LCDS - Leão Consultoria e Desenvolvimento de Sistemas Ltda ME LAquis SCADA
2018-04-05T00:00:00
ID ICSA-18-095-03 Type ics Reporter Industrial Control Systems Cyber Emergency Response Team Modified 2019-01-15T00:00:00
Description
1. EXECUTIVE SUMMARY
CVSS v3 7.0
Vendor: LCDS - Leão Consultoria e Desenvolvimento de Sistemas LTDA ME
Equipment: LAquis SCADA
Vulnerability: Improper Check or Handling of Exceptional Conditions
2. RISK EVALUATION
Successful exploitation of this vulnerability could cause the device an attacker is accessing to crash, resulting in a structured exception handler overflow condition, which may allow code execution.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of LAquis SCADA, an industrial automation software, are affected:
LAquis SCADA software versions 4.1.0.3391 and prior.
Critical Infrastructure Sectors: Chemical, Commercial Facilities, Energy, Food and Agriculture, Transportation Systems, Water and Wastewater Systems
Countries/Areas Deployed: South America
Company Headquarters Location: Joinville-SC, Brazil
3.4 RESEARCHER
Karn Ganeshen reported the vulnerability to NCCIC.
4. MITIGATIONS
LCDS recommends that users update to version 4.1.0.3774, which can be found at the following location:
<http://laquisscada.com/instale1.php>
NCCIC recommends that users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT website.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely. High skill level is needed to exploit.
Contact Information
For any questions related to this report, please contact the CISA at:
For industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics
or incident reporting: https://us-cert.cisa.gov/report
CISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.
This product is provided subject to this Notification and this Privacy & Use policy.
Please share your thoughts.
We recently updated our anonymous product survey; we'd welcome your feedback.
{"id": "ICSA-18-095-03", "type": "ics", "bulletinFamily": "info", "title": "LCDS - Le\u00e3o Consultoria e Desenvolvimento de Sistemas Ltda ME LAquis SCADA", "description": "## 1\\. EXECUTIVE SUMMARY\n\n * **CVSS v3 7.0**\n * **Vendor**: LCDS - Le\u00e3o Consultoria e Desenvolvimento de Sistemas LTDA ME\n * **Equipment**: LAquis SCADA\n * **Vulnerability**: Improper Check or Handling of Exceptional Conditions\n\n## 2\\. RISK EVALUATION\n\nSuccessful exploitation of this vulnerability could cause the device an attacker is accessing to crash, resulting in a structured exception handler overflow condition, which may allow code execution.\n\n## 3\\. TECHNICAL DETAILS\n\n### 3.1 AFFECTED PRODUCTS\n\nThe following versions of LAquis SCADA, an industrial automation software, are affected:\n\n * LAquis SCADA software versions 4.1.0.3391 and prior.\n\n### 3.2 VULNERABILITY\n\n### 3.2.1 [IMPROPER CHECK OR HANDLING OF EXCEPTIONAL CONDITIONS CWE-703](<https://cwe.mitre.org/data/definitions/703.html>)\n\nA structured exception handler overflow vulnerability has been identified that may allow code execution.\n\n[CVE-2018-5463](<http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-5463>) has been assigned to this vulnerability. A CVSS v3 base score of 7.0 has been calculated; the CVSS vector string is ([AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H](<https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H>)).\n\n### 3.3 BACKGROUND\n\n * Critical Infrastructure Sectors: Chemical, Commercial Facilities, Energy, Food and Agriculture, Transportation Systems, Water and Wastewater Systems\n * Countries/Areas Deployed: South America\n * Company Headquarters Location: Joinville-SC, Brazil\n\n### 3.4 RESEARCHER\n\nKarn Ganeshen reported the vulnerability to NCCIC.\n\n## 4\\. MITIGATIONS\n\nLCDS recommends that users update to version 4.1.0.3774, which can be found at the following location:\n\n<http://laquisscada.com/instale1.php>\n\nNCCIC recommends that users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:\n\n * Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.\n * Locate control system networks and remote devices behind firewalls, and isolate them from the business network.\n * When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.\n\nNCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.\n\nNCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.\n\nAdditional mitigation guidance and recommended practices are publicly available in the ICS\u2011CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT website.\n\nOrganizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.\n\nNo known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely. High skill level is needed to exploit.\n\n## \nContact Information\n\nFor any questions related to this report, please contact the CISA at: \n \nEmail: [CISAservicedesk@cisa.dhs.gov](<mailto:cisaservicedesk@cisa.dhs.gov>) \nToll Free: 1-888-282-0870\n\nFor industrial control systems cybersecurity information: https://us-cert.cisa.gov/ics \nor incident reporting: https://us-cert.cisa.gov/report\n\nCISA continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.\n\nThis product is provided subject to this Notification and this [Privacy & Use](<https://www.dhs.gov/privacy-policy>) policy.\n\n**Please share your thoughts.**\n\nWe recently updated our anonymous [product survey](<https://www.surveymonkey.com/r/CISA-cyber-survey?product=https://us-cert.cisa.gov/ics/advisories/ICSA-18-095-03>); we'd welcome your feedback.\n", "published": "2018-04-05T00:00:00", "modified": "2019-01-15T00:00:00", "cvss": {"score": 4.6, "vector": "AV:L/AC:L/Au:N/C:P/I:P/A:P"}, "href": "https://www.us-cert.gov/ics/advisories/ICSA-18-095-03", "reporter": "Industrial Control Systems Cyber Emergency Response Team", "references": ["https://twitter.com/share?url=https%3A%2F%2Fus-cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-095-03", "https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-095-03", "http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-095-03", "https://cwe.mitre.org/data/definitions/703.html", "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-5463", "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H", "http://laquisscada.com/instale1.php", "https://www.dhs.gov/privacy-policy", "https://www.surveymonkey.com/r/CISA-cyber-survey?product=https://us-cert.cisa.gov/ics/advisories/ICSA-18-095-03", "http://twitter.com/icscert", "https://www.dhs.gov", "https://www.dhs.gov/freedom-information-act-foia", "https://www.dhs.gov/homeland-security-no-fear-act-reporting", "https://www.dhs.gov/plain-writing-dhs", "https://www.dhs.gov/plug-information", "https://www.oig.dhs.gov/", "https://www.whitehouse.gov/", "https://www.usa.gov/", "https://www.dhs.gov/"], "cvelist": ["CVE-2018-5463"], "lastseen": "2021-02-27T19:51:43", "viewCount": 6, "enchantments": {"dependencies": {"references": [{"type": "cve", "idList": ["CVE-2018-5463"]}], "modified": "2021-02-27T19:51:43", "rev": 2}, "score": {"value": 5.8, "vector": "NONE", "modified": "2021-02-27T19:51:43", "rev": 2}, "vulnersScore": 5.8}}