Lucene search

K
icsIndustrial Control Systems Cyber Emergency Response TeamICSA-18-088-02
HistoryMar 29, 2018 - 12:00 p.m.

Siemens TIM 1531 IRC

2018-03-2912:00:00
Industrial Control Systems Cyber Emergency Response Team
www.cisa.gov
28

10 High

CVSS2

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

NONE

Confidentiality Impact

COMPLETE

Integrity Impact

COMPLETE

Availability Impact

COMPLETE

AV:N/AC:L/Au:N/C:C/I:C/A:C

9.8 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

0.004 Low

EPSS

Percentile

72.6%

CVSS v3 9.8

**ATTENTION:**Exploitable remotely/low skill level to exploit.

Vendor: Siemens

Equipment: TIM 1531 IRC

Vulnerability: Missing Authentication for Critical Function

AFFECTED PRODUCTS

Siemens reports that the vulnerability affects the following TIM 1531 IRC communications modules:

  • TIM 1531 IRC, all versions prior to v1.1

IMPACT

Successful exploitation may cause the device to enter a denial-of-service condition, or allow the attacker to read and manipulate data and configuration settings of the affected device.

MITIGATION

Siemens recommends updating to version 1.1 as soon as possible. The update can be found at the following location on the Siemens website:

<https://support.industry.siemens.com/cs/ww/en/view/109755374&gt;

Siemens has identified the following specific workaround and mitigation that users can apply to reduce the risk:

  • Users can limit access to Port 80/TCP and Port 443/TCP in their network infrastructure (e.g., cell protection firewall or corporate firewall) to reduce the risk.

Siemens recommends users protect network access with appropriate mechanisms. Siemens also advises that users follow recommendations in the product manuals and configure the operational environment according to Siemens’ Operational Guidelines for Industrial Security:

<https://www.siemens.com/cert/operational-guidelines-industrial-security&gt;

For more information on this vulnerability and more detailed mitigation instructions, please see Siemens Security Advisory SSA-110922 at the following location:

<http://www.siemens.com/cert/advisories&gt;

NCCIC recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

  • Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.

NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available in the NCCIC Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT website.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.

No known public exploits specifically target this vulnerability.

VULNERABILITY OVERVIEW

INCORRECT IMPLEMENTATION OF AUTHENTICATION ALGORITHM CWE-303

A remote attacker with network access to Port 80/TCP or Port 443/TCP could perform administrative operations on the device without prior authentication.

CVE-2018-4841 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

RESEARCHER

Siemens reported this vulnerability to NCCIC.

BACKGROUND

Critical Infrastructure Sectors: Chemical, Critical Manufacturing, and Food and Agriculture

Countries/Areas Deployed: Worldwide

Company Headquarters Location: Germany

References

10 High

CVSS2

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

NONE

Confidentiality Impact

COMPLETE

Integrity Impact

COMPLETE

Availability Impact

COMPLETE

AV:N/AC:L/Au:N/C:C/I:C/A:C

9.8 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

NONE

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

0.004 Low