@VDE.

4. MITIGATIONS

Phoenix Contact recommends that users of FL SWITCH devices with affected firmware versions update the firmware to Version 1.35 or higher, which fixes these vulnerabilities. The updated firmware may be downloaded from the managed switch product page on the Phoenix Contact website. Please see the CERT VDE advisory for these vulnerabilities for the location of the new firmware download for each specific product: <https://cert.vde.com/de-de/advisories/vde-2019-001&gt;

Phoenix Contact also recommends that users using the Phoenix Contact managed FL SWITCH devices enable HTTP security.

NCCIC recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

  • Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.

NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities.

References

9.8 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

8 High

AI Score

Confidence

Low

6.8 Medium

CVSS2

Access Vector

NETWORK

Access Complexity

MEDIUM

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

PARTIAL

Availability Impact

PARTIAL

AV:N/AC:M/Au:N/C:P/I:P/A:P

0.028 Low

EPSS

Percentile

90.5%