Lucene search

K
icsIndustrial Control Systems Cyber Emergency Response TeamICSA-18-163-01
HistoryJun 18, 2018 - 12:00 p.m.

Schneider Electric U.motion Builder

2018-06-1812:00:00
Industrial Control Systems Cyber Emergency Response Team
www.cisa.gov
31

CVSS2

7.5

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

PARTIAL

Availability Impact

PARTIAL

AV:N/AC:L/Au:N/C:P/I:P/A:P

CVSS3

9.8

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

AI Score

8.4

Confidence

Low

EPSS

0.005

Percentile

75.5%

1. EXECUTIVE SUMMARY

  • CVSS v3 10.0

  • ATTENTION: Exploitable remotely/low skill level to exploit

  • Vendor: Schneider Electric

  • Equipment: U.motion Builder

  • Vulnerabilities: Command Injection, Cross-site Scripting, and Improper Input Validation

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow remote code execution.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following U.motion Builder Software versions are affected:

  • U.motion Builder versions prior to 1.3.4

3.2 VULNERABILITY OVERVIEW

3.2.1 STACK-BASED BUFFER OVERFLOW CWE-121

An input string may be evaluated as a command by the application. An attacker could exploit this to execute code, read the stack, or cause a segmentation fault in the running application.

CVE-2018-7784 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).

3.2.2 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND (OS COMMAND INJECTION) CWE-78

A remote command injection allows authentication bypass.

CVE-2018-7785 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).

3.2.3 IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION (CROSS-SITE SCRIPTING) CWE-79

A cross-site scripting (XSS) vulnerability exists, which could allow injection of malicious scripts.

CVE-2018-7786 has been assigned to this vulnerability. A CVSS v3 base score of 6.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N).

3.2.4 IMPROPER INPUT VALIDATION CWE-20

This vulnerability is due to improper validation of input of context parameter in HTTP GET request, which could allow the disclosure of sensitive information.

CVE-2018-7787 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.3 BACKGROUND

  • Critical Infrastructure Sectors: Commercial Facilities, Critical Manufacturing, and Energy
  • Countries/Areas Deployed: United States, Europe, and Asia
  • Company Headquarters Location: Paris, France

3.4 RESEARCHER

Wei Gao of Keysight and bigric3@360A-TEAM reported these vulnerabilities to NCCIC.

4. MITIGATIONS

Schneider Electric has released firmware update Version 1.3.4, which includes fixes for these vulnerabilities. It is highly recommended that U.motion Builder users apply the patch in a timely manner.

The firmware is available for download at:

<https://www.schneider-electric.com/en/download/document/Umotion_Server_update/&gt;

Schneider Electric’s security notice SEVD-2018-151-01 is available at the following location:

<https://www.schneider-electric.com/en/download/document/SEVD-2018-151-01/&gt;

NCCIC recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

  • Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.

NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities.

References

CVSS2

7.5

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

NONE

Confidentiality Impact

PARTIAL

Integrity Impact

PARTIAL

Availability Impact

PARTIAL

AV:N/AC:L/Au:N/C:P/I:P/A:P

CVSS3

9.8

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

AI Score

8.4

Confidence

Low

EPSS

0.005

Percentile

75.5%